DGA 900 online analyzer of 9 dissolved gases in transformer oil
The stationary online DGA 900 analyzer measures 9 dissolved gases and the moisture content in transformer oil. It is used for continuous diagnostics of power transformers and their OLTCs.
- Measured parameters
- 9 gases (H₂, CO, CH₄, C₂H₂, C₂H₄, CO₂, C₂H₆, O₂, N₂) and moisture content
- Method
- photoacoustic spectroscopy (PAS), no carrier gas
- H₂ range
- 5–5000 ppm
- C₂H₂ range
- 0.5–50 000 ppm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The instrument determines H₂, CO, CH₄, C₂H₂, C₂H₄, CO₂, C₂H₆, O₂ and N₂ by photoacoustic spectroscopy (PAS); no carrier gas is needed. The range for hydrogen is 5–5000 ppm and for acetylene 0.5–50 000 ppm. The analysis cycle is set from once per hour to once per 4 weeks, and a full analysis takes about 30 minutes. Power supply is 100–240 V AC or 100–250 V DC. The line includes DGA 900, DGA 900 PLUS, MULTITRANS and TAPTRANS, the last one for OLTC monitoring.
Technical specifications
| Measured parameters | 9 gases (H₂, CO, CH₄, C₂H₂, C₂H₄, CO₂, C₂H₆, O₂, N₂) and moisture content |
|---|---|
| Method | photoacoustic spectroscopy (PAS), no carrier gas |
| H₂ range | 5–5000 ppm |
| C₂H₂ range | 0.5–50 000 ppm |
| Analysis cycle | from once per hour to once per 4 weeks; full analysis about 30 min |
| Power supply | 100–240 V AC / 100–250 V DC |
| Versions | DGA 900, DGA 900 PLUS, MULTITRANS, TAPTRANS (for OLTC) |
Request a price and lead time
DGA 900 online analyzer of 9 dissolved gases in transformer oil. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 9027 10 10 00 |
|---|---|
| HS, 6 digits | 9027 10 |
| CN (EU) | 9027 10 10 |
| HTSUS (USA) | 9027 10 20 00 |
| China customs tariff | 9027 10 00 90 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
Which gases does the DGA 900 measure?
The analyzer measures 9 gases, H₂, CO, CH₄, C₂H₂, C₂H₄, CO₂, C₂H₆, O₂ and N₂, plus the moisture content of the oil.
How often does the analyzer run an analysis?
The cycle is set from once per hour to once per 4 weeks. A full analysis takes about 30 minutes.
Is there a version for OLTC monitoring?
Yes, the TAPTRANS version is produced for OLTC monitoring.