TM3 Dissolved Gas Monitor for Transformer Oil, Methane, Ethylene and Acetylene
The TM3 measures methane, ethylene and acetylene dissolved in transformer oil using laboratory-grade gas chromatography. The results suit Duval triangle analysis, which is used to assess partial discharges and developing arcing and thermal faults.
- Method
- laboratory-grade gas chromatography
- Methane CH4
- 5 to 7000 ppm, ±5 % or ±5 ppm
- Ethylene C2H4
- 3 to 5000 ppm, ±5 % or ±3 ppm
- Acetylene C2H2
- 1 to 3000 ppm, ±5 % or ±1 ppm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The monitor is installed on power transformers in generation, transmission and distribution: unit transformers at power stations, large network transformers and critical substation transformers. It is used where continuous tracking of fault gases in the oil is needed, and where gas data is compared with temperature, moisture and load of the transformer.
The measurement system is based on gas chromatography, the method specified in IEEE, ASTM, CIGRE and IEC standards for dissolved gas analysis. Measuring ranges are: methane CH4 5 to 7000 ppm with an accuracy of ±5 % or ±5 ppm, ethylene C2H4 3 to 5000 ppm with ±5 % or ±3 ppm, and acetylene C2H2 1 to 3000 ppm with ±5 % or ±1 ppm. The rate of change ranges from 0 to 805 ppm. The monitor checks its calibration automatically against a reference gas mixture traceable to NIST. It works with mineral oil and with ester-based liquids.
The standard reporting interval is four hours. If a set alarm threshold for the rate of change of concentration is exceeded, the monitor switches to hourly analysis. Oil moisture (0 to 100 % RS), oil temperature (from -40 °C to +180 °C) and transformer load can also be monitored as options.
The enclosure is NEMA 4X / IP66 and measures 55.9 × 50.8 × 28.4 cm, weighing 29.5 kg. It is mounted on a stand or on the wall of the transformer tank. Operating temperature is -50 °C to +55 °C, cold start is possible at -20 °C, storage is from -40 °C to +75 °C, and humidity is 5 to 95 % non-condensing. Oil inlet pressure is 0 to 45 psi (0 to 3 bar).
Power is 100 to 240 V AC or 125 to 250 V DC at 50/60 Hz, with 48 V DC as an option, and the maximum current is 6 A or 8 A with the 48 V option. The monitor has 2 relays and 3 analogue inputs of 4 to 20 mA. Standard interfaces are RS-232, RS-485 and optical Ethernet 100Base-FX, with options for a cellular modem, copper Ethernet 10/100Base-TX, radio and a built-in telephone modem. Protocols are ASCII, DNP3, IEC 61850, Modbus RTU, OPC and TCP/IP. It works stand-alone or as part of a substation condition monitoring system.
Technical specifications
| Method | laboratory-grade gas chromatography |
|---|---|
| Methane CH4 | 5 to 7000 ppm, ±5 % or ±5 ppm |
| Ethylene C2H4 | 3 to 5000 ppm, ±5 % or ±3 ppm |
| Acetylene C2H2 | 1 to 3000 ppm, ±5 % or ±1 ppm |
| Rate of change range | 0 to 805 ppm |
| Oil moisture (option) | 0 to 100 % RS |
| Oil temperature (option) | -40 °C to +180 °C |
| Insulating fluid | mineral oil, ester-based liquids |
| Operating temperature | -50 °C to +55 °C |
| Cold start | -20 °C |
| Storage temperature | -40 °C to +75 °C |
| Humidity | 5 to 95 % RH, non-condensing |
| Oil inlet pressure | 0 to 45 psi (0 to 3 bar) |
| Enclosure | NEMA 4X / IP66 |
| Dimensions | 55.9 × 50.8 × 28.4 cm |
| Weight | 29.5 kg |
| Power supply | 100 to 240 V AC or 125 to 250 V DC, 50/60 Hz, option 48 V DC |
| Inputs and outputs | 2 relays, 3 analogue inputs 4 to 20 mA |
| Interfaces and protocols | RS-232, RS-485, 100Base-FX; ASCII, DNP3, IEC 61850, Modbus RTU, OPC, TCP/IP |
Part numbers
Show all part numbers (7)
TM3, 900-0153-00, 900-0156-00, 900-160-00, 900-0075-02, 900-0057-01, 900-0138-00
Request a price and lead time
TM3 Dissolved Gas Monitor for Transformer Oil, Methane, Ethylene and Acetylene. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How often does the monitor report gas data?
The standard reporting interval is four hours. If a set alarm threshold for the rate of change is exceeded, the monitor switches to hourly analysis.
Is the TM3 suitable for transformers filled with ester fluid?
Yes. The monitor analyses dissolved gases in mineral oil and in ester-based insulating fluids.
How does the TM3 connect to a substation control system?
Through RS-232, RS-485 or optical Ethernet 100Base-FX, using DNP3, IEC 61850, Modbus RTU, OPC or TCP/IP protocols.