Gen3 PDM Online Partial Discharge and SF6 Gas Density Monitoring for GIS Substations

Continuous on-line supervision of gas-insulated switchgear, combining UHF partial discharge detection with SF6 gas density measurement. A single Gen3 PDM installation scales to 2,000 UHF PD sensors and 4,000 gas density sensors, with arc detection and HV test capture as add-on modules.

Purpose
on-line partial discharge and gas density monitoring of GIS
PD sensors
up to 2,000 UHF
Gas density sensors
up to 4,000
Hardware
PDMG-RH-Gen3

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

On the hardware side the system is built around the PDMG-RH-Gen3 unit, which collects signals from up to 2,000 UHF partial discharge sensors and up to 4,000 gas density sensors. Filtering is set channel by channel, so each sensor can be tuned to the noise picture of its own substation, and alarm thresholds, trend charts and stored history are available for every point.

Why fit it at all? Gas-insulated switchgear gives little warning before an internal flashover, and an SF6 leak is both a reliability and an environmental problem. Gen3 PDM spots partial discharge and arcing as it happens, classifies the fault and keeps the record needed for condition-based maintenance.

Two modules extend the basic set-up. Arc detection is enabled through software and narrows down where a flashover took place. The HV testing module captures PD events while the switchgear is under voltage stress, for instance during commissioning or after repair work.

Substation SCADA links are made over Modbus, DNP3 or IEC 61850, and remote access and diagnostics run through the DMS platform. The system ships with its own software for configuration and data review.

Layouts are flexible enough to suit different GIS arrangements, both on new builds and as a retrofit to switchgear already in service. For a quotation, tell us the GIS type and voltage level, the number of bays and the number of gas compartments.

Technical specifications

Purposeon-line partial discharge and gas density monitoring of GIS
PD sensorsup to 2,000 UHF
Gas density sensorsup to 4,000
HardwarePDMG-RH-Gen3
FunctionsPD and arc detection, fault classification, trending, alarm thresholds, history
Filteringconfigurable per sensor
Optionsarc detection module; HV testing module
ProtocolsModbus, DNP3, IEC 61850
Remote accessDMS platform
Installationnew GIS and retrofit

Request a price and lead time

Gen3 PDM Online Partial Discharge and SF6 Gas Density Monitoring for GIS Substations. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many sensors can one Gen3 PDM system handle?

Up to 2,000 UHF partial discharge sensors and up to 4,000 gas density sensors.

Which protocols are available for SCADA integration?

Modbus, DNP3 and IEC 61850, with remote access and diagnostics through the DMS platform.

Is Gen3 PDM suitable for switchgear already in service?

Yes, it is used both on new GIS and as a retrofit, and the layout adapts to different switchgear arrangements.