ISGM Online SF6 Gas Density Monitoring for Switchgear, Gas Insulated Lines and Breakers
iSGM brings separate SF6 gas density sensors together in one networked monitoring system, from a single gas compartment on a breaker to thousands of compartments on the largest switchgear. It collects gas parameters, raises alarms and reports automatically, and supports maintenance decisions.
- Type
- Networked SF6 gas density monitoring system
- Scale
- From one gas compartment to thousands of compartments
- Parameters
- TCP, density, temperature, pressure, dew point, humidity
- Sensor inputs
- 4-20 mA or MODBUS
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The system is applied at substations and gas insulated switchgear (GIS), and it is also used for gas insulated transformers (GIT), gas insulated lines (GIL) and gas operated circuit breakers (GCB). It scales from monitoring one gas compartment on a single breaker up to thousands of compartments on large switchgear. iSGM integrates with partial discharge monitoring, arc detection and localisation, breaker monitoring and enterprise analytics software.
The system collects gas parameters: temperature-compensated pressure (TCP), density, temperature, pressure, dew point and humidity. The parameters available depend on the sensors fitted to the equipment. Any SF6 density monitor with a 4-20 mA or MODBUS output can be connected to the system.
Real-time automatic alarms are generated for time to refill, time to lock-out and fast changing events, and ranking tables are produced. The data hierarchy allows indicators and alarms to be viewed for a single sensor or as summaries by equipment, by substation and across all substations of a utility. At each level the system ranks the gas zones with the largest leaks in real time and keeps account of SF6 emissions and leak rate since the start of the year and over the year. A report generator can be configured and automatically prepares emission reports for environmental authorities.
The software runs as a web version or in a client-server architecture, and alerts are sent by SMS and e-mail. The system supports IEC 61850 and integration with SCADA / PI and with the systems of environmental authorities. On the hardware side, a cabinet with a local HMI panel and an uninterruptible power supply is supplied, together with weatherproof enclosures for network nodes where there is no room in the breaker cabinets.
Technical specifications
| Type | Networked SF6 gas density monitoring system |
|---|---|
| Scale | From one gas compartment to thousands of compartments |
| Parameters | TCP, density, temperature, pressure, dew point, humidity |
| Sensor inputs | 4-20 mA or MODBUS |
| Alarms | Time to refill, time to lock-out, fast changes |
| Notifications | SMS, e-mail |
| Protocols and integration | IEC 61850, SCADA / PI |
| Software | Web version or client-server |
| Hardware | Cabinet with local HMI and UPS, weatherproof enclosures for network nodes |
| Applications | GIS, GIT, GIL, GCB |
Part numbers
Show all part numbers (1)
iSGM
Request a price and lead time
ISGM Online SF6 Gas Density Monitoring for Switchgear, Gas Insulated Lines and Breakers. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can SF6 density sensors that are already installed be connected?
Yes, the system accepts signals from any SF6 density monitor with a 4-20 mA or MODBUS output.
Does the system send data to the substation SCADA?
Yes, it supports IEC 61850 and integration with SCADA and PI.
Does the system prepare SF6 emission reports?
Yes, it keeps account of emissions and leak rate for the year and automatically prepares reports for environmental authorities.