FALCON MK II partial discharge monitoring system for MV switchgear, up to 40 channels
FALCON MK II is a modular system for centralised monitoring of partial discharge, enclosure contact temperature and humidity in medium voltage switchgear. A single 19” 6U module hosts up to 40 channels, enough to watch up to 20 switchgear units in one substation.
- Number of channels
- up to 40
- Construction
- 19” 6U rack mount module
- Switchgear units monitored
- up to 20
- Partial discharge sensors
- HFCT, TEV antenna, UHF, airborne and contact ultrasonic
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
FALCON MK II is designed for large clusters of switchgear in medium voltage substations. It receives partial discharge signals from sensors on the equipment, then processes and stores them. The installation is non-intrusive and centralised, so one system can cover a whole cluster, while enclosure contact temperature and humidity are monitored alongside partial discharge.
The instrument is modular. Up to 40 channels fit in a standard 19” rack mount module of 6U, which is enough to watch up to 20 switchgear units in one substation. Sensor options include HFCT clamps, TEV antennas, UHF sensors and ultrasonic sensors, both airborne and contact types. The acquisition interval can be set anywhere from 2 minutes to 30 minutes.
Full signal waveforms are captured and processed with the patented T/F-Map technology, which raises the signal to noise ratio and separates signals that come from different sources. Processing is integrated and fast, and the front end has ultra-wide bandwidth. Acquisition and analysis of partial discharge data run automatically, and alarms are triggered by the trend of each recorded phenomenon.
The system also includes the MTCLog 100 unit, which tracks the temperature of switchgear enclosures to detect possible overheating. Watching several switchgear units together helps link faults or failures to rising panel temperatures, and overheated components in medium voltage switchgear can lead to failure or even fire. The MTCLog 100 handles up to 40 temperature channels with PT100 Tipo A and Tipo B sensors to IEC 60751. It works as an OPC-UA server and connects to a SCADA platform.
Technical specifications
| Number of channels | up to 40 |
|---|---|
| Construction | 19” 6U rack mount module |
| Switchgear units monitored | up to 20 |
| Partial discharge sensors | HFCT, TEV antenna, UHF, airborne and contact ultrasonic |
| Processing technology | T/F-Map |
| Acquisition interval | 2 to 30 minutes |
| Temperature sensors | PT100 Tipo A and Tipo B to IEC 60751 |
| MTCLog 100 temperature channels | up to 40 |
| Protocol | OPC-UA server |
| Application | MV and LV switchgear, MV substations |
Part numbers
Show all part numbers (2)
FALCON MK II, MTCLog 100
Request a price and lead time
FALCON MK II partial discharge monitoring system for MV switchgear, up to 40 channels. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many switchgear units can one FALCON MK II system monitor?
Up to 20 switchgear units in a substation, using up to 40 channels in a 19” 6U module.
Which sensors can be connected?
HFCT clamps, TEV antennas, UHF sensors and airborne or contact ultrasonic sensors, plus PT100 Tipo A and Tipo B temperature sensors to IEC 60751.
How does the system send data to the control level?
The MTCLog 100 unit works as an OPC-UA server and connects to a SCADA platform.