QPDM online partial discharge monitor for transformers and GIS, UHF 300–2100 MHz
The QPDM provides continuous online partial discharge monitoring in power transformers and small gas-insulated switchgear (GIS), using ultra high frequency (UHF) detection. It offers -80 dBm sensitivity across a 300–2100 MHz band, a 70 dB dynamic range, and alarm and data output over IEC 61850 or Modbus.
- Purpose
- online partial discharge monitoring of transformers and small GIS
- Technology
- ultra high frequency (UHF)
- Sensitivity
- -80 dBm
- Frequency band
- 300–2100 MHz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Partial discharges in the insulation of a transformer or gas-insulated switchgear appear long before a breakdown. The QPDM records them in real time while the equipment stays in service, so an insulation fault can be found at an early stage, repairs can be planned, and an emergency failure with loss of supply can be avoided.
The system works in the ultra high frequency (UHF) range. Its built-in sensitivity is -80 dBm, and the frequency selection band covers 300–2100 MHz. The 70 dB dynamic range is designed for analysing discharges with a wide spread of amplitudes. The circuit has strong interference immunity, so measurements are possible at outdoor substations and in difficult conditions.
An embedded human-machine interface handles storage, display and interpretation of results. Optional 2D and 3D PRPD and PRPS displays are referenced to the voltage phase, and real-time PRPD and STT views are also available. The package includes a library of typical defects for comparing recorded patterns.
Data are written to a solid-state drive and kept for up to 5 years. The instrument runs automatic self-diagnostics with a log and alarm, and the user sets the alarm criteria. Alarms and data pass to SCADA or an asset management system over IEC 61850 or Modbus, and settings and review are available remotely.
Typical uses include power transformers, GIS, retrofits to operating installations, condition monitoring and asset management systems, utility substations and high-voltage networks, and outdoor installation. The manufacturer offers flexible mounting and configuration options for each site, as well as expert analysis of partial discharge data as a service.
Technical specifications
| Purpose | online partial discharge monitoring of transformers and small GIS |
|---|---|
| Technology | ultra high frequency (UHF) |
| Sensitivity | -80 dBm |
| Frequency band | 300–2100 MHz |
| Dynamic range | 70 dB |
| Data display | 2D, 3D, PRPD and PRPS with phase reference; real-time PRPD and STT (optional) |
| Data storage | solid-state drive, up to 5 years |
| Self-diagnostics | automatic, with log and alarm |
| Alarms | user-configurable criteria |
| Communication protocols | IEC 61850 or Modbus |
| Remote access | remote monitoring and configuration |
Request a price and lead time
QPDM online partial discharge monitor for transformers and GIS, UHF 300–2100 MHz. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the transformer need to be shut down for measurement?
No, the QPDM works online at operating voltage and records partial discharges continuously.
How is data passed to the upper level?
Alarms and data are output over IEC 61850 or Modbus, and settings are available remotely.
How long is data archived?
Data are written to a solid-state drive and kept for up to 5 years.