PDMG-RH Gen3 UHF partial discharge monitoring system for GIS, up to 2000 sensors
The PDMG-RH Gen3 is a permanent partial discharge monitoring system for gas insulated switchgear (GIS) that uses UHF sensors and is certified to IEC 61850. It serves up to 2000 UHF partial discharge sensors and up to 4000 gas density sensors.
- UHF partial discharge sensors
- up to 2000
- Gas density sensors
- up to 4000
- Frequency band
- 300–2000 MHz
- Sensitivity
- −80 dBm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The bandwidth is 300–2000 MHz with a sensitivity of −80 dBm and a dynamic range of 70 dB. The standard optical unit, OCU, works in the 300–1500 MHz band with a range of −75 to −30 dBm, while the HDR OCU works across 300–2000 MHz with a range of −80 to −10 dBm. The RDC unit has 7 UHF channels, six for sensor inputs and one for an external antenna, and it accepts voltage transformer signals and switching signals. The optional Arc Monitor software uses the UHF sensors already installed to detect and locate arc flashovers, so healthy sections can be re-energised more quickly.
Internal or external UHF sensors pick up partial discharge signals. Each channel has its own filter and gain control: band-pass or programmable filters, gating, coincidence filtering and notch filtering. Data goes to the Expert program, where a neural network separates noise and assigns the signal to one of six types of GIS defect with a confidence level: protrusion on the conductor, protrusion on the enclosure, floating parts with poor electrical contact, free particles, cavities between screens and insulation, and voids and tree-like breakdowns in the insulation. Together with amplitude, discharge frequency and trend, this forms the basis for risk assessment.
Control is handled from a central computer with a backup system, a 21.5 inch screen, keyboard and mouse. Timestamps come from NTP over the local network or from GPS, and data is kept on solid-state storage for up to 5 years. The unit provides 3 standard SCADA or SCS alarm contacts and 5 more that can be configured, plus 8 status LEDs, a remote Ethernet client, and data and alarm reporting through IEC 61850 and Modbus. It runs from 110 V at 50/60 Hz and 250 mA, operates from −25 to 55 °C at humidity up to 100 % including condensing conditions, and the equipment is tested for immunity and emissions against industrial standards at raised levels.
Partial discharge is an early indicator of most causes of GIS failure, so continuous monitoring under operating voltage is the basis of condition-based maintenance. The system is installed at high-voltage substations, power stations and critical industrial sites, is suitable for upgrading existing installations, and is compatible with GIS from most leading manufacturers.
Technical specifications
| UHF partial discharge sensors | up to 2000 |
|---|---|
| Gas density sensors | up to 4000 |
| Frequency band | 300–2000 MHz |
| Sensitivity | −80 dBm |
| Dynamic range | 70 dB |
| Standard OCU | 300–1500 MHz, −75…−30 dBm |
| HDR OCU | 300–2000 MHz, −80…−10 dBm |
| RDC inputs | 7 UHF channels (6 sensors + 1 external antenna) |
| Filtering | band-pass or programmable, gating, coincidence, notch |
| Alarms | 3 standard SCADA/SCS + 5 configurable |
| External interfaces | Ethernet, IEC 61850, Modbus |
| Indication | 8 status LEDs |
| Time sync | NTP over LAN or GPS |
| Data storage | SSD, up to 5 years |
| Power supply | 110 V 50/60 Hz, 250 mA |
| Operating temperature | −25…55 °C |
| Humidity | up to 100 % with condensation |
Part numbers
Show all part numbers (1)
PDMG - RH - Gen 3
Request a price and lead time
PDMG-RH Gen3 UHF partial discharge monitoring system for GIS, up to 2000 sensors. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the system be installed on existing GIS from another manufacturer?
Yes, the system suits upgrades and is compatible with GIS from most leading manufacturers, working with internal and external UHF sensors.
How does the system send alarms to SCADA?
Through 3 standard and 5 configurable alarm contacts, with data and alarm reporting over IEC 61850 and Modbus.
Can the system locate an arc flashover?
Yes, with the Arc Monitor software option, which uses the UHF sensors already installed.