International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

TPM Air 24 kV SF6-free ring main unit with dry air insulation

Ring main unit (RMU) for medium voltage networks, Ur 24 kV. Dry air insulation and vacuum switching, with no SF6. Rated current 630 A, short-time withstand current up to 20 kA (1 s), internal arc class AFLR.

Rated voltage Ur
24 kV (L panel: 25 kV)
Rated frequency
50/60 Hz
Power-frequency withstand voltage Ud
50/60 kV
Lightning impulse withstand voltage Up
125/145 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

TPM Air is a ring main unit for medium voltage distribution networks that insulates with dry air and switches in vacuum. Only natural components of atmospheric air are used, so the insulating medium has no global warming potential (GWP) and meets current environmental requirements as well as future greenhouse gas regulations. It carries over the proven concept of the TPM switchgear.

The unit is built from panels for different purposes: line panels (L), transformer panels with disconnectors and fuses (T), circuit breaker panels (W), coupling panels (S) and measuring panels (M). A switchboard is easily extended with further sets, which should be stated when ordering, and each set can be made expandable. An L panel can be a single module with an expansion option or can share a tank with other configurations, up to four fields. The unit can be adapted to remote control and measurement systems, for example SmartGrid.

The devices are inside a stainless, acid-resistant steel tank filled with dry air under overpressure. The sealed design needs no maintenance throughout its service life. Protection is IP 67 for the tank, IP 4X for the drive and connection compartment, and IP4X for the unit (IP54 optional), with impact resistance IK10. A pressure gauge with a two-zone scale is fitted, and each tank has a safety valve that vents arc gases downwards into the cable duct, away from personnel.

The L panel has a three-position disconnector-earthing switch on common moving contacts, with a shunt current interruption system in a vacuum chamber while disconnecting. It has a manual drive, a synoptic status display, C-type bushings with M16 thread and capacitive dividers for LRM voltage indicators and electromagnetic interlocks, and mechanical locks on the cable compartment covers: a cover comes off only after the earthing switch is closed. Disconnector class is M2, E3, C2 and earthing switch class M1, E2. In the T panel the disconnectors work with fuses, and a quick earthing device earths the fuse link on both sides.

Options include a 24 V DC motor drive (other voltages on request) that can be retrofitted on site, a density meter with auxiliary contacts, low-power voltage sensors, current transformers, current sensors and Rogowski coils, earth fault transformers, short-circuit indicators, an auxiliary circuit cabinet, indicator lights, anti-condensation heaters, key and electromagnetic locks, surge arresters and AST-05 wireless temperature sensors of the eTemp system. Standards: PN-EN 62271-1, -200, -100, -102, -103, -105 and -213.

Technical specifications

Rated voltage Ur24 kV (L panel: 25 kV)
Rated frequency50/60 Hz
Power-frequency withstand voltage Ud50/60 kV
Lightning impulse withstand voltage Up125/145 kV
Rated current Ir630 A (T panel: 250 A, 125 A fuse insert)
Short-time withstand current Ikup to 20 kA (1 s)
Peak current Ipup to 50 kA
Internal arc class IACAFLR
Degree of protectionIP4X (IP54 optional)
Resistance to mechanical impactIK10
Apparatus compartment stainless steel tankIP 67
Drive and connection compartmentIP 4X
Ambient temperature, peak short-term+ 40 °C
Lowest temperature without secondary circuits- 25 °C
Lowest temperature with secondary circuits- 5 °C / - 15 °C / - 25 °C
Relative humidity, 24-hour / monthly average95% / 90%
Disconnector classM2, E3, C2
Earthing switch classM1, E2
Panel typesL, T, W, S, M

Request a price and lead time

TPM Air 24 kV SF6-free ring main unit with dry air insulation. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Is SF6 used in TPM Air?

No. Insulation is dry air under overpressure in a stainless steel tank, and switching takes place in vacuum.

Which panels can a TPM Air be built from?

Line (L), transformer with fuses (T), circuit breaker (W), coupling (S) and measuring (M) panels. L fields can share one tank, up to four fields.

What are the rated current and arc rating?

Rated current is 630 A, short-time withstand current up to 20 kA (1 s), internal arc class AFLR and degree of protection IP4X (IP54 optional).

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides