Rotoblok SF 20 kV medium voltage switchgear with SF6 switching devices
Indoor two-compartment switchgear for three-phase 50 Hz distribution networks, rated 20 kV with a highest equipment voltage of 25 kV. The three-position disconnectors and switch disconnectors are SF6 insulated. Rated current 630 A, internal arc withstand 16 kA (1 s).
- Rated network voltage
- 20 kV
- Highest device voltage
- 25 kV
- Rated frequency / number of phases
- 50 Hz / 3
- Rated short-time network frequency withstand voltage
- 50 kV / 60 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Rotoblok SF is an indoor switchgear for three-phase alternating current at 50 Hz and voltages up to 25 kV, used in industrial and commercial power distribution networks. It is configured from standard single modules with varied equipment. The published data let a designer assemble a line-up from typical bays, while bays with other equipment or changed dimensions are agreed with the manufacturer.
Each bay has two compartments that separate the primary busbars from the cable connections, and the line-up uses a single busbar system. The enclosure is air-insulated (AIS) and made of zinc-coated sheet metal, which gives equipotential bonding. The switching devices are three-position disconnectors and switch disconnectors insulated with SF6, in stainless steel tanks.
Bays use GTR SF disconnectors and switch disconnectors and VCB GIS circuit breakers, or equipment from other leading manufacturers. For transformer switching with GTR SF 2V and GTR SF 2VM switch disconnectors, a 6 kV network (77 A) corresponds to a maximum transformer power of 800 kVA.
Bay types include line feeders SL1 and SL2, transformer feeder ST2, metering unit SP1, lightning arrester unit SO1, bus coupler units SS1L and SS2L, plus circuit breaker bays SWG1 (feeder), SWTp (transformer feeder, also with voltage measurement) and SWS1 (bus coupler with disconnectors and circuit breaker). An auxiliary transformer bay is also listed. Bay masses: SL1175 kg, SL2190 kg, ST2210 kg, SP1390 kg, SS1L 265 kg, SS2L 465 kg, SO1100 kg.
Reinforced bay construction (enclosures, locks, hinges) and an arc-proof design protect against internal arcing. Mechanical interlocks stop incorrect switching and contact with live parts, and the operator can reach control gear and circuits without touching primary parts. The three-position on-off-earth devices have mechanical position indicators, and the fast earthing switch has an impulse drive that keeps an incorrect closing onto a short circuit safe. Wall mounting is possible. Standards: (PN-EN) IEC 62271-1, -200, -100, -102, -103 and -105; certified by the Electrotechnical Institute.
Technical specifications
| Rated network voltage | 20 kV |
|---|---|
| Highest device voltage | 25 kV |
| Rated frequency / number of phases | 50 Hz / 3 |
| Rated short-time network frequency withstand voltage | 50 kV / 60 kV |
| Rated withstand lightning surge voltage 1.2/50 μs | 125 kV / 145 kV |
| Continuous rated current | 630 A |
| Rated short-time withstand current | 20 kA (1 s) |
| Rated peak withstand current | 50 kA |
| Resistance to internal arc effects | 16 kA (1 s) |
| IP protection rating | IP4X |
| Ambient temperature, peak short-time | + 40 °C |
| Ambient temperature, highest annual average | + 20 °C |
| Relative humidity, day / month average | 95% / 90% |
| Vapour pressure, day / month average | 2.2 kPa / 1.8 kPa |
| Installation altitude | up to 1000 m a.s.l. |
| Transformer on a 6 kV network (GTR SF 2V, 2VM switch disconnectors) | 77 A, 800 kVA |
| Bay mass | SL1175 kg, SL2190 kg, ST2210 kg, SP1390 kg, SS1L 265 kg, SS2L 465 kg, SO1100 kg |
Request a price and lead time
Rotoblok SF 20 kV medium voltage switchgear with SF6 switching devices. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How are the switching devices of Rotoblok SF insulated?
The three-position disconnectors and switch disconnectors are SF6 insulated in stainless steel tanks, while the switchgear enclosure itself is air-insulated (AIS).
What are the main ratings?
Rated network voltage 20 kV, highest equipment voltage 25 kV, rated current 630 A, short-time withstand current 20 kA (1 s), peak 50 kA, internal arc withstand 16 kA (1 s) and degree of protection IP4X.
Can the switchgear be mounted against a wall?
Yes. Wall mounting saves space in the switch room, which matters most when existing stations are refurbished or extended.