RELF 2S 12 kV double busbar medium voltage switchgear
Air-insulated, metal-clad, withdrawable switchgear for indoor primary distribution at 12 kV. Two busbar systems, busbar and incoming feeder current 630–2500 A, internal arc withstand 31.5 kA/1 s.
- Rated voltage
- 12 kV
- Busbar and incoming feeder rated continuous current
- 630, 1250, 1600, 2000, 2500 A
- Rated power-frequency withstand voltage
- 28 kV
- Rated lightning impulse withstand voltage
- 75 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
RELF 2S is a free-standing, air-insulated switchgear rated 12 kV for use indoors. The cubicles are metal-clad and modular, and the main devices sit on withdrawable modules. It serves primary distribution in industrial distribution stations and in the generation and distribution sector, under the normal service conditions defined in IEC 62271-1.
Two busbar systems make it possible to build complex supply arrangements. A line-up is assembled from functional bays: feeder bays with a circuit breaker (optionally with voltage measurement), a transverse bus coupler bay, a longitudinal two-cubicle bus coupler bay with a circuit breaker and sectionaliser, a metering bay and a feeder bay with a switch disconnector, which can feed an auxiliary transformer. Other bay types and special equipment are agreed with the manufacturer.
A withdrawable module can carry a circuit breaker, a contactor, a sectionaliser or a set of fused voltage transformers, and it can be set to the service, test/disconnection or separation position. The main switches and the module come with manual or electric drives, depending on the bay configuration, and electric drives for remote control of all switches are optional. Current and voltage sensors can be fitted.
The frame-less, self-supporting structure is built from zinc-coated riveted steel sheet. Each bay has separate compartments: busbars of system I and system II, disconnectors of each system, the main device, the cables, the low-voltage auxiliary circuits and an internal pressure relief and blow-out duct. An optional gas exhausting duct carries gases outside the switching room. The internal arc classification is IAC AFLR.
Safe operation rests on interlocks between switching and door opening, racking of the module with the doors closed, inspection windows for checking the switches visually, partitions between compartments and a bay voltage indication system. Rear doors open up the cables and instrument transformers, and removable inspection plates give access to the disconnectors. The switchgear complies with IEC 62271-200 and IEC 60529 and is certified by accredited bodies.
Technical specifications
| Rated voltage | 12 kV |
|---|---|
| Busbar and incoming feeder rated continuous current | 630, 1250, 1600, 2000, 2500 A |
| Rated power-frequency withstand voltage | 28 kV |
| Rated lightning impulse withstand voltage | 75 kV |
| Rated frequency | 50 Hz |
| Rated short-time withstand current | 31.5 kA/3 s |
| Rated peak withstand current | 80 kA |
| Internal arc withstand | 31.5 kA/1 s, IAC AFLR |
| Degree of protection | up to IP4X |
| Cubicle width | 650, 800, 800, 800, 1100, 1100 mm |
| Cubicle depth | 1800 mm |
| Compliance with standards | (PN-EN) IEC 62271-200; (PN-EN) IEC 62271-1; (PN-EN) IEC 60529 |
Request a price and lead time
RELF 2S 12 kV double busbar medium voltage switchgear. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What busbar and incoming feeder currents are available?
630, 1250, 1600, 2000 or 2500 A, at a rated voltage of 12 kV and a frequency of 50 Hz.
What are the short-circuit and internal arc ratings?
Rated short-time withstand current is 31.5 kA/3 s, rated peak withstand current 80 kA, and internal arc withstand 31.5 kA/1 s with classification IAC AFLR.
What are the cubicle dimensions?
Depth is 1800 mm, and width is 650, 800 or 1100 mm depending on the bay type. The gas exhausting duct is an optional extra.