Rotoblok Air 24 kV dry air insulated switchgear, SF6-free

Two-compartment indoor switchgear for voltages up to 24 kV. The switching devices sit in sealed stainless steel tanks filled with dry air under overpressure, with no SF6. Rated current 630 A, internal arc withstand 16 kA (1 s).

Rated voltage
24 kV
Maximum voltage of devices
25 kV
Rated frequency / number of phases
50 Hz / 3
Rated short-time withstand voltage at mains frequency
50 kV / 60 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Rotoblok Air answers the market demand for less fluorinated gas in medium voltage switchgear. Its switching devices use dry air insulation, and the voltage range is up to 24 kV. Typical sites are commercial power engineering, industry and municipal infrastructure.

The switchgear is an indoor, air-insulated (AIS) assembly with two compartments per bay, one for the busbar and one for the cables, inside a galvanised sheet metal enclosure with a single busbar system. The devices are housed in sealed stainless steel tanks. The insulating medium is dry air under overpressure, so SF6 is not used.

Each bay is an independent module, which simplifies design, assembly and operation and allows any number of bays in a line-up. Depending on the bay, it contains a three-position disconnector-earthing switch with a vacuum chamber system, a three-position disconnector-earthing switch or a vacuum circuit breaker. The device types are GT Air 1 and GT Air 4 (three-position disconnector with earthing switch), GT Air 2V (three-position switch with earthing switch and fuses) and VCB Air (a multifunctional device with a built-in vacuum switch and a three-position disconnector with earthing switch). Devices from other manufacturers can be fitted.

The enclosure is arc-resistant, with reinforced covers, locks and hinges. Mechanical interlocks prevent incorrect switching and contact with live parts, and position is shown by mechanical and electrical indicators and sight glasses. The three-position on-off-earth devices carry mechanical position indicators, and the fast-acting earthing switches have a step drive.

Compared with switchgear built on air-insulated devices, the dimensions are smaller at the same insulation level, rated current and short-circuit withstand. Wall-mounted installation saves floor space when switch rooms are modernised or extended. Cable connections need a cable duct, and a raised plinth or technical floor is possible. AST-05 wireless temperature sensors are optional. The design follows PN-EN 62271-1, -200, -100, -102, -103, -105 and -213.

Technical specifications

Rated voltage24 kV
Maximum voltage of devices25 kV
Rated frequency / number of phases50 Hz / 3
Rated short-time withstand voltage at mains frequency50 kV / 60 kV
Rated withstand lightning impulse voltage 1.2/50 μs125 kV / 145 kV
Rated continuous current630 A
Rated short-time withstand currentup to 20 kA (1 s)
Rated peak current withstandup to 50 kA
Internal arc resistance16 kA (1 s)
IP protection ratingIP3X
Ambient temperature, peak short-term+ 40 °C
Ambient temperature, highest 24-hour average+ 35 °C
Ambient temperature, highest annual average+ 20 °C
Ambient temperature, lowest long-term- 25 °C
Relative humidity, 24-hour / monthly average95% / 90%
Installation heightup to 1000 m a.s.l.
Device typesGT Air 1, GT Air 4, GT Air 2V, VCB Air

Request a price and lead time

Rotoblok Air 24 kV dry air insulated switchgear, SF6-free. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does Rotoblok Air use SF6?

No. The devices are in sealed stainless steel tanks filled with dry air under overpressure.

What are the main ratings?

Rated voltage 24 kV (highest voltage for equipment 25 kV), rated current 630 A, short-time withstand current up to 20 kA (1 s), peak up to 50 kA and internal arc withstand 16 kA (1 s).

Which devices can be installed in the bays?

GT Air 1, GT Air 4, GT Air 2V or VCB Air: three-position disconnectors with earthing switch, a switch with fuses, or a vacuum circuit breaker unit.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides