International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Rotoblok VCB 25 kV switchgear with three-function TGI device

Indoor two-compartment switchgear for 50 Hz networks, rated 20 kV with a highest equipment voltage of 25 kV. The TGI device combines circuit breaker, disconnector and earthing switch, giving a basic bay width of 500 mm at 630 A.

Rated network voltage
20 kV
Highest device voltage
25 kV
Rated frequency / number of phases
50 Hz / 3
Rated short-time network frequency withstand voltage
50 kV / 60 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Rotoblok VCB is an indoor switchgear for three-phase alternating current at 50 Hz and voltages up to 25 kV, intended for industrial and commercial power distribution networks. Its modular bays can be combined in any configuration with bays from the Rotoblok and Rotoblok SF ranges.

The line-up is air-insulated (AIS), with two compartments per bay, a single busbar system and a zinc-coated sheet metal enclosure. Its compact size comes from the TGI device, a three-function unit that takes the place of a circuit breaker, a disconnector and an earthing switch. Vacuum chambers built into resin insulators sit on a common rotating shaft, and that shaft also works as the disconnector.

The basic bay width is only 500 mm. Interlocking is limited to a single device, so many mechanical and electrical interlocks and busbar connections are eliminated. The device is operated locally or remotely, for example by radio. Two visible, fully insulating air gaps are provided, and in the off and open position the device itself forms a mechanical and insulating partition between the busbar compartment and the cable compartment. The main shaft (circuit breaker and switch disconnector) can be exchanged quickly during service.

The device has four positions: on (closed), off (closed), off (open) and earthed. Example bay equipment configurations are VCB 1, VCB 2, VCB 5, VCB O5, VCB S1L and VCB S3L. Mechanical interlocks block incorrect switching and keep the bay door shut until the supply is disconnected and the earthing switch is closed.

Bays accept protection and control devices from various manufacturers, and the zinc-coated sheet steel resists corrosion. Devices are easy to reach for supervision and maintenance, and wall mounting saves floor space when existing switch rooms are refurbished or extended. Internal arc classification is AFLR up to 16 kA (1 s). Standards: (PN-EN) IEC 62271-1, -100 and -200; certified by the Electrotechnical Institute.

Technical specifications

Rated network voltage20 kV
Highest device voltage25 kV
Rated frequency / number of phases50 Hz / 3
Rated short-time network frequency withstand voltage50 kV / 60 kV
Rated withstand lightning surge voltage 1.2/50 μs125 kV / 145 kV
Continuous rated current630 A
Rated short-time withstand currentup to 16 kA (3 s) / up to 20 kA (1 s)
Rated peak withstand currentup to 50 kA
Resistance to internal arc effectsAFLR up to 16 kA (1 s)
Degree of protectionup to IP4X
Ambient temperature, peak short-time+ 40 °C
Ambient temperature, highest annual average+ 20 °C
Ambient temperature, lowest long-term- 25 °C
Relative humidity, day / month average95% / 90%
Installation altitudeup to 1000 m a.s.l.
Basic bay width500 mm
Example bay configurationsVCB 1, VCB 2, VCB 5, VCB O5, VCB S1L, VCB S3L

How it compares with similar models

ParameterRotoblok VCB 25 kV switchgear with three-function TGI deviceRotoblok Air 24 kV dry air insulated switchgear, SF6-freeRotoblok SF 20 kV medium voltage switchgear with SF6 switching devicesRELF 2S 12 kV double busbar medium voltage switchgear
Rated short-time withstand currentup to 16 kA (3 s) / up to 20 kA (1 s)up to 20 kA (1 s)20 kA (1 s)31.5 kA/3 s
Rated peak withstand currentup to 50 kA—50 kA80 kA

Request a price and lead time

Rotoblok VCB 25 kV switchgear with three-function TGI device. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which functions does the TGI device combine?

It combines a circuit breaker, a disconnector and an earthing switch. The vacuum chambers sit in resin insulators on a common rotating shaft.

What is the bay width, and is remote operation possible?

The basic bay width is 500 mm. The device can be operated locally or remotely, for example by radio.

What short-time withstand and arc ratings apply?

Up to 16 kA (3 s) or up to 20 kA (1 s) at a rated current of 630 A, with internal arc classification AFLR up to 16 kA (1 s).