Sabre EcoTec — RMU with synthetic air insulation up to 17.5 kV (SF6-free)
Sabre EcoTec RMU for voltages up to 17.5 kV, 50 Hz, with synthetic air insulation and no SF6 (GWP = 0). It is installed on a transformer or free-standing and keeps the functionality of the Sabre series with built-in automation.
- Rated voltage
- up to 17.5 kV, 50 Hz
- Impulse withstand voltage
- 95 kV
- Short-time current
- 20 kA / 3 s, peak 52.5 kA
- Internal arc withstand
- AF / AFL / AFLR, 20 kA (tank) / 13.5–20 kA (cable compartment), 1 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The new RMU is intended for power networks, industry and infrastructure. Impulse withstand voltage 95 kV, short-time current 20 kA for 3 s, peak current 52.5 kA. Internal arc withstand classes AF / AFL / AFLR, 20 kA for the tank and 13.5–20 kA for the cable compartment for 1 s. Degree of protection IP54 for the outdoor version and IP41 for the indoor version.
Technical specifications
| Rated voltage | up to 17.5 kV, 50 Hz |
|---|---|
| Impulse withstand voltage | 95 kV |
| Short-time current | 20 kA / 3 s, peak 52.5 kA |
| Internal arc withstand | AF / AFL / AFLR, 20 kA (tank) / 13.5–20 kA (cable compartment), 1 s |
| Degree of protection | IP54 (outdoor) / IP41 (indoor) |
| Insulation | synthetic air, GWP = 0 |
Request a price and lead time
Sabre EcoTec — RMU with synthetic air insulation up to 17.5 kV (SF6-free). We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8537 20 91 00 |
|---|---|
| HS, 6 digits | 8537 20 |
| CN (EU) | 8537 20 91 |
| HTSUS (USA) | 8537 20 00 20 |
| China customs tariff | 8537 20 90 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
What insulation is used in Sabre EcoTec?
Synthetic air with GWP = 0; there is no SF6 gas in the unit.
What internal arc withstand does the RMU have?
Classes AF / AFL / AFLR, 20 kA for the tank and 13.5–20 kA for the cable compartment for 1 s.
Can Sabre EcoTec be installed outdoors?
Yes, the degree of protection is IP54 for the outdoor version and IP41 for the indoor version.
Similar equipment from other manufacturers