Sabre EcoTec — RMU with synthetic air insulation up to 17.5 kV (SF6-free)

Sabre EcoTec RMU for voltages up to 17.5 kV, 50 Hz, with synthetic air insulation and no SF6 (GWP = 0). It is installed on a transformer or free-standing and keeps the functionality of the Sabre series with built-in automation.

Rated voltage
up to 17.5 kV, 50 Hz
Impulse withstand voltage
95 kV
Short-time current
20 kA / 3 s, peak 52.5 kA
Internal arc withstand
AF / AFL / AFLR, 20 kA (tank) / 13.5–20 kA (cable compartment), 1 s

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The new RMU is intended for power networks, industry and infrastructure. Impulse withstand voltage 95 kV, short-time current 20 kA for 3 s, peak current 52.5 kA. Internal arc withstand classes AF / AFL / AFLR, 20 kA for the tank and 13.5–20 kA for the cable compartment for 1 s. Degree of protection IP54 for the outdoor version and IP41 for the indoor version.

Technical specifications

Rated voltageup to 17.5 kV, 50 Hz
Impulse withstand voltage95 kV
Short-time current20 kA / 3 s, peak 52.5 kA
Internal arc withstandAF / AFL / AFLR, 20 kA (tank) / 13.5–20 kA (cable compartment), 1 s
Degree of protectionIP54 (outdoor) / IP41 (indoor)
Insulationsynthetic air, GWP = 0

Request a price and lead time

Sabre EcoTec — RMU with synthetic air insulation up to 17.5 kV (SF6-free). We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8537 20 91 00
HS, 6 digits8537 20
CN (EU)8537 20 91
HTSUS (USA)8537 20 00 20
China customs tariff8537 20 90 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What insulation is used in Sabre EcoTec?

Synthetic air with GWP = 0; there is no SF6 gas in the unit.

What internal arc withstand does the RMU have?

Classes AF / AFL / AFLR, 20 kA for the tank and 13.5–20 kA for the cable compartment for 1 s.

Can Sabre EcoTec be installed outdoors?

Yes, the degree of protection is IP54 for the outdoor version and IP41 for the indoor version.