International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

EH-MVSg-24 medium-voltage switchgear up to 24 kV, up to 630 A

The EH-MVSg-24 is metal-enclosed medium-voltage switchgear rated 12, 17.5 and 24 kV for indoor installation, with rated current up to 630 A. It combines vacuum switching with SF6 gas insulation and is arc-protected to 16 kA for 1 s.

Rated voltage Ur
12, 17.5, 24 kV
Frequency fr
50/60 Hz
Rated current Ir
up to 630 A
Rated lightning impulse withstand voltage 1.2/50, to earth and between phases Up
75, 95, 125 kV (peak)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

EH-MVSg-24 switchgear is built from interconnected panels, each with a defined function such as switching, measuring or protection. It is used in installations rated up to 24 kV, in industry, in renewable energy and in the commercial power sector, for secondary distribution of electricity.

The design has two compartments and a single busbar system. The enclosure is metal, the construction is arc-protected, and the equipment is meant for indoor installation. Vacuum switching and SF6 gas insulation keep the panels compact. The gas-filled containers are rated IP65 and the switchgear as a whole IP2X / IP3X. Protection, control system and interlocks are intended to keep operation and use safe.

Rated voltage Ur is 12, 17.5 or 24 kV at 50/60 Hz, and rated current Ir is up to 630 A. Short-term rated current Ik is 16 kA for 1 s, rated peak withstand current Ip is 40 kA, and internal arc resistance IAC for 1 s is 16 kA.

Four panel types are available. EH-I is the line panel, an inlet or outlet with a disconnector-earthing switch. EH-TM is the transformer panel, a disconnector feeder with fuse and earthing switch. EH-ITI is the circuit breaker panel, a disconnector feeder with circuit breaker and earthing switch. EH-MAS is the measuring panel, taking readings from current and voltage transformers.

The upper compartment holds the busbars: copper busbars form a three-phase busbar bridge between panels, and some panel types take a superstructure for current transformers connected directly to the busbars. The lower compartment carries the switching, measuring and cable equipment, for example the circuit breaker, switch, earthing switch, measuring transformers, fuses, surge arresters and cable connections. The low-voltage compartment houses auxiliary and guaranteed power supplies, auxiliary relays, field controllers, power quality analysers, telemechanics components and other control and measuring equipment. Depending on the panel, it can also take the parts of an in-house switchboard or SCADA functions.

Technical specifications

Rated voltage Ur12, 17.5, 24 kV
Frequency fr50/60 Hz
Rated current Irup to 630 A
Rated lightning impulse withstand voltage 1.2/50, to earth and between phases Up75, 95, 125 kV (peak)
Rated lightning impulse withstand voltage 1.2/50, safe insulation distance Up85, 110, 145 kV (peak)
Insulation level 1 min / 50 Hz, to earth and between phases Ud28, 38, 50 kV (RMS)
Insulation level 1 min / 50 Hz, safe insulation interval Ud32, 45, 60 kV (RMS)
Short-term rated current Ik16 kA
Rated short-circuit duration tk1 s
Rated peak withstand current Ip40 kA
Internal arc resistance IAC 1 s16 kA
Protection level, gas-filled containersIP65
Protection level, switchgearIP2X / IP3X
Panel typesEH-I, EH-TM, EH-ITI, EH-MAS

Request a price and lead time

EH-MVSg-24 medium-voltage switchgear up to 24 kV, up to 630 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What voltages is the EH-MVSg-24 available for?

Rated voltage Ur is 12, 17.5 or 24 kV at 50/60 Hz, with rated current up to 630 A.

What internal arc protection does it have?

Internal arc resistance IAC is 16 kA for 1 s, and the switchgear is a metal-enclosed arc-protected design.

Which panel types make up the switchgear?

EH-I line panel, EH-TM transformer panel with fuse, EH-ITI circuit breaker panel and EH-MAS measuring panel.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides