VECTOR — medium-voltage busbar trunking 12/24 kV, 2000 A
Medium-voltage busbar trunking rated 12 or 24 kV and 2000 A, compatible with VECTOR switchgear. It links two rows of air-insulated switchgear without extra cubicles or cables under the floor. Modules up to 800 mm long are made in standard or custom lengths.
- Rated voltage
- 12 / 24 kV
- Rated current
- 2000 A
- Short-circuit withstand
- 40 kA 3 s (12 kV), 25 kA 3 s (24 kV)
- Internal arc withstand
- 40 kA 1 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
When VECTOR switchgear is installed in two rows, the sections are linked with this busbar trunking. Without it, linking the sections requires extra cubicles and cables laid under the floor. The busbar trunking replaces both options and saves space in the switchgear room. It is used both in new installations and in the modernization of switchgear at substations, power plants and industrial facilities.
The rated voltage of the busbar trunking is 12 or 24 kV, and the rated current is 2000 A. Short-circuit withstand is 40 kA for 3 s at 12 kV and 25 kA for 3 s at 24 kV, and internal arc withstand is 40 kA for 1 s. The short-circuit withstand values match the short-time withstand current limit of the VECTOR switchgear itself in the corresponding voltage class. For 24 kV the withstand is lower, so during design it is checked against the calculated short-circuit current of the network.
The busbar trunking consists of modules. They are produced in standard length or made to order for a specific room layout, and the length of one module is up to 800 mm. The run is assembled from the required number of modules, so it is fitted to the positions of the switchgear rows in the particular room. Individual modules are easier to deliver and carry into the switchgear room than a long continuous structure.
The busbar trunking was tested at the IPH laboratory to current IEC standards, and the design is intended for a high level of personnel safety. Tests in an independent laboratory confirm the declared short-circuit and arc withstand values. The product carries the SGS Fimko, CE and FI marks. The SGS Fimko mark is issued by a Finnish certification body, and CE means compliance with EU directive requirements. The busbar trunking is designed for the manufacturer's own switchgear range and is built at the same plant in Vaasa (Finland) as the VECTOR cubicles.
When ordering, specify the voltage class, the layout plan of the two switchgear rows and the length of the run, from which the number of standard and custom modules is determined. Module type and length are agreed at the project stage with the switchgear layout. For low-voltage systems the manufacturer offers a separate VEBA busbar trunking, and for medium voltage this busbar trunking complements the VECTOR switchgear range.
Technical specifications
| Rated voltage | 12 / 24 kV |
|---|---|
| Rated current | 2000 A |
| Short-circuit withstand | 40 kA 3 s (12 kV), 25 kA 3 s (24 kV) |
| Internal arc withstand | 40 kA 1 s |
| Module length | up to 800 mm (standard and custom lengths) |
| Testing | IPH, to IEC |
| Marks | SGS Fimko, CE, FI |
Request a price and lead time
VECTOR — medium-voltage busbar trunking 12/24 kV, 2000 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the VECTOR busbar trunking for?
It links two rows of VECTOR switchgear at 12 or 24 kV without extra cubicles and cables under the floor. The rated current of the busbar trunking is 2000 A.
What short-circuit withstand does the busbar trunking have?
40 kA for 3 s at 12 kV and 25 kA for 3 s at 24 kV. Internal arc withstand is 40 kA for 1 s.
What tests and marks does the busbar trunking have?
The busbar trunking has been tested at the IPH laboratory for compliance with IEC standards. The product carries the SGS Fimko, CE and FI marks, and the module length is up to 800 mm.