WDG-V Blowback oxygen and combustibles analyser for dusty flue gas

The WDG-V Blowback measures oxygen and combustible components (CO+H2) continuously in boiler flue gas with high dust loading. A built-in blowback unit cleans the sample probe and filter with compressed, preheated air, without removing the analyser from the process flange.

Principle
zirconia cell for O2, catalytic detector for combustibles (CO+H2)
O2 range
0-1% to 0-100%
Combustibles range
0-2000 ppm to 0-10000 ppm, or 0-1% to 0-5%
O2 accuracy
±0.75% of reading or ±0.05%, whichever is greater

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The analyser mounts directly on the flue gas duct flange and works on a close-coupled extractive principle, so the sample reaches the sensors within a short time. Dust loading of the gas can be up to 30 mg/m3. It is applied to coal, wood waste and heavy fuel oil fired power and steam boilers, biofuel boilers and high dust industrial processes, and to monitoring purge and light-off cycles during start-up and shutdown.

Oxygen is measured by a zirconium oxide cell and combustible gases by a catalytic detector. The output ranges are 0-1% to 0-100% for O2, and for combustibles 0-2000 ppm to 0-10000 ppm or 0-1% to 0-5%. O2 accuracy is ±0.75% of the reading or ±0.05%, whichever is greater, and combustibles are accurate to ±2% of full scale. The response to a 90% step is under 6 seconds for O2 and under 20 seconds for combustibles, and drift is below 0.1% of cell output per month.

The Blowback option adds a second cabinet with a receiver and a three-way valve. During a purge the valve isolates the analyser and feeds compressed, preheated air to the probe and filter. Purging can be started on a timer, on a fall in sample flow, on either condition, or manually from the operator panel. A self-regulating heater and a heated receiver prevent condensation in the cabinet and sample line, and a flow sensor in the sample loop raises an alarm at 45% of nominal flow.

Probes are made from 316 SS for gas up to 704 °C, 310 SS up to 1024 °C and ceramic up to 1648 °C. The sensor cabinet is hinged, stainless steel and rated IP65 (NEMA 4X), and purged versions are available. The ambient range is -25 to 65 °C with 10 to 90% humidity without condensation, up to 5000 m altitude. Power is 115 or 230 V AC ±10%, 47–63 Hz.

Three isolated current outputs of 4-20 or 0-20 mA with NAMUR configuration, five dry contact alarms, RS-485 Modbus RTU and an optional HART interface are provided. Ethernet gives remote diagnostics, calibration and verification. Diagnostics include a watchdog timer, a service alarm, cell resistance measurement and end-of-life warnings for the cell and detector. The WDG-VCM variant also measures methane. Maintenance is carried out without removing the analyser from the flange.

Technical specifications

Principlezirconia cell for O2, catalytic detector for combustibles (CO+H2)
O2 range0-1% to 0-100%
Combustibles range0-2000 ppm to 0-10000 ppm, or 0-1% to 0-5%
O2 accuracy±0.75% of reading or ±0.05%, whichever is greater
Combustibles accuracy±2% of full scale
Response (90%)O2 under 6 s; combustibles under 20 s
Driftunder 0.1% of cell signal per month
Dust loadingup to 30 mg/m3
Gas temperature and probe material704 °C / 316 SS; 1024 °C / 310 SS; 1648 °C / ceramic
Analogue outputs3 isolated, 4-20 / 0-20 / 20-4 / 20-0 mA
Alarms5 dry contacts, 0.5 A, 30 V
Digital interfaceRS-485 Modbus RTU at 57.6 kbaud, HART option
EnclosureIP65 (NEMA 4X), stainless steel
Ambient temperature-25 to 65 °C
Power115 V AC or 230 V AC ±10%, 47–63 Hz, up to 950 VA

Part numbers

Show all part numbers (3)

WDG-V, WDG-VC, WDG-VCM

Request a price and lead time

WDG-V Blowback oxygen and combustibles analyser for dusty flue gas. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How often is the probe purged?

Purging is set on a timer, on a fall in sample flow, or on both conditions, and it can also be started by hand from the operator panel.

How much dust can the analyser handle?

The analyser is rated for dust loading up to 30 mg/m3, and the probe and filter are cleaned with compressed, preheated air from the receiver.

Can the analyser measure methane?

Yes. The WDG-VCM variant has a methane detector with a range of 0-1% to 0-5% and an accuracy of ±5% of full scale.