WDG Insitu zirconia oxygen probe for flue gas up to 800 °C
The WDG Insitu measures oxygen directly in the stack on a zirconia cell, so no gas sample has to be drawn off. The inner cell block, heater and thermocouple withdraw through the probe head, while the outer tube stays installed in the process. It is supplied with the Series 2000 control unit.
- Measuring principle
- zirconium oxide (ZrO2), hot wet gas
- Range
- 0–1% to 0–100% O2
- Accuracy
- ±1% of reading or ±0.05% O2, whichever is greater
- Response
- 63% of a step change in under 20 seconds
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
This probe monitors combustion in boilers and furnaces where flue gas stays at or below 800 °C (1472 °F). Typical sites are hydrocarbon processing, metals and mining, power and steam generation, and cement and lime kilns. Because the measurement is made in hot, wet gas, the reading takes account of the moisture present.
The probe is built from two tubes. The inner assembly, which holds the zirconia cell, heater and thermocouple, slides out through the probe head, and the outer support tube remains fitted to the process. The reference side of the cell is open to ambient air, so no instrument air supply needs to be run to the installation point. With the inner assembly removed, the outer tube gives direct access to the filter, which can be cleaned with compressed air. Probes come in several lengths, and the body is made from 310 SS stainless steel.
The measuring range runs from 0–1% to 0–100% O2, with accuracy of ±1% of the reading or ±0.05% O2, whichever is greater. The response to a 63% step change is under 20 seconds, drift is below 0.1% of cell output per month, and linearity and repeatability are each ±1% of output span. The probe tolerates a sample pressure of ±10 inches water gauge, an ambient range of -20 to 71 °C and humidity of 10 to 90% without condensation, with a NEMA 4X enclosure. It runs from 115 or 230 V AC ±10%, 47–63 Hz, drawing up to 150 VA.
The Series 2000 control unit has a four-line, 20-character vacuum fluorescent display and two isolated current outputs, configurable as 4–20, 0–20, 20–4 or 20–0 mA into loads up to 1200 ohms, with O2, cell temperature, thermocouple mV or cell mV selectable for each. Two independent O2 alarms can be set high or low, using 0.5 A, 30 V relays, and the unit has an RS-485 interface, a watchdog timer, a twenty-entry event log and an optional autocalibration function. It works between -10 and 50 °C and comes in a NEMA 4 (IP 56) enclosure for wall or panel mounting, or in a 19-inch rack, general purpose or stainless steel NEMA 4X housing.
Calibration uses air or gas with 1.0–100% O2 for the span point and 2% or 0.1–10% O2 in nitrogen for the zero point, at 10 PSIG and a flow of 1.41–2.82 litres per minute. An optional flame arrestor filter, a remote calibration unit and versions for Class I, Division 2, groups A, B, C and D are available.
Technical specifications
| Measuring principle | zirconium oxide (ZrO2), hot wet gas |
|---|---|
| Range | 0–1% to 0–100% O2 |
| Accuracy | ±1% of reading or ±0.05% O2, whichever is greater |
| Response | 63% of a step change in under 20 seconds |
| Drift | under 0.1% of cell signal per month |
| Linearity and repeatability | ±1% of span |
| Flue gas temperature | up to 800 °C (1472 °F) |
| Sample pressure | ±10 inches water gauge |
| Ambient temperature (probe) | -20 to 71 °C |
| Probe material | 310 SS |
| Probe power | 115 or 230 V AC ±10%, 47–63 Hz, up to 150 VA |
| Analogue outputs | 2 isolated, 4–20 / 0–20 / 20–4 / 20–0 mA, up to 1200 ohms |
| Alarms | 2 independent O2 alarms, relays 0.5 A, 30 V |
| Interface | RS-485 |
| Control unit | Series 2000, -10 to 50 °C, NEMA 4 (IP 56) |
| Explosion protection (option) | Class I, Division 2, groups A, B, C, D |
Part numbers
Show all part numbers (5)
WDG Insitu, WDG-HPIIC, WDG-HPIICM, WDG-VC, WDG-VCM
Request a price and lead time
WDG Insitu zirconia oxygen probe for flue gas up to 800 °C. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Is an instrument air supply needed at the probe?
No. The reference side of the zirconia cell is open to the surrounding air, so no instrument air has to be run to the mounting point.
How can the probe be serviced without stopping the process?
The inner cell block, heater and thermocouple slide out through the probe head while the outer tube stays in the process, and the filter can be cleaned with compressed air through that tube.
Which outputs does the Series 2000 control unit provide?
Two isolated current outputs of 4–20 or 0–20 mA into loads up to 1200 ohms, two O2 alarm relays and an RS-485 interface.
Similar equipment from other manufacturers