TCT isolated thermocouple transmitter, Eurocard (4-wire)

The TCT takes the millivolt signal of any standard thermocouple and converts it to a standard current or voltage output. Input, output and power are isolated, input impedance is at least 10 megohms, and reference junction compensation is automatic.

Input
millivolt signal of any standard thermocouple
Output
standard current or voltage
Narrow-span input
down to 2-5 mV (optional)
Low-voltage output
0-1 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

A thermocouple transmitter, the TCT accepts the millivolt input of any standard thermocouple and converts it to either a standard current or voltage output that indicates process temperature. It interfaces to recording, monitoring and controlling instruments, or directly to a computer in process control systems.

Input, output and power terminals are completely isolated, which prevents false input from ground loop currents. Common mode rejection is 120 dB (1,000,000:1) up to 500 volts rms, limiting errors from induced common mode voltage. Input impedance is at least 10 megohms, so extended thermocouple leads do not turn common mode voltage into normal mode voltage. Reference junction temperature changes are compensated automatically.

Input and output ranges are selectable from standard values. Narrow-span input is possible (optionally as low as 2-5 mV), and a low-voltage output of 0-1 V is available. Options include -LNT linearisation, -RF radio-frequency protection with a patented filter assembly, dual input ranges, reversed input/output signals and a raised zero. The -LNT option gives at least a 10:1 improvement in linearity for type E, J, K, R, S and T thermocouples.

If a thermocouple burns out or the input circuit opens, the output is driven upscale to 150% of span, or downscale with the -DD option. Zero and span are set with 22-turn potentiometers, and zero can correct offsets up to ±20% of span (±10% with -LNT). Calibration capability (linearity and repeatability) is ±0.1% of span, frequency response is 5 Hz (3 dB point) and ripple is under 10 mV peak-to-peak. The ambient effect on the amplifier is ±0.005% per °F over -29°C to +82°C.

The standard housing is a corrosion-resistant aluminium case with a U-Back mounting bracket that fits a 3 inch by 7-1/2 inch space. Enclosures used with the TCT include explosion-proof, fibreglass, oiltight, watertight and transparent-cover types.

Technical specifications

Inputmillivolt signal of any standard thermocouple
Outputstandard current or voltage
Narrow-span inputdown to 2-5 mV (optional)
Low-voltage output0-1 V
Input impedance10 megohms minimum
Isolationinput, output and power, transformer
Common mode rejection120 dB up to 500 volts rms
Calibration capability±0.1% of span
Frequency response5 Hz (3 dB point)
Ripplebelow 10 mV peak-to-peak
Burnoutoutput upscale to 150% of span; -DD downscale
Adjustment22-turn potentiometers, zero up to ±20% of span
Ambient range-29°C to +82°C
Options-LNT, -RF, -DD

How it compares with similar models

ParameterTCT isolated thermocouple transmitter, Eurocard (4-wire)RBT 4-wire RTD transmitter, ±0.1% accuracyACT 4-Wire AC Current and Voltage Transmitter with Input-Output IsolationLIT 4-Wire Linear Integrating Totaliser, Pulse Output Proportional to the Input Signal
Inputmillivolt signal of any standard thermocouplestandard 2-, 3- or 4-wire RTD (platinum, copper, nickel)—Standard current or voltage process signal
Outputstandard current or voltageproportional current—Pulse string proportional to the input
Isolationinput, output and power, transformercomplete, input/output/powerTransformer isolated, to 500 VrmsPower from input-output; input-output with relay output
Options-LNT, -RF, -DD-LNP, -LNN, -RO, -RF—8-digit LCD counter, -FS, -RF, attenuated input, raised zero, relay outputs -HS, -PR, -RE, -RR

Request a price and lead time

TCT isolated thermocouple transmitter, Eurocard (4-wire). We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which thermocouples does the TCT support?

Any standard thermocouple through its millivolt input. The -LNT option linearises types E, J, K, R, S and T.

What happens when a thermocouple burns out?

The output is driven upscale to 150% of span, or downscale with the -DD option.

What isolation and input impedance does it have?

Input, output and power are transformer isolated, and input impedance is at least 10 megohms.

Similar equipment from other manufacturers