International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing

The FCT [UB] takes a current or voltage input and gives an isolated current or voltage output. It runs from 90-260 Vac or 22-300 Vdc, isolates at 1000 Vrms, is accurate to +/-0.1 % of span, and comes in a UB housing with a U-back bracket.

Type
Signal converter and isolator, 4-wire
Input
0-20 mA, 4-20 mA (50 ohms); 0-50 mA, 10-50 mA (20 ohms); 0-1 V, 0-5 V, 1-5 V (1 megohm); 0-10 V (2 megohms)
Special inputs
Spans from 1 to 24 V or from 1 to 100 mA
Output
0-20 mA, 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V, 1-5 V into 20K ohms minimum; 0-10 V into 40K ohms minimum

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The FCT [UB] accepts a current or voltage input and provides an isolated current or voltage output. It is a compact 4-wire unit with universal power and user-set ZERO and SPAN potentiometers. Complete isolation between input, output and power, up to 1000 Vrms, stops ground loops.

Power input is universal: the standard unit accepts 90 to 260 Vac and 22 to 300 Vdc with no field configuration, drawing 3.5 W nominal and 5 W maximum depending on output. The -TX option supplies regulated 24 Vdc at 25 mA for one external 2-wire transmitter.

Inputs are 0-20 mA and 4-20 mA into 50 ohms; 0-50 mA and 10-50 mA into 20 ohms; 0-1 V, 0-5 V and 1-5 V into 1 megohm; and 0-10 V into 2 megohms. Special input spans run from 1 to 24 V or from 1 to 100 mA. Outputs are 0-20 mA and 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V and 1-5 V into 20K ohms minimum; and 0-10 V into 40K ohms minimum, with special outputs on request.

Accuracy is +/-0.1 % of span, including adjustment resolution and linearity. Dielectric withstand is 1500 Vrms between case, power, inputs and outputs. Frequency response is 5 Hz at -3 dB, ripple is 10 mV peak-to-peak and common mode rejection exceeds 120 dB at 60 Hz. Maximum input overrange is +/-60 V on voltage inputs, +/-50 mA on 0-20 mA inputs and +/-100 mA on 0-50 mA inputs; output is limited to 160 % of full scale at most. Load effect is +/-0.01 % of span, power supply effect is below 0.05 % of span, and RFI/EMI immunity is 10 V/m tested to SAMA Standard PMC 33.1.

Ambient range is -30 to +82 degrees C, with an effect on accuracy of +/-0.015 % of span per degree C. External multiturn potentiometers adjust SPAN (+/-10 %) and ZERO (+/-5 %). The UB housing has a U-back bracket for surface mounting and measures 186 x 76.2 x 63.3 mm, weighing 300 g.

Technical specifications

TypeSignal converter and isolator, 4-wire
Input0-20 mA, 4-20 mA (50 ohms); 0-50 mA, 10-50 mA (20 ohms); 0-1 V, 0-5 V, 1-5 V (1 megohm); 0-10 V (2 megohms)
Special inputsSpans from 1 to 24 V or from 1 to 100 mA
Output0-20 mA, 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V, 1-5 V into 20K ohms minimum; 0-10 V into 40K ohms minimum
PowerUniversal: 90-260 Vac or 22-300 Vdc; 3.5 W nominal, 5 W maximum
Option -TX24 Vdc at 25 mA for one 2-wire transmitter
Accuracy+/-0.1 % of span
Isolation1000 Vrms between input, output and power
Dielectric withstand1500 Vrms between case, power, inputs and outputs
Frequency response5 Hz at -3 dB
Common mode rejectionExceeds 120 dB at 60 Hz
Ambient range-30 to +82 degrees C
AdjustmentsSPAN +/-10 %, ZERO +/-5 %
HousingUB with U-back bracket for surface mounting
Dimensions186 x 76.2 x 63.3 mm
Weight300 g

Part numbers

Show all part numbers (1)

FCT [UB]

How it compares with similar models

ParameterFCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount HousingFCT PRG/PRG/U/-TX Field-Configurable Signal Isolator, Converter and RepeaterSIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms IsolationECT 4-20mA/4-20mA/5.5VLP 2-Wire Input-Loop-Powered Signal Isolator and Converter
TypeSignal converter and isolator, 4-wireSignal isolator, converter and repeater, 4-wireSignal isolator, converter and repeater, 2-wireSignal isolator and converter, 2-wire
Input0-20 mA, 4-20 mA (50 ohms); 0-50 mA, 10-50 mA (20 ohms); 0-1 V, 0-5 V, 1-5 V (1 megohm); 0-10 V (2 megohms)—1-5 V4-20 mA, fixed
Output0-20 mA, 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V, 1-5 V into 20K ohms minimum; 0-10 V into 40K ohms minimum—4-20 mA4-20 mA, fixed
Isolation1000 Vrms between input, output and power1000 Vrms between input, output and power; 500 Vac with -RF option1500 Vrms input to output; 500 Vrms with -RF option500 Vrms for input-loop-powered versions
Frequency response5 Hz at -3 dB5 Hz at -3 dB point-3 dB at 10 Hz—
HousingUB with U-back bracket for surface mountingUniversal DIN-style housing, 32 mm G-type and 35 mm Top Hat railDIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) railUniversal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail

Request a price and lead time

FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What power supply does the FCT [UB] need?

Universal: 90 to 260 Vac or 22 to 300 Vdc, with no configuration.

Can the FCT [UB] power a 2-wire transmitter?

Yes, with the -TX option: regulated 24 Vdc at 25 mA for one external 2-wire transmitter.

What isolation is provided?

1000 Vrms between input, output and power, with 1500 Vrms dielectric withstand.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search