FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing
The FCT [UB] takes a current or voltage input and gives an isolated current or voltage output. It runs from 90-260 Vac or 22-300 Vdc, isolates at 1000 Vrms, is accurate to +/-0.1 % of span, and comes in a UB housing with a U-back bracket.
- Type
- Signal converter and isolator, 4-wire
- Input
- 0-20 mA, 4-20 mA (50 ohms); 0-50 mA, 10-50 mA (20 ohms); 0-1 V, 0-5 V, 1-5 V (1 megohm); 0-10 V (2 megohms)
- Special inputs
- Spans from 1 to 24 V or from 1 to 100 mA
- Output
- 0-20 mA, 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V, 1-5 V into 20K ohms minimum; 0-10 V into 40K ohms minimum
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The FCT [UB] accepts a current or voltage input and provides an isolated current or voltage output. It is a compact 4-wire unit with universal power and user-set ZERO and SPAN potentiometers. Complete isolation between input, output and power, up to 1000 Vrms, stops ground loops.
Power input is universal: the standard unit accepts 90 to 260 Vac and 22 to 300 Vdc with no field configuration, drawing 3.5 W nominal and 5 W maximum depending on output. The -TX option supplies regulated 24 Vdc at 25 mA for one external 2-wire transmitter.
Inputs are 0-20 mA and 4-20 mA into 50 ohms; 0-50 mA and 10-50 mA into 20 ohms; 0-1 V, 0-5 V and 1-5 V into 1 megohm; and 0-10 V into 2 megohms. Special input spans run from 1 to 24 V or from 1 to 100 mA. Outputs are 0-20 mA and 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V and 1-5 V into 20K ohms minimum; and 0-10 V into 40K ohms minimum, with special outputs on request.
Accuracy is +/-0.1 % of span, including adjustment resolution and linearity. Dielectric withstand is 1500 Vrms between case, power, inputs and outputs. Frequency response is 5 Hz at -3 dB, ripple is 10 mV peak-to-peak and common mode rejection exceeds 120 dB at 60 Hz. Maximum input overrange is +/-60 V on voltage inputs, +/-50 mA on 0-20 mA inputs and +/-100 mA on 0-50 mA inputs; output is limited to 160 % of full scale at most. Load effect is +/-0.01 % of span, power supply effect is below 0.05 % of span, and RFI/EMI immunity is 10 V/m tested to SAMA Standard PMC 33.1.
Ambient range is -30 to +82 degrees C, with an effect on accuracy of +/-0.015 % of span per degree C. External multiturn potentiometers adjust SPAN (+/-10 %) and ZERO (+/-5 %). The UB housing has a U-back bracket for surface mounting and measures 186 x 76.2 x 63.3 mm, weighing 300 g.
Technical specifications
| Type | Signal converter and isolator, 4-wire |
|---|---|
| Input | 0-20 mA, 4-20 mA (50 ohms); 0-50 mA, 10-50 mA (20 ohms); 0-1 V, 0-5 V, 1-5 V (1 megohm); 0-10 V (2 megohms) |
| Special inputs | Spans from 1 to 24 V or from 1 to 100 mA |
| Output | 0-20 mA, 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V, 1-5 V into 20K ohms minimum; 0-10 V into 40K ohms minimum |
| Power | Universal: 90-260 Vac or 22-300 Vdc; 3.5 W nominal, 5 W maximum |
| Option -TX | 24 Vdc at 25 mA for one 2-wire transmitter |
| Accuracy | +/-0.1 % of span |
| Isolation | 1000 Vrms between input, output and power |
| Dielectric withstand | 1500 Vrms between case, power, inputs and outputs |
| Frequency response | 5 Hz at -3 dB |
| Common mode rejection | Exceeds 120 dB at 60 Hz |
| Ambient range | -30 to +82 degrees C |
| Adjustments | SPAN +/-10 %, ZERO +/-5 % |
| Housing | UB with U-back bracket for surface mounting |
| Dimensions | 186 x 76.2 x 63.3 mm |
| Weight | 300 g |
Part numbers
Show all part numbers (1)
FCT [UB]
How it compares with similar models
| Parameter | FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing | FCT PRG/PRG/U/-TX Field-Configurable Signal Isolator, Converter and Repeater | SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation | ECT 4-20mA/4-20mA/5.5VLP 2-Wire Input-Loop-Powered Signal Isolator and Converter |
|---|---|---|---|---|
| Type | Signal converter and isolator, 4-wire | Signal isolator, converter and repeater, 4-wire | Signal isolator, converter and repeater, 2-wire | Signal isolator and converter, 2-wire |
| Input | 0-20 mA, 4-20 mA (50 ohms); 0-50 mA, 10-50 mA (20 ohms); 0-1 V, 0-5 V, 1-5 V (1 megohm); 0-10 V (2 megohms) | — | 1-5 V | 4-20 mA, fixed |
| Output | 0-20 mA, 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V, 1-5 V into 20K ohms minimum; 0-10 V into 40K ohms minimum | — | 4-20 mA | 4-20 mA, fixed |
| Isolation | 1000 Vrms between input, output and power | 1000 Vrms between input, output and power; 500 Vac with -RF option | 1500 Vrms input to output; 500 Vrms with -RF option | 500 Vrms for input-loop-powered versions |
| Frequency response | 5 Hz at -3 dB | 5 Hz at -3 dB point | -3 dB at 10 Hz | — |
| Housing | UB with U-back bracket for surface mounting | Universal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail | DIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) rail | Universal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail |
Request a price and lead time
FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What power supply does the FCT [UB] need?
Universal: 90 to 260 Vac or 22 to 300 Vdc, with no configuration.
Can the FCT [UB] power a 2-wire transmitter?
Yes, with the -TX option: regulated 24 Vdc at 25 mA for one external 2-wire transmitter.
What isolation is provided?
1000 Vrms between input, output and power, with 1500 Vrms dielectric withstand.