FCT PRG/PRG/U/-TX Field-Configurable Signal Isolator, Converter and Repeater
The FCT PRG/PRG/U/-TX is set by jumpers to any input within 0-50 mA or 0-10 V and any output within 0-20 mA or 0-10 V. It takes 22-300 Vdc or 90-260 Vac, isolates at 1000 Vrms, and the -TX option supplies 24 V to a 2-wire transmitter.
- Type
- Signal isolator, converter and repeater, 4-wire
- Input (PRG)
- Jumper selectable within 0-50 mA or 0-10 V
- Output (PRG)
- Jumper selectable within 0-20 mA or 0-10 V
- Power (U)
- Universal: 22-300 Vdc or 90-260 Vac
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Compact and 4-wire, the FCT acts as a signal isolator, converter and repeater. In the PRG/PRG version both sides are configured in the field by jumpers: the input anywhere within 0-50 mA or 0-10 V, the output anywhere within 0-20 mA or 0-10 V. That covers the common 4-20 mA, 1-5 V and 0-10 V signals, while unusual input and output types can be ordered separately.
Power input is universal. The unit accepts 22-300 Vdc or 90-260 Vac automatically, with no jumper changes. The -TX option adds 24 V transmitter excitation, so the FCT can power a 2-wire transmitter while it isolates the signal.
As an isolator it separates a non-isolated transmitter from the receiving device and removes false readings caused by ground loops, electrical interference and motor noise. As a repeater it boosts drive capability for further instruments on the loop, or splits a secondary signal off to a recorder or indicator.
Accuracy is +/-0.1 % of span, including adjustment resolution and linearity. Isolation between input, output and power is 1000 Vrms (500 Vac with the -RF option) and dielectric withstand is 1500 Vrms between case, power, inputs and outputs. Common mode rejection exceeds 120 dB at 60 Hz, frequency response is 5 Hz at the -3 dB point, and ripple is 10 mV peak-to-peak. Maximum input overrange is +/-60 V on voltage inputs, +/-50 mA on 0-20 mA inputs and +/-100 mA on 0-50 mA inputs. RFI/EMI immunity is 10 V/m, or 30 V/m with -RF.
The DIN-style housing clips onto 32 mm G-type or 35 mm Top Hat rail. Removable terminal blocks let a unit be replaced without rewiring. Signals should run in shielded twisted pair, and the metal case, and the rail for DIN housings, should be earthed. Maintenance is limited to checking terminal connections every six months. The unit is CSA approved for general locations.
Technical specifications
| Type | Signal isolator, converter and repeater, 4-wire |
|---|---|
| Input (PRG) | Jumper selectable within 0-50 mA or 0-10 V |
| Output (PRG) | Jumper selectable within 0-20 mA or 0-10 V |
| Power (U) | Universal: 22-300 Vdc or 90-260 Vac |
| Option -TX | 24 V transmitter excitation for powering a 2-wire transmitter |
| Accuracy | +/-0.1 % of span |
| Isolation | 1000 Vrms between input, output and power; 500 Vac with -RF option |
| Dielectric withstand | 1500 Vrms between case, power, inputs and outputs |
| Frequency response | 5 Hz at -3 dB point |
| Common mode rejection | Exceeds 120 dB at 60 Hz |
| Maximum input overrange | Voltage inputs +/-60 V; 0-20 mA +/-50 mA; 0-50 mA +/-100 mA |
| RFI/EMI immunity | 10 V/m; 30 V/m with -RF option |
| Housing | Universal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail |
| HART / SIS | HART pass-through: no; for SIS use: no |
| Approvals | CSA General Location |
Part numbers
Show all part numbers (1)
FCT/PRG/PRG/U/-TX
How it compares with similar models
| Parameter | FCT PRG/PRG/U/-TX Field-Configurable Signal Isolator, Converter and Repeater | FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing | MIT 2XPRG 2-Channel 4-Wire Signal Isolator and Converter, 20-125 VDC or 90-250 VAC Supply | SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation |
|---|---|---|---|---|
| Type | Signal isolator, converter and repeater, 4-wire | Signal converter and isolator, 4-wire | Multi-channel signal isolator and converter, 4-wire | Signal isolator, converter and repeater, 2-wire |
| Accuracy | +/-0.1 % of span | +/-0.1 % of span | +/-0.1 % | +/-0.1 % of span |
| Isolation | 1000 Vrms between input, output and power; 500 Vac with -RF option | 1000 Vrms between input, output and power | Up to 1000 Vrms input to output and channel to channel; 2500 Vrms between power and signals | 1500 Vrms input to output; 500 Vrms with -RF option |
| Frequency response | 5 Hz at -3 dB point | 5 Hz at -3 dB | — | -3 dB at 10 Hz |
| Housing | Universal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail | UB with U-back bracket for surface mounting | Universal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail | DIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) rail |
| Approvals | CSA General Location | — | UL, CSA General Location, Non-Incendive/Div. 2, CE, RoHS | cULus Class I, Division 2, Groups A, B, C, D T4; CE; RoHS |
Request a price and lead time
FCT PRG/PRG/U/-TX Field-Configurable Signal Isolator, Converter and Repeater. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What signals can the FCT PRG be set to?
The input is jumper-selected within 0-50 mA or 0-10 V, and the output within 0-20 mA or 0-10 V.
What supply voltage does it accept?
Any of 22-300 Vdc or 90-260 Vac; nothing has to be switched or jumpered.
What does the -TX option do?
It provides 24 V transmitter excitation, so the unit can power a 2-wire transmitter while isolating its signal.
Similar equipment from other manufacturers
![FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing](/media/no-photo-640.webp)