SIY signal isolator and converter, PC programmable, loop-powered, two-wire
The SIY is a two-wire signal isolator and converter that draws its power from the output current loop and is configured from a PC for a standard or custom input range. It builds user curves for non-linear signals and has no open potentiometers.
- Type
- Signal isolator and converter
- Wiring
- Two-wire
- Power
- Loop-powered from the output loop
- Configuration
- PC programmed, standard and custom input ranges
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The SIY is used on critical measurement loops whose signal has to reach several receivers at once, such as a control system, a backup system, a recorder or an indicator. Pharmaceutical sites are a typical example, where some measuring points are so important that an inaccurate reading can injure personnel, and the signal often feeds several control devices together. Wiring receivers in series within one loop is risky, because a fault or disconnection of any single receiver opens the circuit and sends it into an alarm state. The SIY separates the loops galvanically, so work on the secondary or backup loop does not affect the main control loop, and vice versa.
The instrument is two-wire and draws its power from the output loop, so no separate supply is needed. The input is configured from a PC to almost any signal type and range, standard or special. For non-linear signals, a user conversion curve is stored in the instrument, so the linearisation is performed by the isolator itself rather than by the controller.
The SIY has no open potentiometers. Settings are changed only through the software, so accidental or unauthorised adjustment of the calibration on site is ruled out. This design suits loops in which every change to the settings must be documented.
Apart from the cabinet-mounted version, a field version is available with hazardous area approvals recognised in various countries. Typical sectors are pharmaceuticals and biotechnology, oil and gas extraction, refining, food and beverage, mining and metal processing, power generation, pulp and paper, semiconductor and microelectronics manufacturing, and water supply and wastewater treatment.
Technical specifications
| Type | Signal isolator and converter |
|---|---|
| Wiring | Two-wire |
| Power | Loop-powered from the output loop |
| Configuration | PC programmed, standard and custom input ranges |
| Non-linear signals | User-defined conversion curves |
| Adjustment controls | No open potentiometers |
| Versions | Cabinet mounting; field version with hazardous area approvals |
| Industries | Pharmaceuticals, oil and gas, food, metals, power, water supply |
Part numbers
Show all part numbers (1)
SIY
Request a price and lead time
SIY signal isolator and converter, PC programmable, loop-powered, two-wire. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the SIY need a separate power supply?
No, the isolator is two-wire and is powered from the output current loop.
How is the input range set?
From a PC through the configuration software, to a standard or custom range, and a user curve can be entered for a non-linear signal.
Can the SIY be installed in a hazardous area?
A field version with approvals for hazardous areas recognised in several countries is available for this purpose.