International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation

The SIX in its 1-5V/4-20mA version turns a 1-5 V signal into an isolated 4-20 mA output. It runs from a 12-42 V DC loop, with +/-0.1 % of span accuracy and 1500 Vrms isolation without the -RF option. The DIN housing is 25.4 mm wide.

Type
Signal isolator, converter and repeater, 2-wire
Input
1-5 V
Output
4-20 mA
Power
12-42 V DC, loop powered

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

This SIX is supplied with a 1-5 V input and a 4-20 mA output, and can serve as an isolator, a converter or a repeater. It is a 2-wire instrument: power comes from the process loop at 12-42 V DC, so no extra supply is fitted.

As an isolator it breaks the galvanic path between a non-isolated transmitter and the receiving device, removing the false readings that ground loops, motor noise and other interference produce. As a converter it lets transmitters, controllers, recorders and control systems with dissimilar signals talk to one another. As a repeater or diverter it raises the drive capability of a loop for additional instruments, or takes a secondary signal off the loop for a recorder or indicator. Where a 4-wire transmitter and a DCS both power the same loop and clash, the SIX is installed between them.

Input impedance is 1.0 Mohm for voltage inputs of 10 V and below and 50 ohms for 4-20 mA and 0-20 mA inputs. Maximum input overrange is 250 % of full scale on current inputs and 150 % on voltage inputs. Frequency response is -3 dB at 10 Hz, output current is limited to 25 mA typical and 30 mA maximum, and the power supply effect is under 0.05 % of span.

Accuracy and linearity are both +/-0.1 % of span. Input-to-output isolation is 1500 Vrms, or 500 Vrms with the -RF option; RFI/EMI immunity is 10 V/m, or 20 V/m with -RF. Operating temperature is -40 to +85 degrees C.

The DIN-style housing measures 127.5 x 80 x 25.4 mm and mounts on 32 mm G-type (EN50035) or 35 mm Top Hat (EN50022) rail. Removable terminal blocks speed installation and servicing. Approvals: cULus Class I, Division 2, Groups A, B, C, D T4, CE to EMC Directive 2014/30/EU (EN 61326), and RoHS.

Technical specifications

TypeSignal isolator, converter and repeater, 2-wire
Input1-5 V
Output4-20 mA
Power12-42 V DC, loop powered
Accuracy+/-0.1 % of span
Linearity+/-0.1 % of span
Isolation1500 Vrms input to output; 500 Vrms with -RF option
Input impedance50 ohms for 4-20 mA and 0-20 mA inputs; 1.0 Mohm for voltage inputs of 10 V and below
Maximum input overrange250 % for current inputs; 150 % for voltage inputs
Frequency response-3 dB at 10 Hz
Output current limiting25 mA typical; 30 mA maximum
RFI/EMI immunity10 V/m; 20 V/m with -RF option
Operating temperature-40 to +85 degrees C
HousingDIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) rail
Dimensions127.5 x 80 x 25.4 mm
ApprovalscULus Class I, Division 2, Groups A, B, C, D T4; CE; RoHS

Part numbers

Show all part numbers (1)

SIX/1-5V/4-20mA/12-42DC [DIN]

How it compares with similar models

ParameterSIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms IsolationFCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount HousingFCT PRG/PRG/U/-TX Field-Configurable Signal Isolator, Converter and RepeaterFDY PC-Programmable 2-Wire Frequency-to-DC Transmitter with Display, 4-20 mA Output
TypeSignal isolator, converter and repeater, 2-wireSignal converter and isolator, 4-wireSignal isolator, converter and repeater, 4-wirePC-programmable frequency-to-DC transmitter, 2-wire
Output4-20 mA0-20 mA, 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V, 1-5 V into 20K ohms minimum; 0-10 V into 40K ohms minimum—4-20 mA, isolated, scaleable
Power12-42 V DC, loop poweredUniversal: 90-260 Vac or 22-300 Vdc; 3.5 W nominal, 5 W maximum—12-42 V DC, output loop powered
Isolation1500 Vrms input to output; 500 Vrms with -RF option1000 Vrms between input, output and power1000 Vrms between input, output and power; 500 Vac with -RF option—
Frequency response-3 dB at 10 Hz5 Hz at -3 dB5 Hz at -3 dB point—
HousingDIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) railUB with U-back bracket for surface mountingUniversal DIN-style housing, 32 mm G-type and 35 mm Top Hat railHockey puck style with DIN-rail clip

Request a price and lead time

SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the SIX need its own power supply?

No. It is a 2-wire unit and takes its power from the 12-42 V DC process loop.

What is the input-to-output isolation?

1500 Vrms. With the -RF option it is 500 Vrms and RFI/EMI immunity rises from 10 V/m to 20 V/m.

When should a SIX be placed between a 4-wire transmitter and a DCS?

When both devices supply power to the same loop and the loop stops working. The SIX accepts powered inputs on both sides and restores normal operation.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00