SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation
The SIX in its 1-5V/4-20mA version turns a 1-5 V signal into an isolated 4-20 mA output. It runs from a 12-42 V DC loop, with +/-0.1 % of span accuracy and 1500 Vrms isolation without the -RF option. The DIN housing is 25.4 mm wide.
- Type
- Signal isolator, converter and repeater, 2-wire
- Input
- 1-5 V
- Output
- 4-20 mA
- Power
- 12-42 V DC, loop powered
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
This SIX is supplied with a 1-5 V input and a 4-20 mA output, and can serve as an isolator, a converter or a repeater. It is a 2-wire instrument: power comes from the process loop at 12-42 V DC, so no extra supply is fitted.
As an isolator it breaks the galvanic path between a non-isolated transmitter and the receiving device, removing the false readings that ground loops, motor noise and other interference produce. As a converter it lets transmitters, controllers, recorders and control systems with dissimilar signals talk to one another. As a repeater or diverter it raises the drive capability of a loop for additional instruments, or takes a secondary signal off the loop for a recorder or indicator. Where a 4-wire transmitter and a DCS both power the same loop and clash, the SIX is installed between them.
Input impedance is 1.0 Mohm for voltage inputs of 10 V and below and 50 ohms for 4-20 mA and 0-20 mA inputs. Maximum input overrange is 250 % of full scale on current inputs and 150 % on voltage inputs. Frequency response is -3 dB at 10 Hz, output current is limited to 25 mA typical and 30 mA maximum, and the power supply effect is under 0.05 % of span.
Accuracy and linearity are both +/-0.1 % of span. Input-to-output isolation is 1500 Vrms, or 500 Vrms with the -RF option; RFI/EMI immunity is 10 V/m, or 20 V/m with -RF. Operating temperature is -40 to +85 degrees C.
The DIN-style housing measures 127.5 x 80 x 25.4 mm and mounts on 32 mm G-type (EN50035) or 35 mm Top Hat (EN50022) rail. Removable terminal blocks speed installation and servicing. Approvals: cULus Class I, Division 2, Groups A, B, C, D T4, CE to EMC Directive 2014/30/EU (EN 61326), and RoHS.
Technical specifications
| Type | Signal isolator, converter and repeater, 2-wire |
|---|---|
| Input | 1-5 V |
| Output | 4-20 mA |
| Power | 12-42 V DC, loop powered |
| Accuracy | +/-0.1 % of span |
| Linearity | +/-0.1 % of span |
| Isolation | 1500 Vrms input to output; 500 Vrms with -RF option |
| Input impedance | 50 ohms for 4-20 mA and 0-20 mA inputs; 1.0 Mohm for voltage inputs of 10 V and below |
| Maximum input overrange | 250 % for current inputs; 150 % for voltage inputs |
| Frequency response | -3 dB at 10 Hz |
| Output current limiting | 25 mA typical; 30 mA maximum |
| RFI/EMI immunity | 10 V/m; 20 V/m with -RF option |
| Operating temperature | -40 to +85 degrees C |
| Housing | DIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) rail |
| Dimensions | 127.5 x 80 x 25.4 mm |
| Approvals | cULus Class I, Division 2, Groups A, B, C, D T4; CE; RoHS |
Part numbers
Show all part numbers (1)
SIX/1-5V/4-20mA/12-42DC [DIN]
How it compares with similar models
| Parameter | SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation | FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing | FCT PRG/PRG/U/-TX Field-Configurable Signal Isolator, Converter and Repeater | FDY PC-Programmable 2-Wire Frequency-to-DC Transmitter with Display, 4-20 mA Output |
|---|---|---|---|---|
| Type | Signal isolator, converter and repeater, 2-wire | Signal converter and isolator, 4-wire | Signal isolator, converter and repeater, 4-wire | PC-programmable frequency-to-DC transmitter, 2-wire |
| Output | 4-20 mA | 0-20 mA, 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V, 1-5 V into 20K ohms minimum; 0-10 V into 40K ohms minimum | — | 4-20 mA, isolated, scaleable |
| Power | 12-42 V DC, loop powered | Universal: 90-260 Vac or 22-300 Vdc; 3.5 W nominal, 5 W maximum | — | 12-42 V DC, output loop powered |
| Isolation | 1500 Vrms input to output; 500 Vrms with -RF option | 1000 Vrms between input, output and power | 1000 Vrms between input, output and power; 500 Vac with -RF option | — |
| Frequency response | -3 dB at 10 Hz | 5 Hz at -3 dB | 5 Hz at -3 dB point | — |
| Housing | DIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) rail | UB with U-back bracket for surface mounting | Universal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail | Hockey puck style with DIN-rail clip |
Request a price and lead time
SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the SIX need its own power supply?
No. It is a 2-wire unit and takes its power from the 12-42 V DC process loop.
What is the input-to-output isolation?
1500 Vrms. With the -RF option it is 500 Vrms and RFI/EMI immunity rises from 10 V/m to 20 V/m.
When should a SIX be placed between a 4-wire transmitter and a DCS?
When both devices supply power to the same loop and the loop stops working. The SIX accepts powered inputs on both sides and restores normal operation.
Similar equipment from other manufacturers
![FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing](/media/no-photo-640.webp)