ECT 4-20mA/4-20mA/5.5VLP 2-Wire Input-Loop-Powered Signal Isolator and Converter
The ECT 4-20mA/4-20mA/5.5VLP isolates a 4-20 mA signal between a non-isolated transmitter and its receiver. It draws power from the input loop, has a fixed input and output, isolates at 500 Vrms and clips onto G-type or Top Hat rail.
- Type
- Signal isolator and converter, 2-wire
- Input
- 4-20 mA, fixed
- Output
- 4-20 mA, fixed
- Power (5.5VLP)
- Input loop powered
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
This ECT is a DIN-style signal isolator from a family that also includes converters, repeaters, boosters and splitters, built for process control and factory automation. In the 4-20mA/4-20mA/5.5VLP version it takes a 4-20 mA input and delivers an isolated 4-20 mA output. Input and output are fixed at the factory.
It is a 2-wire unit powered from the input loop (5.5VLP), so no separate supply is needed. Input-loop-powered ECT versions are rated at 500 Vrms isolation, while other versions in the family carry 1500 Vrms.
The ECT gives complete signal isolation between a non-isolated transmitter and a receiving device. That removes the faulty readings in measurement and control equipment caused by ground loops, motor noise and other electrical interference. For this reason an ECT is often fitted in each troublesome loop when DCS start-up exposes the effects of non-isolated transmitters.
The housing clips onto standard G-type and Top Hat rail, 32 mm and 35 mm. This version has no display, no relay output, no HART pass-through and is not meant for SIS safety systems.
Approvals: UL, Non-Incendive/Div. 2, Zone 2 and RoHS. The family conforms to EN 61326 for electromagnetic compatibility.
Technical specifications
| Type | Signal isolator and converter, 2-wire |
|---|---|
| Input | 4-20 mA, fixed |
| Output | 4-20 mA, fixed |
| Power (5.5VLP) | Input loop powered |
| Isolation | 500 Vrms for input-loop-powered versions |
| Housing | Universal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail |
| Display | None |
| Alarm/relay output | None |
| HART / SIS | HART pass-through: no; for SIS use: no |
| Approvals | UL, Non-Incendive/Div. 2, Zone 2, RoHS |
Part numbers
Show all part numbers (1)
ECT/4-20MA/4-20MA/5.5VLP
How it compares with similar models
| Parameter | ECT 4-20mA/4-20mA/5.5VLP 2-Wire Input-Loop-Powered Signal Isolator and Converter | MIT 2XPRG 2-Channel 4-Wire Signal Isolator and Converter, 20-125 VDC or 90-250 VAC Supply | HIX two-wire loop-powered HART isolator, 4-20mA, 12-42DC supply | SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation |
|---|---|---|---|---|
| Type | Signal isolator and converter, 2-wire | Multi-channel signal isolator and converter, 4-wire | two-wire loop-powered HART isolator | Signal isolator, converter and repeater, 2-wire |
| Input | 4-20 mA, fixed | — | 4-20mA (1) | 1-5 V |
| Output | 4-20 mA, fixed | — | 4-20mA (1) | 4-20 mA |
| Isolation | 500 Vrms for input-loop-powered versions | Up to 1000 Vrms input to output and channel to channel; 2500 Vrms between power and signals | 500Vrms between input, output and case | 1500 Vrms input to output; 500 Vrms with -RF option |
| Housing | Universal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail | Universal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail | aluminium, 32mm G-type or 35mm Top Hat DIN rail | DIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) rail |
| Approvals | UL, Non-Incendive/Div. 2, Zone 2, RoHS | UL, CSA General Location, Non-Incendive/Div. 2, CE, RoHS | — | cULus Class I, Division 2, Groups A, B, C, D T4; CE; RoHS |
Request a price and lead time
ECT 4-20mA/4-20mA/5.5VLP 2-Wire Input-Loop-Powered Signal Isolator and Converter. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the ECT 5.5VLP need a separate power supply?
No. It is powered from the input loop.
What isolation does this version provide?
500 Vrms, as for all input-loop-powered ECT versions.
Can the input and output ranges be changed?
No. The configuration is fixed at 4-20 mA input and 4-20 mA output.