MIX 2XPRG 2-Channel Signal Isolator and Converter, 4-20 mA, 0-5 V, 1-5 V, 0-10 V Inputs

The MIX 2XPRG packs two isolated signal channels into a housing 25.4 mm wide. Each input is set by DIP switch to 4-20 mA, 0-5 V, 1-5 V or 0-10 V, and both outputs are 4-20 mA. Isolation reaches 1000 Vrms and the unit draws 12-42 V DC from the output loop.

Type
Multi-channel signal isolator and converter, 2-wire
Number of channels
2
Input (2XPRG)
4-20 mA, 0-5 V, 1-5 V or 0-10 V, DIP-switch selectable per channel
Output (2X4-20mA)
Two 4-20 mA channels

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The 2XPRG version of the MIX carries two independent channels in a housing 25.4 mm wide. A DIP switch on each channel selects the input type: 4-20 mA, 0-5 V, 1-5 V or 0-10 V. Each channel delivers a 4-20 mA output that connects straight to an indicator, recorder, DCS, PLC or SCADA system.

Isolation between inputs and outputs, and from channel to channel, is rated up to 1000 Vrms. It breaks ground loops and blocks motor noise and other electrical interference that cause false readings. The same unit can boost a signal when more instruments must share a heavily loaded loop, or split one primary measurement between several systems.

The MIX is a 2-wire device. Power of 12-42 V DC is taken from the output loop, normally supplied by the receiving device such as a DCS or PLC, so no separate supply is needed. This also cures the clash that occurs when a 4-wire transmitter and a DCS both try to power one process loop.

The metal case screens the unit against RFI/EMI. The universal DIN-style housing clips onto 32 mm G-type or 35 mm Top Hat rail and measures 114 x 102 x 25.4 mm. Accuracy is +/-0.1 %, and humidity 0-95 % non-condensing.

Approvals comprise UL, CSA for general locations, Non-Incendive Class I, Division 2, Groups A, B, C, D, CE conformity to EMC Directive 2014/30/EU (EN 61326) and Low Voltage Directive 2014/35/EU (EN 61010), and RoHS. Signal wiring should be shielded twisted pair, with the shield earthed at the unit. The unit has no HART pass-through and is not intended for SIS applications.

Technical specifications

TypeMulti-channel signal isolator and converter, 2-wire
Number of channels2
Input (2XPRG)4-20 mA, 0-5 V, 1-5 V or 0-10 V, DIP-switch selectable per channel
Output (2X4-20mA)Two 4-20 mA channels
Power (12-42DC)12-42 V DC, drawn from the output loop
IsolationUp to 1000 Vrms, input to output and channel to channel
Accuracy+/-0.1 %
Humidity0-95 %, non-condensing
HousingUniversal DIN-style housing, 32 mm G-type and 35 mm Top Hat rail
Dimensions114 x 102 x 25.4 mm
HART / SISHART pass-through: no; for SIS use: no
ApprovalsUL, CSA General Location, Non-Incendive/Div. 2, CE, RoHS

Part numbers

Show all part numbers (1)

MIX/2XPRG/2X4-20mA/12-42DC

How it compares with similar models

ParameterMIX 2XPRG 2-Channel Signal Isolator and Converter, 4-20 mA, 0-5 V, 1-5 V, 0-10 V InputsMIT 2XPRG 2-Channel 4-Wire Signal Isolator and Converter, 20-125 VDC or 90-250 VAC SupplyFCT PRG/PRG/U/-TX Field-Configurable Signal Isolator, Converter and RepeaterSIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation
TypeMulti-channel signal isolator and converter, 2-wireMulti-channel signal isolator and converter, 4-wireSignal isolator, converter and repeater, 4-wireSignal isolator, converter and repeater, 2-wire
IsolationUp to 1000 Vrms, input to output and channel to channelUp to 1000 Vrms input to output and channel to channel; 2500 Vrms between power and signals1000 Vrms between input, output and power; 500 Vac with -RF option1500 Vrms input to output; 500 Vrms with -RF option
Accuracy+/-0.1 %+/-0.1 %+/-0.1 % of span+/-0.1 % of span
HousingUniversal DIN-style housing, 32 mm G-type and 35 mm Top Hat railUniversal DIN-style housing, 32 mm G-type and 35 mm Top Hat railUniversal DIN-style housing, 32 mm G-type and 35 mm Top Hat railDIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) rail
Dimensions114 x 102 x 25.4 mm114 x 111 x 25.4 mm—127.5 x 80 x 25.4 mm
ApprovalsUL, CSA General Location, Non-Incendive/Div. 2, CE, RoHSUL, CSA General Location, Non-Incendive/Div. 2, CE, RoHSCSA General LocationcULus Class I, Division 2, Groups A, B, C, D T4; CE; RoHS

Request a price and lead time

MIX 2XPRG 2-Channel Signal Isolator and Converter, 4-20 mA, 0-5 V, 1-5 V, 0-10 V Inputs. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the MIX 2XPRG need a separate power supply?

No. It is a 2-wire unit powered at 12-42 V DC from the output loop, which the receiving device normally supplies.

Which input signals can each channel accept?

A DIP switch sets each channel to 4-20 mA, 0-5 V, 1-5 V or 0-10 V. Every channel outputs 4-20 mA.

Are the channels isolated from each other?

Yes. Isolation between inputs and outputs, and between channels, reaches 1000 Vrms.