ACX 2-Wire AC Current Isolator and Transmitter, 4-20 mA Output, 12-42 V DC Loop Power
The ACX takes AC current and voltage from current and potential transformers and outputs a proportional 4-20 mA or 10-50 mA DC signal. It is loop-powered at 12-42 V DC, with input-output isolation to 500 Vdc and +/-0.2 % of span calibration capability.
- Type
- AC current and voltage isolator and transmitter, 2-wire
- Current input
- 0-1, 0-2, 0-3, 0-4 or 0-5 A AC, 0.1 ohm impedance
- Voltage input
- 0-0.5, 0-1.5, 0-5, 0-10, 0-25, 0-50, 0-120 or 0-150 VAC, 100 ohms per volt
- Output
- 4-20 mA into 600 ohms at 24 Vdc; 10-50 mA into 600 ohms at 42 Vdc
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 2-wire ACX accepts standard AC inputs from current and potential transformers and converts them to a proportional DC current signal, used to monitor motor currents and to interface with a distributed control system or another process instrument. It is powered from the output side of the loop at 12-42 V DC.
Current inputs are 0-1, 0-2, 0-3, 0-4 or 0-5 A AC into 0.1 ohm. Voltage inputs are 0-0.5, 0-1.5, 0-5, 0-10, 0-25, 0-50, 0-120 or 0-150 VAC at 100 ohms per volt. The output is 4-20 mA into 600 ohms with a 24 Vdc supply, or 10-50 mA into 600 ohms with 42 Vdc; load capability follows R = (E - 12) / I.
The measuring circuit contains an internal toroidal transformer that steps a 0-5 A input down to 0-5 mA AC. It isolates input from output and lets the ACX withstand large momentary overloads such as start-up or in-rush current. For personal safety the transformer can be mounted externally with the -EM option, available on current inputs: the signal at the ACX terminals stays low, and the unit can be serviced without shorting the transformer secondary. The -RF option adds RFI/EMI protection and requires -EM on current inputs.
Calibration capability is +/-0.2 % of span, or +/-0.5 % at 0-10 Vac and lower. Input and output are transformer isolated up to 500 Vdc. Overload capability is 35 A for 30 seconds with -EM, and 150 % overvoltage on voltage inputs. Ripple is 10 mV peak-to-peak maximum, ambient range is -20 to +82 degrees C with a temperature effect of +/-0.015 %/degree C, and weight is 170 g.
Housings: DIN aluminium for G-type rail, HP hockey-puck with spring clips for an explosion-proof enclosure, FL hockey-puck with flanges for surface or relay-track mounting, and 2LS hockey-puck in a 2-hub explosion-proof enclosure. The DIN housing also offers -FA front-accessible terminals and -RTB removable terminal blocks. Approvals: CE to EMC Directive 2014/30/EU, EN61326; for the ACX-HP in a BH or SB2 housing, FM Class I, Division 1, Groups A, B, C, D, Type 4X, IP66, T6, ATEX Ex d IIC T6 Gb and II 2 D Ex tb IIIC Db T85°C IP66.
Technical specifications
| Type | AC current and voltage isolator and transmitter, 2-wire |
|---|---|
| Current input | 0-1, 0-2, 0-3, 0-4 or 0-5 A AC, 0.1 ohm impedance |
| Voltage input | 0-0.5, 0-1.5, 0-5, 0-10, 0-25, 0-50, 0-120 or 0-150 VAC, 100 ohms per volt |
| Output | 4-20 mA into 600 ohms at 24 Vdc; 10-50 mA into 600 ohms at 42 Vdc |
| Power | 12-42 V DC, loop powered on output side |
| Calibration capability | +/-0.2 % of span; +/-0.5 % at 0-10 Vac and lower |
| Isolation | Transformer isolated, up to 500 Vdc |
| Overload | 35 A for 30 seconds with -EM option; 150 % overvoltage |
| Ripple | 10 mV peak-to-peak maximum |
| Ambient range | -20 to +82 degrees C |
| Temperature effect | +/-0.015 %/degree C |
| Housings | DIN aluminium (G-type rail), HP, FL, 2LS |
| Weight | 170 g |
| Approvals | CE (EMC 2014/30/EU, EN61326); FM, CSA, ATEX, ANZEx for explosion-proof enclosure versions |
Part numbers
Show all part numbers (1)
ACX/0-5AAC/4-20MA/12-42DC/-EM-FA[DIN]
How it compares with similar models
| Parameter | ACX 2-Wire AC Current Isolator and Transmitter, 4-20 mA Output, 12-42 V DC Loop Power | ACT 4-Wire AC Current and Voltage Transmitter with Input-Output Isolation | FDT 4-Wire Frequency-to-DC Transmitter with Quartz Crystal Time Base | ASM 4-Wire Adder Subtractor Module for Two to Four Analog Inputs |
|---|---|---|---|---|
| Type | AC current and voltage isolator and transmitter, 2-wire | AC current and voltage transmitter, 4-wire | Frequency-to-DC transmitter, 4-wire | Adder-subtractor module, 4-wire |
| Current input | 0-1, 0-2, 0-3, 0-4 or 0-5 A AC, 0.1 ohm impedance | 0-1, 0-2, 0-3, 0-4 or 0-5 A AC, 0.1 ohm impedance | — | 1-5 mA into 1000 ohms; 4-20 mA into 250 ohms; 10-50 mA into 100 ohms |
| Voltage input | 0-0.5, 0-1.5, 0-5, 0-10, 0-25, 0-50, 0-120 or 0-150 VAC, 100 ohms per volt | Up to 0-150 VAC, 1000 ohms per volt | — | 0-5 V, 1-5 V, 250,000 ohms minimum |
| Calibration capability | +/-0.2 % of span; +/-0.5 % at 0-10 Vac and lower | +/-0.5 % of span | — | +/-0.5 % of span |
| Isolation | Transformer isolated, up to 500 Vdc | Transformer isolated, to 500 Vrms | Input, output and power isolated | — |
| Ripple | 10 mV peak-to-peak maximum | Below 10 mV peak-to-peak | — | 10 mV peak-to-peak |
Request a price and lead time
ACX 2-Wire AC Current Isolator and Transmitter, 4-20 mA Output, 12-42 V DC Loop Power. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the input of ACX/0-5AAC/4-20MA/12-42DC?
AC current of 0-5 A into 0.1 ohm, with a 4-20 mA output and 12-42 V DC loop power.
Why mount the input transformer externally?
The -EM option keeps the signal at the unit terminals low and lets the unit be taken out of service without shorting the transformer secondary; it is required for current inputs with -RF.
Can the ACX survive surge currents?
Yes. The internal transformer isolates the input and withstands large momentary overloads, rated 35 A for 30 seconds with the -EM option.
Similar equipment from other manufacturers