International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

T2X-DWB wall-mount room air temperature monitoring system, 4-20 mA output

The T2X-DWB is a PC-programmable wall-mount transmitter with an internal 1000 ohm platinum RTD for room air temperature. It gives a 4-20 mA output linear with temperature on 8-42 Vdc, with input accuracy of ±0.4°C.

Sensor
Pt 3850 RTD, 1000 ohm, internal
Output
4-20 mA, linear with temperature
Power supply
8-42 Vdc ±10%
Load
700 ohms at 24 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The T2X-DWB puts a T2X transmitter into a decorative wall box for indoor temperature sensing. The 1000 ohm Pt 3850 RTD is built in and fixed, and the vented housing and sensor position are arranged for maximum air flow.

The 4-20 mA output is proportional and linear with temperature, ready to connect to a monitoring or control system. Supply is 8-42 Vdc ±10%, and the unit drives 700 ohms at 24 V. Minimum span is 10°C. The output updates at least 8 times per second, and response time is typically 256 ms and at most 360 ms for a 10% to 90% change.

Input accuracy is ±0.4°C for the platinum RTD, and output accuracy adds 0.1% of output span. Stability at maximum span is ±0.12% over 1 year, ±0.21% over 3 years and ±0.27% over 5 years. Ambient temperature effect is ±0.015% of span per °C. Noise rejection is 100 dB common mode at 50/60 Hz and typically 70 dB normal mode.

All settings are made in the PC configuration software and kept in non-volatile memory. Input and output scaling are independent, the digital filter is selectable for 50/60 Hz, and burnout can be programmed upscale to 23.6 mA or downscale to 3.3 mA.

Operating range is -40°C to +85°C, storage -55°C to +105°C, humidity 0-95% non-condensing. The output is protected against over-voltage and reverse polarity up to 48 Vdc. The unit meets EMC Directive 2014/30/EU and EN 61326. Housings are DWB and DWBDN (with DIN clips), and weight is 113 g.

Technical specifications

SensorPt 3850 RTD, 1000 ohm, internal
Output4-20 mA, linear with temperature
Power supply8-42 Vdc ±10%
Load700 ohms at 24 V
Input accuracy±0.4°C (±0.7°F)
Output accuracyinput accuracy + 0.1% of output span
Minimum span10°C (18°F)
Stability1 year ±0.12%; 3 years ±0.21%; 5 years ±0.27%
Output response time256 ms typical, 360 ms maximum
Burnoutupscale to 23.6 mA or downscale to 3.3 mA
Operating range-40°C to +85°C
Storage range-55°C to +105°C
Humidity0-95%, non-condensing
Weight113 g

Part numbers

Show all part numbers (5)

T2X-DWB, software 750-75E05-01, cables 803-039-26, 803-040-26, USB cable 804-030-26

How it compares with similar models

ParameterT2X-DWB wall-mount room air temperature monitoring system, 4-20 mA outputT2X (TEMPTATION 2000) PC-programmable RTD temperature transmitter, 4-20mA, 8-42DC, non-isolatedECT-DIN 15 mm signal isolator and converter, 1-5 V to 4-20 mALRX 2-wire low-power temperature transmitter with 1-5 Vdc output
Output4-20 mA, linear with temperature4-20mA, linear with temperature, non-isolated4-20 mA, one output1-5 Vdc, proportional to input
Power supply8-42 Vdc ±10%—12-42 Vdc, 2-wire, from the output loop8-30 Vdc
Operating range-40°C to +85°C—-40°C to +85°C-45°C to +82°C

Request a price and lead time

T2X-DWB wall-mount room air temperature monitoring system, 4-20 mA output. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How is the T2X-DWB configured?

With the PC configuration software: input and output scaling, a 50/60 Hz digital filter and the burnout direction.

What supply and load apply to the 4-20 mA output?

Supply is 8-42 Vdc, and the load can be up to 700 ohms at 24 V.

Can the internal sensor be replaced?

No. Calibration is set at the factory and the sensor cannot be removed.