LRX 2-wire low-power temperature transmitter with 1-5 Vdc output
The LRX takes a 3-wire platinum RTD, a K-type thermocouple or a direct millivolt signal up to 100 mV and gives a linear 1-5 Vdc output. It runs from a solar panel or battery at 8-30 Vdc. Ambient range is -45°C to +82°C.
- RTD input
- 3-wire Pt 100 ohm, alpha 0.00385 ohm/°C, 0-500°F
- Thermocouple input
- K-type, 0-2500°F
- Direct input
- up to 100 mV
- Output
- 1-5 Vdc, proportional to input
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Remote well-head installations and other sites without line power are the place for the LRX. It is a 2-wire loop-powered transmitter, supplied with 8-30 Vdc from a solar panel or a battery.
Three input types are accepted: a 3-wire 100 ohm platinum RTD (alpha 0.00385 ohm/°C) over 0-500°F, a K-type thermocouple over 0-2500°F, or a direct millivolt signal up to 100 mV. The output is a linear 1-5 Vdc signal for indicators, recorders, a DCS or SCADA, into a load of 100 kohms or more.
Accuracy is ±0.15% of span, including linearity, hysteresis and repeatability. Output ripple stays below 10 mV peak-to-peak and the ambient temperature effect is at most ±0.02% of span per °C. Zero and span are set with front-panel potentiometers over ±5% of input span.
The unit operates at ambient temperatures from -45°C to +82°C and can be stored from -45°C to +100°C, at 0-95% relative humidity, non-condensing. Immunity to radio-frequency and electromagnetic interference is 10 V/m at 80-1000 MHz when tested to IEC61326, with an error of 0.5% of span or less. The factory-fitted -RF option raises this to 20 V/m.
Housing choices are the HP hockey-puck case with spring clips (76 x 38 x 73 mm) for explosion-proof enclosures, the HP case with snap-in mounting on TS-32 DIN rail (DN), the explosion-proof enclosures BH2NS and BH3NS with two or three 1/2-inch NPT entries, and the D2LS NEMA 4X (IP66) enclosure. The range is given at ordering, for example PT1-0-500F.
Technical specifications
| RTD input | 3-wire Pt 100 ohm, alpha 0.00385 ohm/°C, 0-500°F |
|---|---|
| Thermocouple input | K-type, 0-2500°F |
| Direct input | up to 100 mV |
| Output | 1-5 Vdc, proportional to input |
| Power supply | 8-30 Vdc |
| Output load | 100 kohms minimum |
| Accuracy | ±0.15% of span |
| Output ripple | below 10 mV peak-to-peak |
| Temperature effect | ±0.02% of span per °C, maximum |
| Operating range | -45°C to +82°C |
| Storage range | -45°C to +100°C |
| Humidity | 0-95%, non-condensing |
| Adjustment | zero and span potentiometers, ±5% of input span |
| Dimensions (HP case) | 76 x 38 x 73 mm |
How it compares with similar models
| Parameter | LRX 2-wire low-power temperature transmitter with 1-5 Vdc output | ECT-DIN 15 mm signal isolator and converter, 1-5 V to 4-20 mA | T2X-DWB wall-mount room air temperature monitoring system, 4-20 mA output | FDY PC-Programmable 2-Wire Frequency-to-DC Transmitter with Display, 4-20 mA Output |
|---|---|---|---|---|
| Output | 1-5 Vdc, proportional to input | 4-20 mA, one output | 4-20 mA, linear with temperature | 4-20 mA, isolated, scaleable |
| Power supply | 8-30 Vdc | 12-42 Vdc, 2-wire, from the output loop | 8-42 Vdc ±10% | — |
| Operating range | -45°C to +82°C | -40°C to +85°C | -40°C to +85°C | — |
| Humidity | 0-95%, non-condensing | 0-95%, non-condensing | 0-95%, non-condensing | 0-95 %, non-condensing |
Request a price and lead time
LRX 2-wire low-power temperature transmitter with 1-5 Vdc output. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which inputs does the LRX accept?
A 3-wire 100 ohm platinum RTD (0-500°F), a K-type thermocouple (0-2500°F) and a direct millivolt input up to 100 mV.
What supply and output signal does it use?
It runs on 8-30 Vdc, for example from a solar panel or battery, and gives 1-5 Vdc into a load of 100 kohms or more.
Which housings are available?
The HP case with spring clips or DIN-rail mounting on TS-32 (DN), the explosion-proof enclosures BH2NS and BH3NS, and the D2LS NEMA 4X (IP66) enclosure.
Similar equipment from other manufacturers