International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SPT site-programmable isolated temperature transmitter, T/C, RTD, ohms, mV, 4-20mA or 1-5V

The SPT accepts T/C, RTD, millivolt or ohms input and gives an isolated, process-ready 4-20mA or 1-5V output with local indication. It is set up by push buttons and auto-senses 22-300VDC or 90-260VAC power.

Type
Site-programmable isolated temperature transmitter
Input
T/C (all common ISA), 2-, 3- or 4-wire RTD, ohms, mV
Input modes
Single sensor, average of multiple sensors, dual sensor differential
Output
4-20mA (source or sink) or 1-5V, switch selectable

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The SPT accepts T/C, RTD, millivolt or ohms input in a host of ranges, sensor types and connection schemes. It provides an isolated, process-ready analogue output along with local indication, in a compact DIN-style housing that fits G-type and Top Hat rails. A switch selects 4-20mA or 1-5V.

The input takes all common ISA thermocouples, 2-, 3- or 4-wire RTDs and direct ohm or millivolt sources. The menu offers output based on a single sensor, the average of multiple sensors, or a dual sensor differential. The 4-20mA output works in source or sink mode.

Setup and calibration need no tools, calibrators or configurators, only push buttons. A large LCD screen leads the user through a simple menu with every option spelled out in plain English. All settings are held in non-volatile memory, protected from power loss and unauthorised changes, and parameters can be viewed at any time without affecting operation. The display shows the input in real time in either °C or °F.

Power is auto-sensing at 22-300VDC or 90-260VAC, with no jumpers or switches to set, so the unit can serve as a universal spare for temperature applications. Output accuracy is ±0.03% of output span, cold junction reference accuracy is ±0.25°C and stability is ±0.1% of calibrated span max over six months. Output limiting is 117% of span max, 115% typical. Load capability is 1200Ω max for current outputs in source mode and 2000Ω max in sink mode.

For hazardous areas the rating is Non-Incendive/Div. 2, Zone 2. Certifications include FM Non-Incendive Class I, Division 2, Groups A, B, C, D, suitability for Class II, Division 2 and Class III, Divisions 1 and 2, and CSA General (Ordinary) Location. The unit is not for use in SIS.

Technical specifications

TypeSite-programmable isolated temperature transmitter
InputT/C (all common ISA), 2-, 3- or 4-wire RTD, ohms, mV
Input modesSingle sensor, average of multiple sensors, dual sensor differential
Output4-20mA (source or sink) or 1-5V, switch selectable
Power22-300VDC or 90-260VAC, auto-sensing
Power connection4-Wire 24DC/117VAC/230VAC line/mains powered
HousingDIN-style, 32mm G-type and 35mm Top Hat
DisplayLCD, input in °C or °F
ConfigurationPush button, on-screen menu
IsolationFully isolated
Output accuracy±0.03% of output span
Cold junction reference accuracy±0.25°C
Output limiting117% of span max, 115% typical
Load capability1200Ω max (4-20mA, source), 2000Ω max (sink)
Stability±0.1% of calibrated span max over six months
Hazardous area certificationsNon-Incendive/Div. 2, Zone 2
For use in SISNo

Part numbers

Show all part numbers (1)

SPT/TPRG/PRG/U [DIN]

How it compares with similar models

ParameterSPT site-programmable isolated temperature transmitter, T/C, RTD, ohms, mV, 4-20mA or 1-5VSPA2 programmable temperature transmitter and alarm trip, RTD, T/C, mV, ohms, 2 relays, analogue outputSPA2IS programmable temperature transmitter and alarm trip with intrinsically safe inputs, 2 relaysTHZ3 dual input HART temperature transmitter for DIN rail, 4-20mA, 12-42DC
TypeSite-programmable isolated temperature transmitterProgrammable temperature transmitter and alarm tripProgrammable temperature transmitter and alarm trip with intrinsically safe field connectionsDual input HART temperature transmitter for DIN rail mounting
InputT/C (all common ISA), 2-, 3- or 4-wire RTD, ohms, mVRTD (23 types), T/C (9 types), mV, ohms, potentiometerRTD (23 types), T/C (9 types), mV, ohms, potentiometerDual sensor, programmable: RTD, T/C, mV, ohms, potentiometer
Power22-300VDC or 90-260VAC, auto-sensing21.6-375VDC or 90-260VAC21.6-125VDC or 90-260VAC12-42DC, 2-wire, loop powered
HousingDIN-style, 32mm G-type and 35mm Top HatDIN-style, 35mm (EN50022) Top Hat DIN railDIN-style, 35mm (EN50022) Top Hat DIN railDIN rail mount, DIN rail enclosure
DisplayLCD, input in °C or °F5-digit, backlit5-digit, backlit—
ConfigurationPush button, on-screen menuPC, USB cable, push buttonsPC, USB cable, push buttonsPC, USB cable, HART

Request a price and lead time

SPT site-programmable isolated temperature transmitter, T/C, RTD, ohms, mV, 4-20mA or 1-5V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which inputs does the SPT accept?

All common ISA thermocouples, 2-, 3- or 4-wire RTDs and direct ohm or millivolt sources. Output can follow a single sensor, an average or a differential.

What power does the SPT need?

22-300VDC or 90-260VAC. It is auto-sensing, with no jumpers or switches to set.

What load can the current output drive?

Up to 1200Ω for 4-20mA in source mode and up to 2000Ω in sink mode.