International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

RIY programmable isolated RTD transmitter, 4-20mA, 12-42DC, push button setup, display

The RIY converts a 2-, 3- or 4-wire RTD or ohms input into 4-20mA, linear with temperature or with ohms. It is a 2-wire 12-42DC unit with push button ranging and an integral display.

Type
Programmable isolated RTD transmitter
Input
2-, 3- or 4-wire RTD or resistance source
Output
4-20mA, linear with temperature or ohm input, direct or reverse
Power
12-42DC, 2-wire, loop powered

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The RIY is a digital/analogue hybrid: a microprocessor-based, 2-wire, programmable isolated RTD transmitter. It accepts a non-linear temperature input from any standard 2-, 3- or 4-wire RTD, or a resistance source, and provides a 4-20mA output linear with temperature or with the ohm input. The output can be direct or reverse.

No hand-held configurator and no calibrator are needed. RTD type, range and upscale or downscale drive are selected in the field with tactile push buttons and easily accessible switches. Zero and span are set by Quick Ranging while reading the integral indicator, and the values are stored in EEPROM and retained when power is lost. The switches also select quick or standard ranging and keyboard lockout or enable.

A 4-digit LCD is standard, and the ND option gives a unit without it. The display reads the input in °C, °F or ohms and shows problem codes, and it keeps showing the current process temperature even if the output goes overrange or underrange. If a break in an RTD wire is detected, the display indicates which wire is broken. Upscale drive is standard and the DD option sets downscale drive on loss of input. A true differential temperature input is available, with two separate inputs and an output reflecting their difference.

Two housing styles are offered: hockey puck (HP) and DIN-style. The HP housing has spring clips for mounting in explosionproof enclosures, and with FL flange plates it mounts on a flat surface or on relay tracks. The all-aluminium DIN-style housing snaps onto G-type or Top-hat rails. Sensor excitation current is 250µA nominal, stability is ±0.1% or better of calibrated span for 6 months, and ripple is below 10mV peak-to-peak up to 120 Hz across a 250 ohm resistor. Input/output isolation prevents false signals from ground loops. For hazardous areas the rating is Non-Incendive/Div. 2, Zone 2. The unit is not for use in SIS and is RoHS compliant.

Technical specifications

TypeProgrammable isolated RTD transmitter
Input2-, 3- or 4-wire RTD or resistance source
Output4-20mA, linear with temperature or ohm input, direct or reverse
Power12-42DC, 2-wire, loop powered
HousingHockey puck housing with DIN rail clip
MountingDIN rail adapter for field mounted electronics
Integral displayYes, 4-digit LCD
ConfigurationPush buttons, switches
Sensor excitation current250µA nominal
Stability±0.1% or better of calibrated span for 6 months
RippleLess than 10mV peak-to-peak max (up to 120 Hz), across a 250 ohm resistor
IsolationFully isolated
Hazardous area certificationsNon-Incendive/Div. 2, Zone 2
For use in SISNo
RoHSYes

Part numbers

Show all part numbers (2)

RIY/PRG/4-20mA/12-42DC [DN], RIY/PRG/4-20mA/12-42DC

How it compares with similar models

ParameterRIY programmable isolated RTD transmitter, 4-20mA, 12-42DC, push button setup, displayTDZ3 dual input HART temperature transmitter, 4-20mA, 12-42DC loop poweredTDY PC-programmable temperature transmitter with large display, 4-20mA, 10-42DCSTZ functional safety dual input HART temperature transmitter, SIL 2/3, 4-20mA, 12-42DC
TypeProgrammable isolated RTD transmitterDual input smart HART temperature transmitterPC-programmable temperature transmitter with displayFunctional safety dual input smart HART temperature transmitter
Input2-, 3- or 4-wire RTD or resistance sourceDual sensor, programmable: RTD, T/C, mV, ohms, potentiometer—One or two sensors: RTD (14 types), T/C (9 types), mV, ohms, potentiometer
Output4-20mA, linear with temperature or ohm input, direct or reverse4-20mA with HART4-20mA, linear, scalable, 4-20mA only4-20mA with HART (HART 7)
Power12-42DC, 2-wire, loop powered12-42DC, 2-wire, loop powered10-42DC, 2-wire, loop powered12-42DC, 2-wire, loop powered
Integral displayYes, 4-digit LCDYesYes, largeYes
ConfigurationPush buttons, switchesPC, USB cable, HARTPC, USB cablePC, USB cable, HART

Request a price and lead time

RIY programmable isolated RTD transmitter, 4-20mA, 12-42DC, push button setup, display. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which inputs does the RIY accept?

A 2-, 3- or 4-wire RTD or a resistance source. The 4-20mA output is linear with temperature or with ohms, direct or reverse.

How is the RIY calibrated?

Zero and span are set with the push buttons by Quick Ranging, reading the integral indicator, with no calibrator. The values are stored in EEPROM.

What happens if an RTD wire breaks?

The display indicates which RTD wire is broken. Upscale drive is standard, and the DD option sets downscale drive.