STZ functional safety dual input HART temperature transmitter, SIL 2/3, 4-20mA, 12-42DC
The STZ is a SIL 2/3 capable temperature transmitter for safety instrumented systems. It takes one or two sensor inputs, outputs 4-20mA with HART and is loop powered at 12-42DC.
- Type
- Functional safety dual input smart HART temperature transmitter
- Input
- One or two sensors: RTD (14 types), T/C (9 types), mV, ohms, potentiometer
- Output
- 4-20mA with HART (HART 7)
- Power
- 12-42DC, 2-wire, loop powered
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The STZ belongs to the FS functional safety series and is built for Safety Instrumented Systems (SIS). It accepts a single or dual input from sensors and analogue devices in hazardous and non-hazardous areas: 14 RTD types, 9 thermocouple types, resistance and potentiometer devices and direct millivolt sources.
The device is certified by exida to IEC 61508:2010, with systematic integrity up to SIL 3 and random integrity up to SIL 2. A single STZ is approved for SIS use up to SIL 2, and in a redundant architecture (1oo2, 2oo3 and so on) up to SIL 3. Certified FMEDA data is available on request.
This 2-wire, loop powered transmitter gives an isolated, linear 4-20mA output proportional to the input, ready for HART and non-HART safety systems, DCS, PLC and SCADA. It is HART 7 compliant, with exception-based reporting and dynamic variable mapping. HART access can be set to read only or off, so the configuration cannot be changed by accident while the safety function is running.
With two sensors the user gets backup and failover, average and differential measurement, and low or high select. Diagnostics cover sensor drift and corrosion detection, smart range alarms, a high-availability option and input simulation.
Input-to-output analogue accuracy reaches ±0.014°C (±0.025°F). Input resolution is 20-bit, giving digital accuracy of ±0.1°C (±0.18°F) with all Pt RTDs and up to ±0.05°C (±0.09°F) for Pt1000. The best figures apply to a 4-wire, 1000 ohm platinum RTD with a span of 100°F (50°F minimum), calibrated in a sensor-matching bath.
Mounting choices are field enclosures with display, compact connection heads without display and a high-density DIN-style housing. The STZ-DIN model with the -AIS option connects sensors in hazardous locations directly, without an intrinsically safe barrier, and has blue terminals. Setup is by a HART handheld, a HART host, a PC over USB or an FDT host such as PACTware using the DTM.
Technical specifications
| Type | Functional safety dual input smart HART temperature transmitter |
|---|---|
| Input | One or two sensors: RTD (14 types), T/C (9 types), mV, ohms, potentiometer |
| Output | 4-20mA with HART (HART 7) |
| Power | 12-42DC, 2-wire, loop powered |
| Functional safety | Systematic integrity up to SIL 3, random integrity up to SIL 2 |
| Standard | IEC 61508:2010 |
| Input-to-output analogue accuracy | Up to ±0.014°C (±0.025°F) |
| Digital accuracy | ±0.1°C (±0.18°F) with Pt RTDs, up to ±0.05°C (±0.09°F) for Pt1000 |
| Input resolution | 20-bit |
| Housing | Hockey puck housing with DIN rail clip |
| Integral display | Yes |
| Alarm / relay output | No |
| Configuration | PC, USB cable, HART |
| Isolation | Fully isolated |
| Hazardous area certifications | Non-Incendive/Div. 2, Zone 2 |
| For use in SIS | Yes |
| RoHS | Yes |
Part numbers
Show all part numbers (4)
STZ/PRG/4-20mA/12-42DC [DN], STZ/PRG/4-20MA/12-30DC/[HP], STZ/PRG/4-20MA/12-30DC/[HPP], STZ/PRG/4-20MA/12-30DC/[DIN]
How it compares with similar models
| Parameter | STZ functional safety dual input HART temperature transmitter, SIL 2/3, 4-20mA, 12-42DC | TDZ3 dual input HART temperature transmitter, 4-20mA, 12-42DC loop powered | STZ associated IS dual input HART temperature transmitter (-AIS), SIL 2/3, 4-20mA | THZ3 dual input HART temperature transmitter for DIN rail, 4-20mA, 12-42DC |
|---|---|---|---|---|
| Type | Functional safety dual input smart HART temperature transmitter | Dual input smart HART temperature transmitter | Functional safety dual input associated IS HART temperature transmitter | Dual input HART temperature transmitter for DIN rail mounting |
| Input | One or two sensors: RTD (14 types), T/C (9 types), mV, ohms, potentiometer | Dual sensor, programmable: RTD, T/C, mV, ohms, potentiometer | One or two sensors: RTD, T/C, mV, ohms, potentiometer | Dual sensor, programmable: RTD, T/C, mV, ohms, potentiometer |
| Output | 4-20mA with HART (HART 7) | 4-20mA with HART | 4-20mA with HART | 4-20mA, isolated, linear, with HART |
| Housing | Hockey puck housing with DIN rail clip | Hockey puck housing with DIN rail clip | DIN rail mount, DIN rail enclosure | DIN rail mount, DIN rail enclosure |
| Integral display | Yes | Yes | No | No |
| Hazardous area certifications | Non-Incendive/Div. 2, Zone 2 | Non-Incendive/Div. 2, Zone 2 | Non-Incendive/Div. 2, Zone 2, Associated Intrinsically-Safe | Non-Incendive/Div. 2, Zone 2 |
Request a price and lead time
STZ functional safety dual input HART temperature transmitter, SIL 2/3, 4-20mA, 12-42DC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What SIL can the STZ be used for?
A single STZ is approved for SIS use up to SIL 2, and in a redundant architecture (1oo2, 2oo3 and so on) up to SIL 3. It is certified by exida to IEC 61508:2010.
What dual sensor modes are available?
Backup and failover, average, differential, and low or high select. Sensor drift and corrosion detection are included.
How can the settings be protected while the loop is in service?
HART access can be set to read only or switched off. This prevents accidental or unauthorised reconfiguration while the safety function is working.