THZ3 associated IS dual input HART temperature transmitter (-AIS), 4-20mA, DIN rail

The THZ3 with the -AIS option is an associated apparatus. It is installed in a non-hazardous or Class I Division 2/Zone 2 area and connects directly to sensors in Class I Div 1/Zone 0/1 locations.

Type
Dual input associated IS HART temperature transmitter
Input
Dual sensor, programmable: RTD, T/C, mV, ohms, potentiometer
Output
4-20mA with HART
Power
12-42DC, 2-wire, loop powered

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The THZ3 with the -AIS option is an associated apparatus. It is suitable for installation in non-hazardous or Class I Division 2/Zone 2 areas, with direct connection to temperature sensors located in Class I Div 1/Zone 0/1 locations. The -AIS option provides associated intrinsically safe input connections.

The transmitter accepts a direct signal from sensors and analogue devices in hazardous and non-hazardous areas. The input is programmable for an RTD, thermocouple (T/C), millivolt source, ohms or a potentiometer. The two input sensors are individually selectable and programmable.

Features include backup and fail-over protection, average and differential measurement, dynamic variable mapping and high-select and low-select abilities. The output is 4-20mA with HART, and the unit is a 2-wire device powered from the loop at 12-42DC.

The housing is a DIN rail enclosure with no integral display. Configuration is from a PC over a USB cable or over HART. The unit is fully isolated. The hazardous area rating is Non-Incendive/Div. 2, Zone 2, Associated Intrinsically-Safe. There is no alarm or relay output and no enhanced RFI/EMI immunity, and the transmitter is not for use in SIS. It is RoHS compliant.

Technical specifications

TypeDual input associated IS HART temperature transmitter
InputDual sensor, programmable: RTD, T/C, mV, ohms, potentiometer
Output4-20mA with HART
Power12-42DC, 2-wire, loop powered
Option -AISAssociated IS input connections
Intrinsically safe input connectionsYes
HousingDIN rail mount, DIN rail enclosure
Integral displayNo
Alarm / relay outputNo
ConfigurationPC, USB cable, HART
IsolationFully isolated
Hazardous area certificationsNon-Incendive/Div. 2, Zone 2, Associated Intrinsically-Safe
For use in SISNo
RoHSYes

Part numbers

Show all part numbers (1)

THZ3/PRG/4-20mA/12-42DC/-AIS [DIN]

How it compares with similar models

ParameterTHZ3 associated IS dual input HART temperature transmitter (-AIS), 4-20mA, DIN railSTZ associated IS dual input HART temperature transmitter (-AIS), SIL 2/3, 4-20mATHZ3 dual input HART temperature transmitter for DIN rail, 4-20mA, 12-42DCTDZ3 dual input HART temperature transmitter, 4-20mA, 12-42DC loop powered
TypeDual input associated IS HART temperature transmitterFunctional safety dual input associated IS HART temperature transmitterDual input HART temperature transmitter for DIN rail mountingDual input smart HART temperature transmitter
InputDual sensor, programmable: RTD, T/C, mV, ohms, potentiometerOne or two sensors: RTD, T/C, mV, ohms, potentiometerDual sensor, programmable: RTD, T/C, mV, ohms, potentiometerDual sensor, programmable: RTD, T/C, mV, ohms, potentiometer
Output4-20mA with HART4-20mA with HART4-20mA, isolated, linear, with HART4-20mA with HART
Intrinsically safe input connectionsYesYesNoNo
HousingDIN rail mount, DIN rail enclosureDIN rail mount, DIN rail enclosureDIN rail mount, DIN rail enclosureHockey puck housing with DIN rail clip
Integral displayNoNoNoYes

Request a price and lead time

THZ3 associated IS dual input HART temperature transmitter (-AIS), 4-20mA, DIN rail. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Where can the THZ3 with the -AIS option be installed?

In non-hazardous or Class I Division 2/Zone 2 areas. Sensors in Class I Div 1/Zone 0/1 locations connect directly.

What dual sensor functions are available?

Backup and fail-over protection, average and differential measurement, dynamic variable mapping, and high-select and low-select.

How is the transmitter configured?

From a PC over a USB cable or over HART. There is no integral display.