THZ3 dual input HART temperature transmitter for DIN rail, 4-20mA, 12-42DC
The THZ3 accepts two sensors and gives an isolated, linear 4-20mA output with HART. It is a 2-wire, loop powered unit at 12-42DC in a DIN rail enclosure, rated Non-Incendive/Div. 2, Zone 2.
- Type
- Dual input HART temperature transmitter for DIN rail mounting
- Input
- Dual sensor, programmable: RTD, T/C, mV, ohms, potentiometer
- Output
- 4-20mA, isolated, linear, with HART
- Power
- 12-42DC, 2-wire, loop powered
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The THZ3 is a loop powered, 2-wire HART temperature transmitter. It accepts a direct signal input from sensors and analogue devices located in hazardous and non-hazardous areas. The input is programmed for an RTD, thermocouple (T/C), millivolt source, ohms or a potentiometer.
The two input sensors are individually selectable and programmable, which gives more control over temperature measurements. The 4-20mA output is isolated and linear, and the supply is 12-42DC. The transmitter can be interrogated at any time from anywhere on the 4-20mA loop.
Setup is from a HART host, a communicator or an FDT-compliant host or program, and also from a PC over a USB cable. This version is built in a DIN rail enclosure and has no integral display.
For hazardous areas the rating is Non-Incendive/Div. 2, Zone 2. There are no intrinsically safe input connections, no alarm or relay output, no enhanced RFI/EMI immunity and no 2 inch pipe mount bracket. The transmitter is not for use in SIS. It is RoHS compliant.
The series is offered in 24 versions. The suffix [DIN] marks the DIN rail housing, and there are also the codes [HPP], [HPPDN], [LH1NX], [LH2NS] and others.
Technical specifications
| Type | Dual input HART temperature transmitter for DIN rail mounting |
|---|---|
| Input | Dual sensor, programmable: RTD, T/C, mV, ohms, potentiometer |
| Output | 4-20mA, isolated, linear, with HART |
| Power | 12-42DC, 2-wire, loop powered |
| Housing | DIN rail mount, DIN rail enclosure |
| Integral display | No |
| Alarm / relay output | No |
| Intrinsically safe input connections | No |
| Configuration | PC, USB cable, HART |
| Isolation | Fully isolated |
| Enhanced RFI/EMI immunity | No |
| Hazardous area certifications | Non-Incendive/Div. 2, Zone 2 |
| For use in SIS | No |
| RoHS | Yes |
Part numbers
Show all part numbers (5)
THZ3/PRG/4-20mA/12-42DC [DIN], THZ3/PRG/4-20mA/12-42DC/-RF [DIN], THZ3/PRG/4-20mA/12-42DC [HPP], THZ3/PRG/4-20mA/12-42DC [HPPDN], THZ3/PRG/4-20mA/12-30DC [HPP]
How it compares with similar models
| Parameter | THZ3 dual input HART temperature transmitter for DIN rail, 4-20mA, 12-42DC | TDZ3 dual input HART temperature transmitter, 4-20mA, 12-42DC loop powered | THZ3 associated IS dual input HART temperature transmitter (-AIS), 4-20mA, DIN rail | STZ associated IS dual input HART temperature transmitter (-AIS), SIL 2/3, 4-20mA |
|---|---|---|---|---|
| Type | Dual input HART temperature transmitter for DIN rail mounting | Dual input smart HART temperature transmitter | Dual input associated IS HART temperature transmitter | Functional safety dual input associated IS HART temperature transmitter |
| Input | Dual sensor, programmable: RTD, T/C, mV, ohms, potentiometer | Dual sensor, programmable: RTD, T/C, mV, ohms, potentiometer | Dual sensor, programmable: RTD, T/C, mV, ohms, potentiometer | One or two sensors: RTD, T/C, mV, ohms, potentiometer |
| Output | 4-20mA, isolated, linear, with HART | 4-20mA with HART | 4-20mA with HART | 4-20mA with HART |
| Housing | DIN rail mount, DIN rail enclosure | Hockey puck housing with DIN rail clip | DIN rail mount, DIN rail enclosure | DIN rail mount, DIN rail enclosure |
| Integral display | No | Yes | No | No |
| Intrinsically safe input connections | No | No | Yes | Yes |
Request a price and lead time
THZ3 dual input HART temperature transmitter for DIN rail, 4-20mA, 12-42DC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which input signals does the THZ3 accept?
Two programmable inputs for RTD, T/C, mV, ohms or potentiometer. Each sensor is selected and programmed individually.
How is the THZ3 configured?
From a HART host, a communicator or an FDT-compliant host or program, and also from a PC over a USB cable.
Does this version have intrinsically safe inputs?
No, there are no intrinsically safe input connections. For hazardous areas the rating is Non-Incendive/Div. 2, Zone 2.