SPA2 programmable temperature transmitter and alarm trip, RTD, T/C, mV, ohms, 2 relays, analogue output
The SPA2 accepts RTD, T/C, mV, ohms or potentiometer input, has two independent alarm relays, an optional programmable analogue output (-AO) and a 5-digit display. Power is 21.6-375VDC or 90-260VAC.
- Type
- Programmable temperature transmitter and alarm trip
- Input
- RTD (23 types), T/C (9 types), mV, ohms, potentiometer
- Alarm outputs
- Two independent, individually configurable alarm relay outputs
- Analogue output (option -AO)
- Programmable, any range between 0-20mA and 0-10V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The SPA2 is a programmable limit alarm trip with a temperature input. It provides on/off control, warns of unwanted process conditions, alarms on rate-of-change and provides emergency shutdown. The input accepts 23 RTD types, 9 thermocouple types, resistance and potentiometer devices and direct millivolt sources.
The unit is 4-wire and line/mains powered. The universal supply is 21.6-375VDC or 90-260VAC, so there is no need to stock dozens of different alarm trips. Two independent, individually configurable alarm relay outputs operate when the monitored variable falls outside the user-set high and/or low limits, and can drive a warning light, annunciator, bell, pump, motor or shutdown system. Trip points, high alarm, low alarm, failsafe, non-failsafe, normally open and normally closed are all configurable.
Parameters are set with the front panel push buttons or the free Windows software: input type and range, input and output trimming, password protection, and high or low trip, out of band, rate of change or stuck input alarms. Input resolution is 20-bit and the interval between calibrations is up to 5 years. The large 5-digit backlit display shows menu prompts, the process variable, the output, or toggles between the two.
The -AO option adds a programmable analogue output in any range between 0-20mA and 0-10V, so alarm and transmitter functions sit at the same location. The metal, RFI resistant housing snaps onto 35mm (EN50022) Top Hat DIN rails. Isolation and RFI/EMI protection reduce the effects of ground loops. The rating is Non-Incendive/Div. 2, Zone 2, and the unit is CE conformant to Directives 2014/30/EU (EN 61326) and 2014/35/EU (EN 61010-1). It is not for use in SIS.
Technical specifications
| Type | Programmable temperature transmitter and alarm trip |
|---|---|
| Input | RTD (23 types), T/C (9 types), mV, ohms, potentiometer |
| Alarm outputs | Two independent, individually configurable alarm relay outputs |
| Analogue output (option -AO) | Programmable, any range between 0-20mA and 0-10V |
| Power | 21.6-375VDC or 90-260VAC |
| Power connection | 4-Wire 24DC/117VAC/230VAC line/mains powered |
| Housing | DIN-style, 35mm (EN50022) Top Hat DIN rail |
| Display | 5-digit, backlit |
| Input resolution | 20-bit |
| Stability | Up to 5 years between scheduled calibrations |
| Configuration | PC, USB cable, push buttons |
| Isolation | Fully isolated |
| Intrinsically safe input connections | No |
| Hazardous area certifications | Non-Incendive/Div. 2, Zone 2 |
| For use in SIS | No |
| RoHS | Yes |
Part numbers
Show all part numbers (1)
SPA2/TPRG/2PRG/U/-AO [DIN]
How it compares with similar models
| Parameter | SPA2 programmable temperature transmitter and alarm trip, RTD, T/C, mV, ohms, 2 relays, analogue output | SPA2IS programmable temperature transmitter and alarm trip with intrinsically safe inputs, 2 relays | SPT site-programmable isolated temperature transmitter, T/C, RTD, ohms, mV, 4-20mA or 1-5V | THZ3 dual input HART temperature transmitter for DIN rail, 4-20mA, 12-42DC |
|---|---|---|---|---|
| Type | Programmable temperature transmitter and alarm trip | Programmable temperature transmitter and alarm trip with intrinsically safe field connections | Site-programmable isolated temperature transmitter | Dual input HART temperature transmitter for DIN rail mounting |
| Input | RTD (23 types), T/C (9 types), mV, ohms, potentiometer | RTD (23 types), T/C (9 types), mV, ohms, potentiometer | T/C (all common ISA), 2-, 3- or 4-wire RTD, ohms, mV | Dual sensor, programmable: RTD, T/C, mV, ohms, potentiometer |
| Power | 21.6-375VDC or 90-260VAC | 21.6-125VDC or 90-260VAC | 22-300VDC or 90-260VAC, auto-sensing | 12-42DC, 2-wire, loop powered |
| Housing | DIN-style, 35mm (EN50022) Top Hat DIN rail | DIN-style, 35mm (EN50022) Top Hat DIN rail | DIN-style, 32mm G-type and 35mm Top Hat | DIN rail mount, DIN rail enclosure |
| Display | 5-digit, backlit | 5-digit, backlit | LCD, input in °C or °F | — |
| Stability | Up to 5 years between scheduled calibrations | Up to 5 years between scheduled calibrations | ±0.1% of calibrated span max over six months | — |
Request a price and lead time
SPA2 programmable temperature transmitter and alarm trip, RTD, T/C, mV, ohms, 2 relays, analogue output. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which inputs does the SPA2 accept?
23 RTD types, 9 thermocouple types, mV, resistance and potentiometer devices. Input resolution is 20-bit.
Which alarm types can be set?
High or low trip, out of band, rate of change and stuck input. The relays are configurable as failsafe or non-failsafe, normally open or normally closed.
What does the -AO option add?
A programmable analogue output in any range between 0-20mA and 0-10V, so one unit serves as alarm trip and transmitter.
Similar equipment from other manufacturers