SSX 2-wire HART safety isolator, SIL 3, 4-20 mA
The SSX is a 2-wire isolator powered from the output side of the loop, for safety instrumented systems. It isolates a 4-20 mA signal at 1500 Vrms and passes HART data in both directions. It is exida certified to IEC 61508 for use up to SIL 3 in monitor mode.
- Input
- 4-20 mA
- Output
- 4-20 mA, one analogue output
- Power supply
- 12-42 Vdc, 2-wire, from the output loop
- Input resistance with -IZ250
- 250 ohms
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Part of the FS Functional Safety Series, the SSX draws its power from the output side of the loop, typically from a DCS or PLC, and gives galvanic isolation between input and output. It separates a safety instrumented system (SIS) from the basic process control or monitoring system, so a disconnection or failure there does not reach the safety system. With 1500 Vrms isolation it also protects safety I/O cards from surges, spikes and transients in the field.
The standard SSX/4-20mA/4-20mA/12-42DC has a 4-20 mA input, a 4-20 mA output and a 12-42 Vdc supply. Its loop function is signal isolator, repeater or splitter, with one analogue output. Loop burden is 8.2 V.
HART data pass through the unit in both directions, so diagnostic, process and calibration information can be read on either side, whereas most isolators strip the HART signal. The -0HART option removes the pass-through, -IZ250 sets 250 ohms input resistance, and the -LMD loop maintenance diode lets the unit be taken out of the loop without interrupting the safety function.
The SSX is certified by exida to IEC 61508:2010. It is approved for an SIS up to SIL 3 in monitor mode, where only the input circuit is part of the safety function, and up to SIL 2 in single use. FMEDA data are available on request. Standard RFI/EMI protection is 20 V/m, and the hazardous-area certification is Non-Incendive/Div. 2, Zone 2.
The metal DIN housing snaps onto 35 mm Top Hat or 32 mm G-type rail (EN 50022, EN 50035). The unit is RoHS compliant.
Technical specifications
| Input | 4-20 mA |
|---|---|
| Output | 4-20 mA, one analogue output |
| Power supply | 12-42 Vdc, 2-wire, from the output loop |
| Input resistance with -IZ250 | 250 ohms |
| Loop burden | 8.2 V |
| Isolation | 1500 Vrms |
| HART | data pass-through (-0HART removes it) |
| Option | -LMD, loop maintenance diode |
| Functional safety | IEC 61508:2010, SIL 3 in monitor mode, SIL 2 in single use |
| RFI/EMI protection | 20 V/m |
| Hazardous areas | Non-Incendive/Div. 2, Zone 2 |
| Housing | metal, 35 mm Top Hat or 32 mm G-type DIN rail |
Part numbers
Show all part numbers (1)
SSX/4-20mA/4-20mA/12-42DC [DIN]
How it compares with similar models
| Parameter | SSX 2-wire HART safety isolator, SIL 3, 4-20 mA | STZ dual input HART temperature transmitter for safety systems, SIL 2/3, associated IS | SLD functional safety programmable loop display, 4-20 mA, loop powered | SST functional safety signal isolator and splitter, 4-20mA, HART pass-through |
|---|---|---|---|---|
| Input | 4-20 mA | single or dual, programmable: RTD, thermocouple, ohms, mV, potentiometer | 4-20 mA | 4-20mA |
| Output | 4-20 mA, one analogue output | 4-20 mA, one analogue output | — | 4-20mA (1 analogue output) |
| Power supply | 12-42 Vdc, 2-wire, from the output loop | 12-42 Vdc, 2-wire, from the output loop | from the loop, voltage drop under 2.3 V | — |
| Option | -LMD, loop maintenance diode | -AIS, associated IS input connections | -LMD, loop maintenance diode | — |
| Functional safety | IEC 61508:2010, SIL 3 in monitor mode, SIL 2 in single use | SIL 2/3, IEC 61508 certificate | SIL 3, non-interfering in a safety loop | SIL 3 capable, IEC 61508 certificate |
| Hazardous areas | Non-Incendive/Div. 2, Zone 2 | Associated Intrinsically-Safe, Non-Incendive/Div. 2, Zone 2 | Non-Incendive/Div. 2, Zone 2 | — |
Request a price and lead time
SSX 2-wire HART safety isolator, SIL 3, 4-20 mA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the HART signal pass through the SSX?
Yes. HART diagnostic, process and calibration data pass in both directions, and the -0HART option turns the pass-through off.
Up to which SIL is the SSX approved?
Up to SIL 3 in monitor mode, where only the input circuit is part of the safety function, and up to SIL 2 in single use, under IEC 61508:2010.
Where does the SSX get its power?
From the output side of the loop, typically a DCS or PLC, at 12-42 Vdc.
Similar equipment from other manufacturers