SLD functional safety programmable loop display, 4-20 mA, loop powered
The SLD is a PC-programmable 4-20 mA loop display for functional safety. It shows the signal in mA, percent or 5-character engineering units. It is loop powered with a voltage drop under 2.3 V and has an accuracy of ±0.012% of input scale.
- Input
- 4-20 mA
- Power supply
- from the loop, voltage drop under 2.3 V
- Display
- two rows of large characters; mA, percent or units up to 5 characters
- Accuracy
- ±0.012% of input scale
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Universal and PC-programmable, the SLD belongs to the FS Functional Safety Series. A large integral display shows real-time process status in mA, percent or any designated engineering units of up to 5 characters. The display has two rows of large characters that read clearly in the field and is configured independently. The SLD is assessed for non-interference in a safety loop (SIL 3). It is not SIL 3 assessed for use as part of the safety function.
It reads any 4-20 mA signal with an accuracy of ±0.012% of input scale. The loop supplies the power, with a drop of less than 2.3 V, so the SLD can go onto burdened loops. The -LMD loop maintenance zener diode option allows removal from the loop without interrupting the safety function. Up to 5 years may pass between scheduled calibrations, and a single front-panel button shows loop current in mA to three decimal places for calibration.
Configuration is done through the DTM in any FDT-compliant host such as PACTware, using a USB communication cable. Readings can be scaled to percent or directly to engineering units for pressure, temperature, level or flow, and span, zero, input range, display range and filtering frequency are programmable. The input range limits of the loop can be captured. A square root or linear curve is chosen from the library, or a custom one is created from a table entered in one unit and converted to another by the PC program.
The unit resists radio-frequency and electromagnetic interference. The SLD/4-20mA/PRG/2.3VLP [DN] comes in an HP hockey-puck case with a DIN rail clip, in an explosion-proof BH enclosure or in an SB protective enclosure, and can be mounted at any angle. Hazardous-area certification is Non-Incendive/Div. 2, Zone 2. The unit is RoHS compliant.
Technical specifications
| Input | 4-20 mA |
|---|---|
| Power supply | from the loop, voltage drop under 2.3 V |
| Display | two rows of large characters; mA, percent or units up to 5 characters |
| Accuracy | ±0.012% of input scale |
| Calibration interval | up to 5 years |
| Calibration | button, loop current in mA to three decimal places |
| Configuration | DTM (PACTware, FDT), USB cable |
| Curves | linear, square root, custom |
| Option | -LMD, loop maintenance diode |
| Functional safety | SIL 3, non-interfering in a safety loop |
| Hazardous areas | Non-Incendive/Div. 2, Zone 2 |
| Housing | HP with DIN rail clip; BH, SB |
Part numbers
Show all part numbers (1)
SLD/4-20mA/PRG/2.3VLP [DN]
How it compares with similar models
| Parameter | SLD functional safety programmable loop display, 4-20 mA, loop powered | SSX 2-wire HART safety isolator, SIL 3, 4-20 mA | SFY functional safety frequency-to-current transmitter with display, SIL 3, 4-20 mA | DSX Digital Indicator, 2-wire loop powered, 4-20 mA, 3-1/2 digit LCD |
|---|---|---|---|---|
| Input | 4-20 mA | 4-20 mA | frequency, period, pulse width, contact closure (programmable) | 4-20 mA |
| Power supply | from the loop, voltage drop under 2.3 V | 12-42 Vdc, 2-wire, from the output loop | 12-42 Vdc, 2-wire, loop powered | — |
| Display | two rows of large characters; mA, percent or units up to 5 characters | — | 5-digit LCD, selectable units | LCD, 3-1/2 active digits, 8.9 mm (0.35 in) numerals |
| Accuracy | ±0.012% of input scale | — | ±0.025% of span, typical | ±0.1% of span ±1 count (0-100%) |
| Option | -LMD, loop maintenance diode | -LMD, loop maintenance diode | — | -DZ: fixed dummy zero after the last digit |
| Functional safety | SIL 3, non-interfering in a safety loop | IEC 61508:2010, SIL 3 in monitor mode, SIL 2 in single use | IEC 61508:2010, SIL 2 single use, SIL 3 redundant | — |
Request a price and lead time
SLD functional safety programmable loop display, 4-20 mA, loop powered. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What are the accuracy and voltage drop of the SLD?
Accuracy is ±0.012% of input scale, and the loop powers the unit with a voltage drop under 2.3 V.
Is the SLD part of the safety function?
No. It is assessed for non-interference in a safety loop (SIL 3) and was not SIL 3 assessed as part of the safety function.
How is the SLD configured?
Through the DTM in an FDT-compliant host such as PACTware with a USB communication cable, and a front-panel button handles loop calibration.
Similar equipment from other manufacturers