PSD PC-Programmable Loop Display, 4-20 mA, loop powered
The PSD is a universal 2-wire, loop-powered display for 4-20 mA signals. Its large integral display shows real-time status in mA, percent or any engineering unit of up to 5 characters. Accuracy is ±0.012% of input scale and the loop voltage drop is under 2.3 V.
- Model
- PSD/4-20mA/PRG/2.3VLP [DN]
- Type
- 2-wire loop display, PC-programmable
- Input
- 4-20 mA
- Power
- Loop powered, 2.3 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
PSD/4-20mA/PRG/2.3VLP [DN] is a universal loop display for 4-20 mA signals, programmed from a PC. It is a 2-wire, loop-powered device, so no separate supply is wired. The large integral display shows real-time process status in mA, in percent, or in any designated engineering unit (EGU) of up to 5 characters.
The display reads any 4-20 mA signal to ±0.012% of input scale, which includes linearity, hysteresis, repeatability and adjustment resolution but not ambient temperature effect. The voltage drop is below 2.3 V, so it burdens most loops very little. Minimum operating current is 3.8 mA or more, over-current protection is 100 mA, and the display input overrange is 24 mA. The display range is -99999 to 99999, updated every 100 ms.
The LCD has two rows. The top row has digits 10 mm (0.4 in) high and the bottom row 6 mm (0.23 in). The PC software scales the reading in percent, or directly in units of pressure, temperature, level or flow, and sets zero, input range and the 50 or 60 Hz filter. A custom linearisation curve of 128 points can be stored. One front-panel button shows the loop current in mA to three decimal places for calibration.
The hockey-puck housing has a DIN rail clip and is meant for field-mounted electronics. For hazardous areas the unit is listed Non-Incendive/Div. 2, Zone 2. It is RoHS compliant. Set-up uses the PSD PC Configuration Software, and the -HHT option adds HART handheld configuration.
Technical specifications
| Model | PSD/4-20mA/PRG/2.3VLP [DN] |
|---|---|
| Type | 2-wire loop display, PC-programmable |
| Input | 4-20 mA |
| Power | Loop powered, 2.3 V |
| Accuracy | ±0.012% of input scale |
| Display range | -99999 to 99999 |
| Display update | 100 ms |
| Display | LCD, top row 10 mm (0.4 in), bottom row 6 mm (0.23 in) |
| Units | mA, percent or any EGU up to 5 characters |
| Linearisation | Custom curve up to 128 points |
| Minimum operating current | 3.8 mA or more |
| Housing | Hockey puck with DIN rail clip |
| Alarm/relay | None |
| Hazardous area certification | Non-Incendive/Div. 2, Zone 2 |
| RoHS | Yes |
Part numbers
Show all part numbers (1)
PSD/4-20mA/PRG/2.3VLP [DN]
How it compares with similar models
| Parameter | PSD PC-Programmable Loop Display, 4-20 mA, loop powered | SPD Programmable Field-Mount Loop Display, 4-20 mA, NEMA 4X / IP66 | DSX Digital Indicator, 2-wire loop powered, 4-20 mA, 3-1/2 digit LCD | SLD functional safety programmable loop display, 4-20 mA, loop powered |
|---|---|---|---|---|
| Type | 2-wire loop display, PC-programmable | Programmable field-mount loop display | 2-wire loop-powered digital indicator | — |
| Accuracy | ±0.012% of input scale | ±0.012% of input scale | ±0.1% of span ±1 count (0-100%) | ±0.012% of input scale |
| Display range | -99999 to 99999 | -99999 to 99999 | -19990 to +19990, minimum span 2000 counts | — |
| Display update | 100 ms | 100 ms | 2.5 times per second | — |
| Display | LCD, top row 10 mm (0.4 in), bottom row 6 mm (0.23 in) | LCD, top row 29.21 mm (1.15 in), bottom row 15.24 mm (0.6 in) | LCD, 3-1/2 active digits, 8.9 mm (0.35 in) numerals | two rows of large characters; mA, percent or units up to 5 characters |
| Housing | Hockey puck with DIN rail clip | — | Aluminium hockey puck; variants FL, FLD, 2LG, 2HG, 3LG, 3HG, OTH (NEMA 12) | HP with DIN rail clip; BH, SB |
Request a price and lead time
PSD PC-Programmable Loop Display, 4-20 mA, loop powered. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the PSD need a separate power supply?
No, it is powered from the 4-20 mA loop, with a voltage drop below 2.3 V.
Which units can the display show?
mA, percent, or any engineering unit (EGU) of up to 5 characters.
What are the accuracy and display range?
Accuracy is ±0.012% of input scale, and the display range is -99999 to 99999.