HIM Smart HART Loop Interface and Monitor, 3 Analogue Outputs, 2 Relays
The HIM polls smart HART field devices and provides up to three extra analogue outputs and up to two alarm relays. Relays, analogue outputs and the 5-digit display can each be assigned to any dynamic HART variable.
- Type
- HART loop interface and monitor
- Model
- HIM/HART/3AO/24DC/-2PRG [DIN]
- Input
- HART
- Analogue outputs
- up to 3
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The HIM polls smart HART field devices and provides up to two alarm relay outputs and up to three analogue outputs, plus an integral display. The relay outputs, analogue outputs and display can each be assigned to represent any dynamic HART variable. A typical model is HIM/HART/3AO/24DC/-2PRG in the DIN housing: HART input, three analogue outputs, 24VDC supply and two alarm relays.
The unit is installed across the 4-20mA instrument loop. It reads the HART digital data that is continuously transmitted on the smart transmitter's loop wires and converts it to 4-20mA values. Up to three additional process variables are therefore available from a multivariable transmitter with no additional process penetrations or wiring. The outputs can follow a transmitter's primary, second, third or fourth variable, or user-selectable valve parameters such as stem position.
The two relays are configured individually to respond to high or low process conditions, or to trip when transmitter diagnostics or loop faults are sensed. The HIM can act as a HART primary or secondary master or sit in passive "Listen" mode, and it monitors instruments in either Normal (poll/response) or Burst mode. The large 5-digit display shows a selected variable in engineering units, or toggles between two variables, and indicates HART instrument fault conditions on site. Output channels are isolated.
Set-up is done with a PC program over a USB cable and takes minutes. The HIM works with multivariable mass flow transmitters, dual-sensor temperature transmitters, pressure transmitters, Coriolis, magnetic, ultrasonic and vortex flow meters, pH transmitters, radar and hydrostatic level transmitters, and valve positioners. The compact metal housing mounts on a G-type or Top Hat DIN rail, or on a surface. Approvals: CSA Non-Incendive, Class I, Division 2, Groups A, B, C, D, T5 at 70°C maximum ambient (except -1PRG models), and CE under the EMC Directive 2014/30/EU, EN 61326. The unit is not for use in Safety Instrumented Systems (SIS).
Technical specifications
| Type | HART loop interface and monitor |
|---|---|
| Model | HIM/HART/3AO/24DC/-2PRG [DIN] |
| Input | HART |
| Analogue outputs | up to 3 |
| Alarm relay outputs | up to 2 |
| Power | 4-wire, 24VDC |
| Display | integral, 5-digit |
| Configuration | PC configurable, USB cable |
| Housing | DIN rail housing, G-type and Top Hat |
| Intrinsically-safe input connections | no |
| For use in SIS | no |
| Hazardous area certifications | Non-Incendive/Div. 2, Zone 2 |
| RoHS | compliant |
How it compares with similar models
| Parameter | HIM Smart HART Loop Interface and Monitor, 3 Analogue Outputs, 2 Relays | PSD PC-Programmable Loop Display, 4-20 mA, loop powered | HDM humidity and temperature display module, dual 4-20mA outputs, 12-42DC, IP66 | TRX non-isolated PC-programmable temperature transmitter, 4-20mA output, 8-42DC supply |
|---|---|---|---|---|
| Type | HART loop interface and monitor | 2-wire loop display, PC-programmable | Humidity and temperature display module (part of the HTZ) | non-isolated temperature transmitter, PC-programmable |
| Input | HART | 4-20 mA | Signal from the HSM module: humidity, dew point, RTD | RTD, T/C, mV, Ohms, potentiometer (configurable) |
| Power | 4-wire, 24VDC | Loop powered, 2.3 V | 12-42DC, 2-wire, loop powered | two-wire, loop powered, 8-42DC |
| Display | integral, 5-digit | LCD, top row 10 mm (0.4 in), bottom row 6 mm (0.23 in) | — | none |
| Configuration | PC configurable, USB cable | — | PC, USB cable | from a PC, USB cable |
| Housing | DIN rail housing, G-type and Top Hat | Hockey puck with DIN rail clip | Surface or pipe mount enclosure, NEMA 4X, IP66 | no enclosure, electronics only |
Request a price and lead time
HIM Smart HART Loop Interface and Monitor, 3 Analogue Outputs, 2 Relays. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many analogue outputs and relays does the HIM have?
Up to three analogue outputs and up to two alarm relays; the HIM/HART/3AO/24DC/-2PRG model has three and two.
Do the existing HART devices have to be replaced?
No. The HIM is installed across the 4-20mA loop, reads the HART data and brings out up to three variables with no new process penetrations or wiring.
How is the HIM configured?
With a PC program over a USB cable, as a primary or secondary HART master or in Listen mode, in Normal or Burst mode.
Similar equipment from other manufacturers