SRM safety relay module with contact closure input and three relay outputs, 24 Vdc
The SRM is a relay repeater for safety systems. It takes one contact closure input from a logic solver trip output and gives three process relay outputs and a monitor relay. Supply is 24 Vdc, mounting is on 35 mm DIN rail, and it is certified for SIL 2 single use and SIL 3 redundant use.
- Input
- contact closure from a logic solver trip output
- Outputs
- three relays + monitor relay
- Power supply
- 24 Vdc, 4-wire
- Power consumption
- 1.5-2.3 W
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Part of the FS Functional Safety Series, the SRM is a relay repeater that accepts a single contact closure input from a logic solver trip output. It provides three contacts per alarm input, so alarm contacts for safety processes can be added without special installation or configuration. It was developed to IEC 61508 and is certified by exida.
Inside is a safety-rated relay with forcibly guided contacts, the design used in control and safety systems when the logic must detect the state of the output contacts. A monitor contact is mechanically linked to the same armature as the output contacts, so welded contacts are not missed and the contacts cannot be stuck in normally open and normally closed states at once.
The module has three process relay outputs and a monitor relay. It is powered by 24 Vdc (4-wire) and draws 1.5-2.3 W. Input power and all four relay outputs are fuse protected, and an internal snubbing diode across the input relay coil removes the need for external suppression. Front-panel LEDs show input, output and power status.
exida certifies the SRM to IEC 61508:2010 for single use in an SIS up to SIL 2 and for redundant use up to SIL 3. FMEDA data are provided on request. RF immunity is up to 20 V/m, 20-1000 MHz, tested to IEC 61000-4-3. The module meets the EMC Directive 2014/30/EU (EN61326) and the Low Voltage Directive 2014/35/EU (EN 61010-1), carries Underwriters Laboratories approval (Canada and US) for general locations and is RoHS compliant.
The aluminium housing mounts on 35 mm Top-Hat DIN rail. Pollution degree is 2.
Technical specifications
| Input | contact closure from a logic solver trip output |
|---|---|
| Outputs | three relays + monitor relay |
| Power supply | 24 Vdc, 4-wire |
| Power consumption | 1.5-2.3 W |
| Loop function | safety relay repeater |
| Functional safety | IEC 61508:2010, SIL 2 single use, SIL 3 redundant |
| Protection | fuses on input power and four relay outputs |
| Indication | 3 LEDs: input, output, power |
| RFI protection | 20 V/m, 20-1000 MHz |
| Housing | aluminium, 35 mm Top-Hat DIN rail |
Part numbers
Show all part numbers (1)
SRM/CC/3RO/24DC [DIN]
How it compares with similar models
| Parameter | SRM safety relay module with contact closure input and three relay outputs, 24 Vdc | SSX 2-wire HART safety isolator, SIL 3, 4-20 mA | SFY functional safety frequency-to-current transmitter with display, SIL 3, 4-20 mA | STA programmable safety trip alarm for SIL 2 and SIL 3 systems with two process alarms |
|---|---|---|---|---|
| Input | contact closure from a logic solver trip output | 4-20 mA | frequency, period, pulse width, contact closure (programmable) | — |
| Power supply | 24 Vdc, 4-wire | 12-42 Vdc, 2-wire, from the output loop | 12-42 Vdc, 2-wire, loop powered | — |
| Functional safety | IEC 61508:2010, SIL 2 single use, SIL 3 redundant | IEC 61508:2010, SIL 3 in monitor mode, SIL 2 in single use | IEC 61508:2010, SIL 2 single use, SIL 3 redundant | IEC 61508:2010; systematic up to SIL 3, random up to SIL 2 |
| Housing | aluminium, 35 mm Top-Hat DIN rail | metal, 35 mm Top Hat or 32 mm G-type DIN rail | — | metal, 35mm Top Hat DIN rail |
Request a price and lead time
SRM safety relay module with contact closure input and three relay outputs, 24 Vdc. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the forcibly guided relay in the SRM?
The monitor contact is mechanically tied to the same armature as the output contacts, so welded contacts do not go unnoticed.
Up to which SIL can the SRM be used?
Up to SIL 2 in single use in an SIS and up to SIL 3 in redundant use, under IEC 61508.
What is fuse protected?
The input power and all four relay outputs.