ECT 4-wire signal isolator, converter and splitter, 4-20 mA, 24 Vdc, 1 or 2 outputs
The 24 Vdc ECT takes a 4-20 mA signal and gives one or two 4-20 mA outputs with isolation up to 1500 Vrms. The -TX option adds 24 V excitation for a 2-wire transmitter. Accuracy is ±0.1% and the aluminium housing mounts on DIN rail.
- Input
- 4-20 mA, one input
- Outputs
- 4-20 mA, 1 or 2 outputs
- Power supply
- 24 Vdc, 4-wire
- Isolation
- up to 1500 Vrms, input/output/power
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Low-cost isolation between instruments in a process loop is the job of the ECT, an isolator, converter and splitter in an aluminium DIN-style housing. The ECT/4-20mA/2X4-20mA/24DC/-TX [DIN] is a 4-wire unit powered by 24 Vdc line/mains. It accepts one 4-20 mA input and provides one or two 4-20 mA outputs, so one primary measurement can go to two separate systems and either output loop can be serviced without losing the signal on the other.
Isolation of up to 1500 Vrms between input, output and power stops ground loops, motor noise and other electrical interference and removes common electrical paths between equipment. Accuracy is ±0.1%. The -TX option supplies 24 V excitation to power a 2-wire transmitter connected to the input.
The ECT family also boosts signals so that more instruments can be added to an overburdened loop, resolves "bucking" power supplies where a 4-wire transmitter and a DCS both try to power one loop, steps down dangerous high-voltage signals and cures DCS start-up problems caused by non-isolated transmitters. Input and output are fixed. Humidity may be 0-95%, non-condensing.
Options are -RF (enhanced RFI/EMI filtering), -EM (externally mounted input transformer), -VTD (standard factory calibration with NIST test data report) and FLB2 (externally mounted flange).
It mounts on 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) rails. Strip wires no more than 0.25 in (7 mm) and tighten terminal screws to 5.0-7.0 lbf-in (0.56-0.79 N-m). UL approval is Class I, Division 2, Zone 2 (Non-Incendive/Div. 2), and the unit carries CE and RoHS compliance.
Technical specifications
| Input | 4-20 mA, one input |
|---|---|
| Outputs | 4-20 mA, 1 or 2 outputs |
| Power supply | 24 Vdc, 4-wire |
| Isolation | up to 1500 Vrms, input/output/power |
| Accuracy | ±0.1% |
| -TX option | 24 V excitation for a 2-wire transmitter |
| Set-up | fixed input/output |
| Housing | aluminium, DIN rail |
| Humidity | 0-95%, non-condensing |
| Options | -TX, -RF, -EM, -VTD, FLB2 |
| Rails | 32 mm G-type, 35 mm Top Hat |
| Hazardous areas | UL, Class I, Div. 2, Zone 2 |
Part numbers
Show all part numbers (1)
ECT/4-20mA/2X4-20mA/24DC/-TX [DIN]
How it compares with similar models
| Parameter | ECT 4-wire signal isolator, converter and splitter, 4-20 mA, 24 Vdc, 1 or 2 outputs | ECT-DIN 15 mm signal isolator and converter, 1-5 V to 4-20 mA | HIT HART signal isolator, 4-20 mA, 24 Vdc, DIN rail | SIY PC-programmable signal isolator and converter, input up to 55mA or 11V, 4-20mA output |
|---|---|---|---|---|
| Input | 4-20 mA, one input | 1-5 V | 4-20 mA, one input | programmable, any range within -2.5 to 55mA or -0.5 to 11V |
| Power supply | 24 Vdc, 4-wire | 12-42 Vdc, 2-wire, from the output loop | 24 Vdc, 117 Vac or 230 Vac, 4-wire | — |
| Options | -TX, -RF, -EM, -VTD, FLB2 | -RF, -VTD, -EM, FLB2 | -IZ100, -RF, -TX | — |
| Hazardous areas | UL, Class I, Div. 2, Zone 2 | UL, Class I, Div. 2, Groups A-D, T4; Zone 2 | CSA General Location, Non-Incendive/Div. 2, Zone 2 | — |
Request a price and lead time
ECT 4-wire signal isolator, converter and splitter, 4-20 mA, 24 Vdc, 1 or 2 outputs. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many outputs does this ECT have?
One or two 4-20 mA outputs from a single 4-20 mA input.
What does the -TX option provide?
24 V excitation to power a 2-wire transmitter on the input.
What are the isolation and accuracy?
Isolation up to 1500 Vrms between input, output and power, and accuracy of ±0.1%.