International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SPA2IS Site Programmable Alarm Trip with Built-in Intrinsically Safe Barrier

A site programmable alarm trip classed as associated intrinsically safe equipment. Its intrinsic safety barrier is built into the unit, so temperature sensors and transmitters in Class I Div 1 or Zone 0/1 hazardous areas connect to it directly.

Type
programmable alarm trip
Protection method
associated intrinsically safe equipment (IS)
Intrinsic safety barrier
built in
Sensor connection from zones
Class I Div 1 or Zone 0/1

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Many plants run processes that can create explosive atmospheres, and alarm points located in those areas need to be monitored. When intrinsic safety is chosen as the protection method, a separate barrier is normally needed for every 4-20mA, RTD and TC signal. These barriers are costly, demand considerable engineering effort and take up valuable panel space.

The SPA2IS takes a different route. Its intrinsic safety barrier sits inside the instrument, so it counts as associated IS equipment that can connect straight to temperature elements and transmitters installed in Class I Div 1 or Zone 0/1 hazardous areas. External barriers and the marshalling cabinet that houses them are no longer needed, which saves time and money on the project.

The unit is approved for installation in Class I Div 2/Zone 2 locations. It provides four programmable SPDT relays for alarm and trip duties, plus an optional auxiliary analogue output for passing the signal to a control system or indicator. One device therefore replaces the external barrier and a separate alarm unit, leaving fewer components and connections in the cabinet.

Set-up is carried out with the push buttons on the instrument or with free PC software. The settings cover the input type, the trip set points and the logic that governs the relays. Typical users include oil and gas upstream and downstream operations, power generation and transmission, chemical and specialty chemical plants, pharmaceutical and biotechnology sites, pulp and paper mills, mining and metal refining, water and wastewater treatment works, and food and beverage producers.

Technical specifications

Typeprogrammable alarm trip
Protection methodassociated intrinsically safe equipment (IS)
Intrinsic safety barrierbuilt in
Sensor connection from zonesClass I Div 1 or Zone 0/1
Installation zone of the instrumentClass I Div 2/Zone 2
Input signals4-20mA, RTD, TC
Relay outputsfour programmable SPDT
Analogue outputauxiliary, optional
Programmingpush buttons on the instrument or free PC software

Part numbers

Show all part numbers (1)

SPA2IS

Request a price and lead time

SPA2IS Site Programmable Alarm Trip with Built-in Intrinsically Safe Barrier. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Are external intrinsic safety barriers needed?

No. The barrier is built into the SPA2IS, so sensors in Class I Div 1 or Zone 0/1 areas connect to it directly.

Where can the instrument itself be installed?

The SPA2IS is approved for installation in Class I Div 2/Zone 2 areas.

How many relay outputs does the alarm trip have?

It has four programmable SPDT relays, and an optional auxiliary analogue output is also available.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides