SLA HIPPS 2oo3 Voting Shutdown System for Gas Wellheads, SIL 2/3
A HIPPS system built around the SLA logic solver protects a gas wellhead from pressure surges using 2oo3 voting. The SLA supplies 24 V DC loop power to three HART pressure transmitters and passes their data on to the RTU or PLC.
- Purpose
- high-pressure protection of a gas wellhead (HIPPS)
- Voting logic
- 2oo3
- Safety integrity level
- SIL 2/3
- Standard
- IEC 61508:2010
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Gas wellheads can experience very high pressure and sudden pressure surges. To protect people and equipment, the annulus pressure is monitored, and the well is shut in when conditions turn hazardous. Relay-based pressure switches used to handle this job, but operators now need full safety instrumented systems.
In a HIPPS arrangement, three separate pressure transmitters feed the SLA logic solver, which applies 2oo3 voting and shuts the well in when at least two of the three channels detect a hazardous condition. Each of the three channels on the SLA has a built-in loop power supply that delivers 24 V DC to all three smart HART transmitters, which keeps installation simpler.
The HART signal from each transmitter is retransmitted onto a matching analogue output of the SLA. The RTU or PLC can therefore reach the settings, variables and diagnostics of every instrument directly. Routing the signals through the SLA, rather than passing them through the input cards of the RTU or PLC in sequence, improves the availability of the safety function, because a failure of an analogue input card or of the RTU or PLC itself does not affect the 2oo3 shutdown logic.
Additional relay outputs report the shutdown state and input faults to the RTU or PLC. A discrete contact input allows any latched alarm setpoint or relay to be reset manually. All inputs, outputs, internal equations, variables, alarm setpoints and relay states are passed to the RTU or PLC over MODBUS RTU in read-only mode.
The 2oo3 voting logic is set with tick boxes and drop-down menus, so no programming is needed. The SLA is suitable for SIL 2/3 functions and is certified to conform to IEC 61508:2010. Its ambient operating range of -40 to 85 °C makes it suitable for remote wellheads in the upstream oil and gas sector.
Technical specifications
| Purpose | high-pressure protection of a gas wellhead (HIPPS) |
|---|---|
| Voting logic | 2oo3 |
| Safety integrity level | SIL 2/3 |
| Standard | IEC 61508:2010 |
| Inputs | 3 HART pressure transmitter channels |
| Loop power | 24 V DC per channel, 3 channels |
| HART | pass-through to analogue outputs for the RTU or PLC |
| Digital communication | MODBUS RTU, read-only |
| Relay outputs | shutdown state, input faults |
| Discrete input | manual reset of latched setpoints and relays |
| Configuration | tick boxes and drop-down menus |
| Ambient temperature | -40 to 85 °C |
Request a price and lead time
SLA HIPPS 2oo3 Voting Shutdown System for Gas Wellheads, SIL 2/3. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What happens to the shutdown function if the PLC or RTU fails?
Nothing changes for the shutdown. The SLA retransmits the transmitter signals and runs the 2oo3 logic itself, so a failed input card or PLC does not affect the shutdown.
Are separate power supplies needed for the pressure transmitters?
No. Each of the three channels on the SLA has a built-in 24 V DC loop power supply.
What data does the SLA send to the control system?
Over MODBUS RTU in read-only mode it passes all inputs, outputs, equations, variables, alarm setpoints and relay states, while transmitter HART data goes through the analogue outputs.