SDY PC-programmable signal isolator and converter with display, 4-20 mA output
The SDY accepts a current or voltage signal and gives an isolated, proportional 4-20 mA output. It is 2-wire loop powered at 10-42 Vdc, has a large display and is set up from a PC over USB. Custom linearisation tables hold up to 85 points.
- Input
- programmable: any range within -2.5 to 55 mA or -0.5 to 11 V
- Current ranges
- 0-20, 4-20, 0-50, 10-50 mA
- Voltage ranges
- 0-1, 0-5, 1-5, 0-10 Vdc
- Output
- 4-20 mA, isolated, scalable
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A 2-wire, PC-programmable isolator and converter with an integral display, the SDY takes a wide range of current or voltage inputs and outputs an isolated, proportional 4-20 mA current. It programs in seconds. The input can be set to any range within -2.5 to 55 mA or -0.5 to 11 V, and the standard choices are 0-20, 4-20, 0-50 and 10-50 mA for current and 0-1, 0-5, 1-5 and 0-10 Vdc for voltage.
It monitors signals on a large display, isolates signals to stop erratic measurements caused by ground loops, and converts them so field instruments can interface with an indicator, recorder, DCS, PLC or SCADA system. It can also divert the output of one transmitter to two locations, protect equipment by removing common electrical paths, boost signals for an overburdened loop and cure "bucking" power supplies.
The display has two rows of large characters that can show any engineering unit, and it updates eight times per second. A custom linearisation table of up to 85 points converts non-linear inputs such as transducers, odd-shaped tank levels and flow meters. Output damping, output scaling, output and input trimming and a 50 or 60 Hz noise filter are also set in software. Error is as low as ±0.09% over one year and ±0.20% over five years.
Opto isolation between input and output guards against ground loops and plant noise, and the unit resists radio-frequency and electromagnetic interference. All set-up is done on one screen of the PC configuration software through a USB cable.
Housings include the HP hockey-puck case with a DIN rail clip (DN), the BH explosion-proof enclosure and the D-BOX NEMA 4X enclosure, and an -IS version exists. Supply is 10-42 Vdc, or 10-30 Vdc for SDY/PRG/4-20MA/10-30DC/-IS [BH2NG]. The unit is RoHS compliant and meets EN 61326.
Technical specifications
| Input | programmable: any range within -2.5 to 55 mA or -0.5 to 11 V |
|---|---|
| Current ranges | 0-20, 4-20, 0-50, 10-50 mA |
| Voltage ranges | 0-1, 0-5, 1-5, 0-10 Vdc |
| Output | 4-20 mA, isolated, scalable |
| Power supply | 10-42 Vdc, 2-wire, from the output loop |
| Display | two rows of large characters, any units |
| Display update | eight times per second |
| Linearisation | custom table up to 85 points |
| Stability | ±0.09% over 1 year; ±0.20% over 5 years |
| Noise filter | 50 or 60 Hz |
| Set-up | PC, USB cable |
| Housings | HP with DIN clip (DN), BH, D-BOX NEMA 4X |
Part numbers
Show all part numbers (2)
SDY/PRG/4-20mA/10-42DC [DN], SDY/PRG/4-20MA/10-30DC/-IS [BH2NG]
How it compares with similar models
| Parameter | SDY PC-programmable signal isolator and converter with display, 4-20 mA output | SIY PC-programmable signal isolator and converter, input up to 55mA or 11V, 4-20mA output | FDY PC-Programmable 2-Wire Frequency-to-DC Transmitter with Display, 4-20 mA Output | SFY functional safety frequency-to-current transmitter with display, SIL 3, 4-20 mA |
|---|---|---|---|---|
| Input | programmable: any range within -2.5 to 55 mA or -0.5 to 11 V | programmable, any range within -2.5 to 55mA or -0.5 to 11V | — | frequency, period, pulse width, contact closure (programmable) |
| Output | 4-20 mA, isolated, scalable | 4-20mA, isolated | 4-20 mA, isolated, scaleable | 4-20 mA, isolated, scalable |
| Display | two rows of large characters, any units | — | 5-digit LCD, selectable engineering units | 5-digit LCD, selectable units |
Request a price and lead time
SDY PC-programmable signal isolator and converter with display, 4-20 mA output. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which inputs does the SDY support?
Any range within -2.5 to 55 mA or -0.5 to 11 V, including 0-20, 4-20, 0-50 and 10-50 mA and 0-1, 0-5, 1-5 and 0-10 Vdc.
How many points can a custom linearisation table hold?
Up to 85 points, used for non-linear transducers, odd-shaped tank levels and flow meter linearisation.
What are the stability and supply?
Error is as low as ±0.09% over one year and ±0.20% over five years, and the unit is loop powered at 10-42 Vdc.
Similar equipment from other manufacturers