SCX 2-Wire Signal Current Isolator and Converter, 4-20mA
The SCX takes a 4-20mA current signal from a transmitter and returns a proportional, isolated 4-20mA output. It is powered from the process loop on the input side, with ±0.075% of span linearity and 500Vrms transformer isolation.
- Type
- signal current isolator, 2-wire
- Input
- 4-20mA (also 10-50mA)
- Output
- 4-20mA, proportional to input
- Power
- current loop, input side
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A transmitter or other current source feeds a 4-20mA signal to the SCX, and the isolator passes a proportional 4-20mA signal on to the receiving device. A 10-50mA input is also available. Total isolation between the two stops ground loops and other electrical interference from producing faulty readings in process measurement and control equipment.
The input side of the SCX is loop-powered, so no dedicated power supply is needed. Input and output are transformer isolated at 500Vrms, with no dc connection between them. A Zener diode limits the maximum voltage drop across the unit if the output load is accidentally disconnected. Output impedance should not exceed 250 ohms for 4-20mA under any condition, and with an open output circuit the input loop voltage drop is limited to 15 volts.
Calibration linearity is ±0.075% of span and maximum output ripple is 10 mV peak to peak, which allows a precise interface to computer-based systems. Burden is 5.5V with the outputs shorted for 4-20mA inputs and 10.5V with a 250 ohm load. If the input fails, the output follows the input below 3mA. An external multiturn potentiometer trims the output span by ±1%. The ambient temperature range is -29°C to +82°C and the unit weighs 141.5 grams.
The SCX comes in a high-density DIN-style housing and in a hockey-puck housing that field-mounts in an explosion-proof enclosure. The HP and DIN versions carry FM, CSA, UL, ATEX (ISSeP) and ANZEx approvals, including the markings II 2 G Ex d IIC T6 Gb and Ex d IIC T6 (Tamb 60°C), with NEMA 4X and IP66 enclosure ratings.
Technical specifications
| Type | signal current isolator, 2-wire |
|---|---|
| Input | 4-20mA (also 10-50mA) |
| Output | 4-20mA, proportional to input |
| Power | current loop, input side |
| Calibration capability (linearity) | ±0.075% of span |
| Input-to-output isolation | transformer, 500Vrms |
| Output ripple | 10 mV P/P maximum |
| Output load | 250 ohms maximum |
| Burden | 5.5V with outputs shorted; 10.5V with 250 ohm load |
| Trim | output span ±1%, external multiturn potentiometer |
| Ambient temperature range | -29°C to +82°C |
| Weight | 141.5 grams |
How it compares with similar models
| Parameter | SCX 2-Wire Signal Current Isolator and Converter, 4-20mA | SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation | FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing | ECT 4-20mA/4-20mA/5.5VLP 2-Wire Input-Loop-Powered Signal Isolator and Converter |
|---|---|---|---|---|
| Type | signal current isolator, 2-wire | Signal isolator, converter and repeater, 2-wire | Signal converter and isolator, 4-wire | Signal isolator and converter, 2-wire |
| Input | 4-20mA (also 10-50mA) | 1-5 V | 0-20 mA, 4-20 mA (50 ohms); 0-50 mA, 10-50 mA (20 ohms); 0-1 V, 0-5 V, 1-5 V (1 megohm); 0-10 V (2 megohms) | 4-20 mA, fixed |
| Output | 4-20mA, proportional to input | 4-20 mA | 0-20 mA, 4-20 mA into 0-1200 ohms; 0-1 V, 0-5 V, 1-5 V into 20K ohms minimum; 0-10 V into 40K ohms minimum | 4-20 mA, fixed |
| Power | current loop, input side | 12-42 V DC, loop powered | Universal: 90-260 Vac or 22-300 Vdc; 3.5 W nominal, 5 W maximum | — |
Request a price and lead time
SCX 2-Wire Signal Current Isolator and Converter, 4-20mA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the SCX need a separate power supply?
No. It is loop-powered on the input side, so no dedicated supply is required.
What is the maximum output load?
Output impedance should not exceed 250 ohms for 4-20mA; with an open output circuit the input loop voltage drop is limited to 15 volts.
What does the output do if the input fails?
With a 4-20mA input and 4-20mA output, the output follows the input below 3mA when the input fails.