PWT AC watt transducer for RMS active power, 4 to 20 mA output
The PWT monitors RMS active power and reports it in watts. The PWT/120AC,5A/4-20mA/2E [SM] model takes 120 V AC and 5 A, gives 4 to 20 mA, has two elements for a 3-phase, 3-wire system and is powered from the measured circuit.
- Model
- PWT/120AC,5A/4-20mA/2E [SM]
- Type
- AC watt transducer, RMS active power
- Voltage input
- 120 V AC
- Current input
- 5 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The PWT continuously tracks the amount of power consumed by an electric device or system and reads it as RMS (root mean square) active power in watts. It gives a proportional milliamp output for judging equipment power use and operating efficiency.
The PWT/120AC,5A/4-20mA/2E [SM] model has a 120 V AC voltage input, a 5 A current input and a 4 to 20 mA output. It uses a 2-element measurement arrangement for 3-phase, 3-wire systems. It is self powered, drawing its operating energy from the measured circuit, and comes in a surface-mount housing (SM).
True RMS values of voltage and current are measured, so the watt reading is computed with high accuracy: ±0.2% of reading. Full input to output isolation removes the errors that ground loops introduce. Output ripple stays below 0.5% of full scale, and the response time is below 100 ms to 90% and below 200 ms to 99%.
The housing is rustproof extruded aluminium that sheds heat well. Keyhole cut-outs let the unit be taken off and refitted just by loosening the screws, and all circuitry is attached to the front panel so the boards slide out without removing the whole case.
The ambient range is -20 °C to +70 °C, the operating frequency is 60 Hz as standard, and the dielectric test is 2000 V RMS for one minute. The unit is UL approved.
Technical specifications
| Model | PWT/120AC,5A/4-20mA/2E [SM] |
|---|---|
| Type | AC watt transducer, RMS active power |
| Voltage input | 120 V AC |
| Current input | 5 A |
| Output | 4 to 20 mA |
| Measurement elements | 2 elements, 3-phase, 3-wire |
| Power source | Self powered from the measured circuit |
| Housing | Surface mount (SM), extruded aluminium |
| Accuracy | ±0.2% of reading |
| Operating frequency | 60 Hz standard |
| Ambient range | -20 °C to +70 °C |
| Dielectric test | 2000 V RMS for one minute |
| Response time | To 90% below 100 ms; to 99% below 200 ms |
| Certification | UL Approved |
Part numbers
Show all part numbers (2)
PWT/120AC, 5A/4-20mA/2E [SM]
How it compares with similar models
| Parameter | PWT AC watt transducer for RMS active power, 4 to 20 mA output | PVT VAR transducer for RMS reactive power, 4-20MAB output | PAC AC current transducer, 1 A input, 0 to 1 mA DC output | PWV combined watt/VAR transducer for RMS active and reactive power |
|---|---|---|---|---|
| Type | AC watt transducer, RMS active power | VAR transducer, RMS reactive power | AC current transducer, single configuration | Watt/VAR transducer |
| Voltage input | 120 V AC | 120 V AC | — | 69 V AC |
| Output | 4 to 20 mA | 4-20MAB | 0 to 1 mA DC | 4 to 20 mA |
| Measurement elements | 2 elements, 3-phase, 3-wire | 2 elements, 3-phase, 3-wire | — | 3 elements, 3-phase, 4-wire |
| Housing | Surface mount (SM), extruded aluminium | Surface mount (SM), aluminium | DIN rail (DM), extruded aluminium | DIN rail (DM) |
Request a price and lead time
PWT AC watt transducer for RMS active power, 4 to 20 mA output. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What does the PWT measure?
RMS active power of an AC circuit in watts, with a 4 to 20 mA output.
Which network does this model suit?
A 3-phase, 3-wire system, with 2 measurement elements, 120 V AC and 5 A inputs.
Does it need a separate supply?
No, it is self powered from the measured circuit.