PVT VAR transducer for RMS reactive power, 4-20MAB output
The PVT measures RMS reactive power with high accuracy. The PVT/120AC,5A/4-20MAB/2E [SM] model takes 120 V AC and 5 A, gives a 4-20MAB output, has two elements for a 3-phase, 3-wire system and uses a surface-mount housing.
- Model
- PVT/120AC,5A/4-20MAB/2E [SM]
- Type
- VAR transducer, RMS reactive power
- Voltage input
- 120 V AC
- Current input
- 5 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The PVT is a VAR transducer that measures RMS (root mean square) reactive power. It is a high-accuracy unit, and all transducers of this range are enclosed in aluminium housings.
The PVT/120AC,5A/4-20MAB/2E [SM] model has a 120 V AC voltage input, a 5 A current input and a 4-20MAB output. It uses a 2-element arrangement for 3-phase, 3-wire systems and is self powered.
The housing is surface mount (SM). No 2-inch pipe-mount bracket is provided.
Used alongside the PWT active power transducer, this unit allows the active and reactive parts of a load to be monitored separately.
Reactive power is measured from the RMS values of voltage and current, so the transducer suits the monitoring of the reactive part of the load of motors, transformers and other inductive consumers. The 4-20MAB output passes the value to a controller or recorder.
Two measurement elements work in a 3-phase, 3-wire network. The unit is self powered and needs no separate supply. The 120 V AC and 5 A inputs are set by the model code, and the surface-mount housing fixes to a flat surface.
Technical specifications
| Model | PVT/120AC,5A/4-20MAB/2E [SM] |
|---|---|
| Type | VAR transducer, RMS reactive power |
| Voltage input | 120 V AC |
| Current input | 5 A |
| Output | 4-20MAB |
| Measurement elements | 2 elements, 3-phase, 3-wire |
| Power | Self powered |
| Housing | Surface mount (SM), aluminium |
| 2-inch pipe-mount bracket | No |
| Certification | UL Approved |
Part numbers
Show all part numbers (2)
PVT/120AC, 5A/4-20MAB/2E [SM]
How it compares with similar models
| Parameter | PVT VAR transducer for RMS reactive power, 4-20MAB output | PWV combined watt/VAR transducer for RMS active and reactive power | PWT AC watt transducer for RMS active power, 4 to 20 mA output | PPA phase angle transducer for voltage and current, bipolar 4 to 20 mA output |
|---|---|---|---|---|
| Type | VAR transducer, RMS reactive power | Watt/VAR transducer | AC watt transducer, RMS active power | Phase angle transducer |
| Voltage input | 120 V AC | 69 V AC | 120 V AC | — |
| Output | 4-20MAB | 4 to 20 mA | 4 to 20 mA | 4-20MAB |
| Measurement elements | 2 elements, 3-phase, 3-wire | 3 elements, 3-phase, 4-wire | 2 elements, 3-phase, 3-wire | — |
| Housing | Surface mount (SM), aluminium | DIN rail (DM) | Surface mount (SM), extruded aluminium | Surface mount (SM), aluminium |
Request a price and lead time
PVT VAR transducer for RMS reactive power, 4-20MAB output. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What does the PVT measure?
RMS reactive power.
Which network does this model suit?
A 3-phase, 3-wire system, with 2 measurement elements and 120 V AC and 5 A inputs.
What is its output?
4-20MAB.