International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

PPA phase angle transducer for voltage and current, bipolar 4 to 20 mA output

The PPA measures the phase angle between a voltage and a current from a single- or three-phase circuit, or between two voltages. The PPA/120AC,120AC/4-20MAB/180 [SM] model has two 120 V AC inputs, a 4-20MAB output, self-powered operation and a surface-mount housing.

Model
PPA/120AC,120AC/4-20MAB/180 [SM]
Type
Phase angle transducer
Input
Voltage and voltage: 120 V AC, 120 V AC
Output
4-20MAB

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The PPA precisely measures the phase angle between a voltage and a current input from a single- or three-phase power circuit, and between two isolated voltage circuits. It accepts two voltage inputs or a voltage and a current, and provides a current output that is linear with the phase angle.

The PPA/120AC,120AC/4-20MAB/180 [SM] model has two 120 V AC voltage inputs and a 4-20MAB output. It is self powered and fitted in a surface-mount housing (SM). Input, output and operating power are configured at the factory from the available settings.

The output may be bipolar to show both leading and lagging angles, or unipolar for one of them only. The unit has full four-quadrant capability, with phase angle spans from +30° to +180°. Accuracy is ±0.5° of phase angle, which helps, for example, when synchronising two voltages across an open breaker.

A single internal jumper sets the unit for single- or three-phase operation, covering 2-, 3- or 4-wire power systems. Power is derived from the measured input; versions with auxiliary AC power, or DC power in series with the output, are also offered. Voltage inputs are 69 V (50 to 90 V), 120 V (85 to 150 V) and 240 V (170 to 300 V), and current inputs are 1 A, 2 A and 5 A.

Options include DSP, a 3.5-digit LCD showing the phase angle in degrees; MG, a relay contact output with LEDs showing the direction of current flow for a motor or generator, which needs one voltage and one current input; and RO, a reverse output. Zero and span adjustments are provided, along with an optional terminal safety cover. The housing is aluminium.

Technical specifications

ModelPPA/120AC,120AC/4-20MAB/180 [SM]
TypePhase angle transducer
InputVoltage and voltage: 120 V AC, 120 V AC
Output4-20MAB
Designation in model code180
PowerSelf powered
HousingSurface mount (SM), aluminium
2-inch pipe-mount bracketNo
Phase angle accuracy±0.5°
Phase angle spans+30° to +180°
Systems2-, 3- and 4-wire, single- and three-phase
OptionsDSP, MG, RO

Part numbers

Show all part numbers (2)

PPA/120AC, 120AC/4-20MAB/180 [SM]

How it compares with similar models

ParameterPPA phase angle transducer for voltage and current, bipolar 4 to 20 mA outputPVT VAR transducer for RMS reactive power, 4-20MAB outputPAV AC voltage transducer, 0 to 90 V AC input, 0 to 1 mA outputPWV combined watt/VAR transducer for RMS active and reactive power
TypePhase angle transducerVAR transducer, RMS reactive powerAC voltage transducer, single configurationWatt/VAR transducer
Output4-20MAB4-20MAB0 to 1 mA DC4 to 20 mA
HousingSurface mount (SM), aluminiumSurface mount (SM), aluminiumDIN rail (DM)DIN rail (DM)

Request a price and lead time

PPA phase angle transducer for voltage and current, bipolar 4 to 20 mA output. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What does the PPA measure?

The phase angle between a voltage and a current of a single- or three-phase circuit, or between two voltages.

How accurate is it?

±0.5° of phase angle.

Which options are available?

DSP (display in degrees), MG (contact output and LEDs for current direction) and RO (reverse output).