PAC AC current transducer, 1 A input, 0 to 1 mA DC output
The PAC accepts an AC current input and returns a DC current output accurate to ±0.25% of rated output. The PAC/1A/0-1mA/S [DM] model has a 1 A input, a 0 to 1 mA output, self-powered operation and a DIN-rail housing.
- Model
- PAC/1A/0-1mA/S [DM]
- Type
- AC current transducer, single configuration
- Input
- 1 A AC
- Output
- 0 to 1 mA DC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The PAC AC current transducer accepts an AC current input and provides a highly accurate DC current output, ±0.25% of rated output. It responds to the average value of the input signal and is calibrated to indicate the RMS value.
The PAC/1A/0-1mA/S [DM] model is a single-configuration unit with a 1 A input and a 0 to 1 mA output. It is self powered, deriving its energy from the monitored circuit, and sits in a DIN-rail housing (DM). Single models are also offered with auxiliary power from an external source, and triple-channel versions share one housing.
The transducer monitors the electrical consumption of load devices such as motors and heaters, measures the output of source devices such as transformers and generators, and can trigger an alarm when the current leaves a safe range. Surge limiters protect both the input and the output.
The housing is rustproof extruded aluminium with keyhole cut-outs for removal by loosening the screws. Multiturn potentiometers set the adjustments: span ±10% of rated output and zero ±2% (4 to 20 mA output), or +2% and 0% with a 1 mA output. A single-configuration unit weighs 295 g.
The ambient range is -20 °C to +70 °C, the frequency is 60 Hz and the dielectric test is 2000 V RMS for one minute. Response time is below 200 ms to 90% and below 400 ms to 99%. The self-powered burden is 0.5 VA.
Technical specifications
| Model | PAC/1A/0-1mA/S [DM] |
|---|---|
| Type | AC current transducer, single configuration |
| Input | 1 A AC |
| Output | 0 to 1 mA DC |
| Power | Self powered |
| Housing | DIN rail (DM), extruded aluminium |
| Accuracy | ±0.25% of rated output |
| Frequency | 60 Hz |
| Self-powered burden | 0.5 VA |
| Ambient range | -20 °C to +70 °C |
| Response time | To 90% below 200 ms; to 99% below 400 ms |
| Dielectric test | 2000 V RMS for one minute |
| Weight, single configuration | 295 g |
| Certification | UL Approved |
Part numbers
Show all part numbers (1)
PAC/1A/0-1mA/S [DM]
How it compares with similar models
| Parameter | PAC AC current transducer, 1 A input, 0 to 1 mA DC output | PAV AC voltage transducer, 0 to 90 V AC input, 0 to 1 mA output | PWT AC watt transducer for RMS active power, 4 to 20 mA output | PVT VAR transducer for RMS reactive power, 4-20MAB output |
|---|---|---|---|---|
| Type | AC current transducer, single configuration | AC voltage transducer, single configuration | AC watt transducer, RMS active power | VAR transducer, RMS reactive power |
| Output | 0 to 1 mA DC | 0 to 1 mA DC | 4 to 20 mA | 4-20MAB |
| Housing | DIN rail (DM), extruded aluminium | DIN rail (DM) | Surface mount (SM), extruded aluminium | Surface mount (SM), aluminium |
| Accuracy | ±0.25% of rated output | ±0.25% of rated output | ±0.2% of reading | — |
Request a price and lead time
PAC AC current transducer, 1 A input, 0 to 1 mA DC output. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How accurate is the PAC?
±0.25% of rated output.
Does it need a separate supply?
No, the S version is self powered from the monitored circuit.
Which other configurations exist?
Single and triple; single models are also offered with auxiliary power.