LDH Series Duct Air Heaters with WATROD Elements, up to 600 V and 225 kW
LDH series duct heaters for air heating systems that run without excess pressure. WATROD tubular elements, 11 mm (0.430 in) across, sit on a 6 mm steel flange, and catalogue ratings reach 225 kW at 600 V with process temperatures up to 650 °C.
- Heating element diameter
- 11 mm (0.430 in)
- Flange
- steel, 6 mm (1/4 in)
- Sheath material
- alloy 840
- Element insulation
- compacted MgO
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
LDH heaters are installed in the ducts of drying ovens, heat-treatment and industrial furnaces, ventilation and air conditioning systems, load banks, paint-drying chambers, autoclaves and reheating systems. They suit a wide range of combinations of temperature and air flow. An electric duct heater needs no chimney or fuel lines, and all the energy it draws is converted into heat.
The structure consists of tubular heating elements, WATROD type, 11 mm (0.430 in) in diameter, mounted on a steel flange 6 mm (1/4 in) thick. The resistance coil sits inside an alloy 840 sheath, which resists corrosion and oxidation and keeps the coil clean. The space inside the element is filled with magnesium oxide compacted to a very high density, and rigid stainless steel supports stop the elements from sagging or deforming.
In the modular version, individual modules can be withdrawn through the assembly housing without dismantling the whole heater from the duct, and single elements can be replaced, which shortens downtime. The modular layout also speeds up the response to load changes and reduces the ingress of heated air into the electrical box.
The surface loading reaches 6.2 W/cm² (40 W/in²), and the recommended operating window is between -29 and 650 °C, or -20 and 1200 °F. Catalogue ratings go up to 225 kW at 600 V AC, and the current per circuit is limited to 48 A. The components are UL recognised (file E52951) and CSA recognised (file 31388), and installation follows the National Electrical Code.
The D series, offered alongside LDH, includes a thermowell of 6 mm (1/4 in) inside diameter, where a J or K type thermocouple can read the sheath temperature. Its silicone seals are rated to 105 °C (221 °F). The flange mounting holes are 9.5 mm (3/8 in) across.
Technical specifications
| Heating element diameter | 11 mm (0.430 in) |
|---|---|
| Flange | steel, 6 mm (1/4 in) |
| Sheath material | alloy 840 |
| Element insulation | compacted MgO |
| Power density | 6.2 W/cm² (40 W/in²) |
| Process temperature | between -29 and 650 °C, or -20 and 1200 °F |
| Catalogue ratings | up to 225 kW |
| Voltage | up to 600 V AC |
| Current per circuit | limited to 48 A |
| Mounting hole diameter | 9.5 mm (3/8 in) |
| Component recognition | UL (E52951), CSA (31388) |
| Medium | air without excess pressure |
Request a price and lead time
LDH Series Duct Air Heaters with WATROD Elements, up to 600 V and 225 kW. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can an element be replaced without removing the heater from the duct?
Yes. The modules can be withdrawn through the assembly housing and individual elements replaced, so the whole heater does not need to come out of the duct.
What is the maximum process temperature?
The recommended window extends to 650 °C, which is 1200 °F. The alloy 840 sheath resists corrosion and oxidation.
Can a thermocouple be fitted to monitor the sheath?
The D series includes a 6 mm inside-diameter thermowell, and a J or K type thermocouple placed in it reads the sheath temperature.