HES HART-to-Ethernet Gateway for Multi-Drop Transmitters, up to 64 HART Devices

The HES gateway collects process and diagnostic data from smart HART instruments and passes it to an Ethernet network through a built-in web server, MODBUS/TCP or HART-IP. It works with HART 5, 6 and 7 devices and can power a multi-drop instrument loop.

Type
HART to Ethernet gateway
Compatible devices
HART 5, 6 and 7
Number of devices
up to 64 HART devices
Configurations
single-channel, four-channel

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The HES is used where an Ethernet-based control system must be linked to HART field instruments: in upstream and downstream oil and gas, power generation, chemicals, semiconductor production, pharmaceuticals, pulp and paper, mining and metal refining, water treatment, food and beverage, and data centres. The gateway takes both measured process variables and diagnostic data from the instruments.

The gateway is compatible with all HART 5, 6 and 7 instruments, including smart valves, multivariable flowmeters, and pressure, pH, level and temperature transmitters. Collected data is available through the built-in web server and to MODBUS/TCP and HART-IP hosts. Configuration is carried out through FDT/DTM.

The HES comes in single-channel and four-channel versions, and the four-channel version supports up to 64 HART instruments. An embedded power supply powers instruments wired in a multi-drop arrangement over a single twisted pair. This matters at remote sites where power sources are scarce.

In one example, an oil and gas company needed to collect data from dozens of radar level meters at a field while also powering them, because power sources at the site were limited. Six level meters on loop power were connected to each single-channel HES in a multi-drop arrangement, with power supplied from the gateway's built-in source. Process and diagnostic data went over MODBUS/TCP to the base process control system (BPCS) for control, data collection and monitoring.

When specifying the unit, define the number of channels, the number of HART instruments on the line, the host protocols required, and whether instrument power must come from the gateway.

Technical specifications

TypeHART to Ethernet gateway
Compatible devicesHART 5, 6 and 7
Number of devicesup to 64 HART devices
Configurationssingle-channel, four-channel
Host protocolsMODBUS/TCP, HART-IP
Web serverbuilt-in
ConfigurationFDT/DTM
Instrument powerbuilt-in supply for a multi-drop loop over one twisted pair
Dataprocess variables and instrument diagnostics
Host connectionEthernet-based systems (BPCS)

Request a price and lead time

HES HART-to-Ethernet Gateway for Multi-Drop Transmitters, up to 64 HART Devices. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many HART instruments can be connected?

The four-channel version supports up to 64 HART instruments, and a single-channel version is also available for a multi-drop loop.

Which protocols carry the data?

MODBUS/TCP, HART-IP and the built-in web server; configuration is done through FDT/DTM.

Can the gateway power field instruments?

Yes. The built-in supply powers HART instruments wired in a multi-drop arrangement over a single twisted pair.