International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

HCS HART to Modbus RTU Gateway for Intrinsically Safe Loops, up to 16 Instruments

The HCS polls between one and 16 HART instruments wired in multidrop mode on a single twisted pair, and passes their data on as Modbus RTU. The gateway itself is approved for Class I Div 2 and Zone 2 locations, while the field loop runs through one intrinsically safe barrier.

Type
HART to Modbus RTU concentrator (gateway)
HART instruments
1 to 16 in multidrop mode
Output protocol
Modbus RTU
Physical layer
RS-232 or RS-485

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Oil and gas production and transport sites contain explosive gases and vapours, so the field wiring and instruments must meet Class I Div 1 requirements. Running a separate twisted pair through its own barrier to every sensor, or in rigid conduit, makes each measuring point expensive.

The HCS lowers the cost per point by using the digital signal of HART. The protocol allows several instruments on one twisted pair. Instead of a pair and barrier for each device, one HCS and one IS barrier serve the loop, with transmitters connected in parallel in multidrop mode. The HCS accepts up to 16 such instruments, although the practical number depends on the power the intrinsically safe barrier can pass into the field zone.

The gateway polls the HART instruments in turn and converts their data to Modbus RTU. A local RTU or controller then reads every instrument on the loop through a single Modbus interface. The physical layer is RS-232 or RS-485.

The HCS is approved for installation in Class I Div 2 and Zone 2 locations, and its ambient operating temperature runs from -40 to 85 °C, which suits cabinets on open sites. Configuration uses a free Windows PC program and takes only a few minutes.

Besides oil and gas, the concentrator arrangement is used in refineries and chemical plants, power generation, mining and metal refining, water treatment, pulp and paper and food production. It suits any site where many HART transmitters sit far from the control room and separate cables to each one would be costly.

Technical specifications

TypeHART to Modbus RTU concentrator (gateway)
HART instruments1 to 16 in multidrop mode
Output protocolModbus RTU
Physical layerRS-232 or RS-485
Approval for installationClass I Div 2 / Zone 2
Field loopOne twisted pair through an IS barrier; Class I Div 1
Operating temperature-40 to 85 °C
ConfigurationFree Windows PC program

Part numbers

Show all part numbers (1)

HCS

Request a price and lead time

HCS HART to Modbus RTU Gateway for Intrinsically Safe Loops, up to 16 Instruments. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many HART instruments can one HCS serve?

Up to 16 in multidrop mode on one pair. The practical count depends on how much power the intrinsically safe barrier passes into the field zone.

Can the gateway be installed in a hazardous area?

The HCS is approved for Class I Div 2 and Zone 2 locations. Field instruments in Div 1 are connected through an IS barrier.

Which interfaces does the gateway offer for the RTU?

Modbus RTU over RS-232 or RS-485.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides